background image

Heating

CLOSED

OPEN

terminal box

Control voltages

to

Potential equation

(on site)

Control voltages

230 V AC or 24 V AC/DC

Cable

Cable

Fire damper

CLOSED OPEN

Control voltages

230 V AC or 24 V AC/DC

Cable

Cable

CLOSED

OPEN

CLOSED OPEN

Fire damper

white

white

white

green

green

brown

brown

white

white

white

green

green

brown

brown

User Manual 5.02 (2016-10)

 13

Subject to change

Series FK120

FK90 fire dampers

Electrical connections, installation, functional testing, servicing

Actuators EM-1, EM-2 and RM-1

Actuators M220-7, M24-7

Limit switches

 on thermal-mechanical release mechanisms

The  CLOSED  limit  switches  are  actuated  when  the  fire  damper  is  closed,  and  the  OPEN 

 

limit switches are actuated when the fire damper is open.

Limit switch not actuated

Limit switch actuated

Actuators M220-9/V, M24-9/V

Remote release

E-Ex limit switch

Installation

  FK90  fire  dampers,  series  FK120,  must  be  installed  based 

on  the  instructions  in  this  user  manual.  The  technical 

 

regulations and national statutory regulations must be obser

-

ved during installation.

  In  Germany,  this  means  the  “Technical  Building  Regulations”

 

(VV TB) and the "Guideline on Fire Protection Requirements 

Pertaining to Ventilation Systems" (Lüftungsanlagenrichtlinie - 

LüAR).

  FK90  fire  dampers  meet  these  requirements  and  generally 

recognised technical regulations.

 

Electric wiring

 must be installed by the customer.

 

Potential equalisation conductors

  to  bridge  flexible 

 

connection  pieces  on  fire  dampers  can  be  fastened 

with  metal  screws  if  they  are  made  of  copper  up  to  a 

 

cross-section of 6 mm² or made of aluminium.

• 

Fire  dampers  in 

potentially  explosive  atmospheres

  must 

be grounded in accordance with regulations.

Functional testing and servicing

  Fire  dampers  must  be  serviced  by  the  owner  and  tested 

 

periodically  to  ensure  they  are  functioning  correctly. 

 

The intervals largely depend on the system operation. Rele

-

vant regulations should be followed. 

  FK90 fire dampers, series FK120, are maintenance-free due 

to  fully  enclosed  components,  corrosion-resistant  materials 

and  precise  manufacture.There  is  no  need  for  regular  clea

-

ning and lubrication, which would otherwise be necessary.

  Functional  tests  on  FK90  fire  dampers,  series  FK120,  are 

generally  limited  to  a  release  and  re-opening.This  can  be 

performed remotely with electric actuators.

  Repairs or service work are required in the event of malfunc

-

tions.Original spare parts must be used for this.

• 

Cleaning  work  required  in  ventilation  systems  for  hygiene 

reasons  must  be  performed  in  an  operation-dependent 

 

manner, and also includes the fire dampers.

Operating instructions

 for the FK90 fire dampers, series FK120, can be downloaded online at www.wildeboer.de/en

.

W220, G24

Closed during current flow

WU220, GU24

Closed during power interruption

Control voltages 230 V AC or 24 V DC

Limit switch not actuated

Connection cable colour coding

1  Thermostats, smoke detectors and switches  

should only be installed if required. 

 

On site delivery.

2  Thermal-electrical release element 

 

70°C or 95°C; EM-1, 

 

EM-2 and RM-1 only 70°C!

3  Thermal cut-off approx. 70°C
4  Electric  actuator  with  limit  switches  for 

OPEN-CLOSED position indicator. 

 

The illustration shows the de-energised 

operating position where the fire dam

-

pers are closed.

  • 

The  plugs  on  the  connection  cables  can 

be removed if they are not being used. 

 

• 

Due  to  their  in-built  thermal  release  ele

-

ments, all actuators must be stored at tem

-

peratures not exceeding 50°C.

