background image

User Manual 5.02 (2016-10)

 3

Subject to change

Series FK120

FK90 fire dampers

Description

Increased corrosion protection through powder coating and stainless steel

Casings coated internally and externally are recommended:

• 

metal frames of the damper blades 

made of 1.4301 stainless steel

 and 

 

– if present – the metal cover as well

• 

thermal-mechanical release mechanisms with 

corrosion-resistant

 (coated) 

release element 70°C.

These combinations allow additional corrosion protection for harsh service conditions.

FK90 fire dampers

 Meet the 

hygiene requirements

 according to VDI 6022-1, DIN 1946-4 and DIN EN 13779

• 

Do not promote the growth of microorganisms 

1)

 (fungi, bacteria)

This reduces the risk of infection for people and also the necessary 

cleaning and disinfection work!

• 

Are 

resistant to disinfectants 

2)

 

• 

Are suitable for use in hospitals and similar facilities!

• 

Permanently 

perform 

their 

function under high corrosion condi-

tions.

Tested according to EN 15650, annex B with 20% saline solution.

1)

  The  corresponding 

resistance of the materials to fungi and bacteria

  was  verified  by  testing  the  microbial  metabolic  potential  under 

DIN EN ISO 846 for all materials in the FR90 fire dampers.

2)

 The 

resistance to disinfectants

 of the materials in the FR90 fire dampers was tested with the disinfectant groups of active ingredients 

alcohol

 and 

quaternary compounds

. These disinfectants are on the list by the Robert Koch Institute, and were used in accordance with the specifications in 

the list of disinfectants by the Disinfectants Commission in the German Association for Applied Hygiene (VAH). It has been verified that FR90 fire 

dampers can withstand normal use of disinfectants and disinfection methods.

Pressure-joined  casing  with  all-round  single-piece  design, 

made  of  galvanized  sheet  steel,  leak  tightness  class  C 

according to EN  1751. Formed connection flanges, outer 

beading  and  tapered  inner  beading  ensure  stability,  free

-

dom of damper blade movement, minimum pressure drop 

and low noise level.

Option: 

Casing with epoxy resin powder coating.

Replaceable  damper  blade  made  of  high-temperature-re

-

sistant,  corrosion-resistant  and  abrasion-proof  calcium 

silicate  with  galvanized  metal  frame  and  folded,  wear-re

-

sistant elastomer lip seals.

Options:

 Damper blade with metal frame made of 1.4301 

stainless  steel/damper  blade  with  metal  cover  made  of 

galvanized  steel/damper  blade  with  metal  cover  made  of 

1.4301 stainless steel. 

Fully  enclosed,  maintenance-free  slider  crank  transmis

-

sion in the area of the casing wall, as a self-locking drive 

mechanism  for  break-proof  torque  transmission.  Sealed 

drive  axles  made  of  stainless  steel,  with  red  metal  bea

-

rings.

Thermal  release  mechanisms  for  70°C,  95°C  and  100°C 

nominal  temperature.  The  operation  units  can  be  actua

-

ted manually or electrically.  

 

 

 

 

 see pages 4 and 5

Release  mechanisms,  operation  units  and  electric  actu

-

ators are enclosed and fitted with a spring return. They are 

maintenance-free,  can  be  connected  in  a  form-locking  or 

force-fitting manner, are easy to replace and can be easily 

retrofitted as required. 
For  installation  with  horizontal  or  vertical  damper  blade 

axles. Air inflow from any connection side. Connection to 

ventilation ducts made of non-combustible or combustible 

materials, including protective grilles.

Option:

  Additional  openings  on  the  operation  side  in  the 

casing.

⇒ 

see page 14

Widths B: 

200 mm to 1500 mm |  200 mm to 1000 mm 

Heights H:

 200 mm to 800 mm |  200 mm to 1000 mm

Lengths: 

400 mm and 500 mm

The respective width and height dimensions are available 

in 5-mm increments and can be combined. 

 see page 14

For installing in rigid walls, ceilings and in metal  

stud walls. 

 