5  Switches or buttons for testing the actuators
6  Thermal-electrical release element 70°C or 

100°C with plug-in connection for testing the 

actuator.

7  Lifting solenoid

8  Magnetic clamp

The right to allow for variations in delivery from 

the versions shown remains reserved

.

Summary of Contents for FK90

Page 1: ...series FK120 Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification EI 30 60 90 120 ve ho i o S C10ooo Hygiene certificate Environmental Product Declaration according to IS...

Page 2: ...arge free cross section Maximum volume flows Minimum pressure drop Extremely low sound power level Connection holes for profiles from 20 mm in height Two control openings inspection openings for viewi...

Page 3: ...tability free dom of damper blade movement minimum pressure drop and low noise level Option Casing with epoxy resin powder coating Replaceable damper blade made of high temperature re sistant corrosio...

Page 4: ...ld smoke extraction are country specific Electric spring return actuators also close the fire dampers if the supply voltage is interrupted They reopen the fire dampers as soon as the voltage is presen...

Page 5: ...n ded and vertical positions on site Terminal box FK90 fire dampers Release mechanisms and actuators 2 Thermal mechanical release mechanism with 70 C release element Option with coated 70 C release el...

Page 6: ...ocations must not be changed on site H J3 K K400 K500 200 170 225 160 250 145 275 135 4 300 120 17 325 110 29 350 95 42 375 85 54 400 70 67 450 45 92 500 20 117 17 550 142 42 600 7 167 67 650 32 192 9...

Page 7: ...637 0 684 0 780 0 876 1050 0 117 0 142 0 167 0 192 0 217 0 268 0 318 0 368 0 418 0 469 0 519 0 569 0 620 0 670 0 720 1100 0 122 0 149 0 175 0 202 0 228 0 281 0 334 0 386 0 439 0 492 0 545 0 598 0 650...

Page 8: ...m m 0 0 5 1 B 1 2 0 0 M e t a l d a m p e r b l a d e B 1 5 0 0 m m 1 4 0 0 v 12 m s A Volume flow m h v 12 m s A Operating pressure User Manual 5 0 2 2016 10 8 Subject to change Series FK120 FK90 fir...

Page 9: ...400 800 500 600 Width B mm 200 250 300 350 400 500 600 700 800 Height H mm Volume flow V m h 225 275 200 300 400 600 800 1000 2000 3000 4000 6000 8000 10000 20000 30000 40000 50000 150 900 1000 900 10...

Page 10: ...Afree 0 098 m Dps 29 Pa vA 7 4 m s LWA 47 dB A Sound power level LW Oct for the octave mid frequencies f Hz 63 125 250 500 1000 2000 4000 8000 LWA dB A 47 47 47 47 47 47 47 47 DL7 4 m s dB 5 6 1 3 6...

Page 11: ...always located to the H side on the casing of the fire dampers see page 6 FK90 fire dampers Installation in rigid walls and ceilings and in metal stud walls 1 with cladding on both sides The fire damp...

Page 12: ...rete in solid construction Rigid walls and ceilings must have bulk density 450 kg m Metal stud walls should be clad on both sides in two or more layers with 12 5 mm GKF plasterboard Installation openi...

Page 13: ...nd tested periodically to ensure they are functioning correctly The intervals largely depend on the system operation Rele vant regulations should be followed FK90 fire dampers series FK120 are mainten...

Page 14: ...Option Explosion protected limit switch EX CLOSED EX OPEN Option Electric actuators M220 9 V M24 9 V M220 7 M24 7 Option Electric explosion protected actuators EM 1 RM 1 EM 2 see pages 5 and 6 FK90 f...

Page 15: ...metal stud walls Enclosed maintenance free thermal release mechanism 70C 95 C or 100 C for manual single handed operation corrosion resistant release element with two electrical limit switch es for s...

Page 16: ...nventional control systems in buildings is complex Special plug and play functionality allows control systems for fire dampers to be designed built and connected in parent hierarchy without any measur...

Reviews:

Related manuals for FK90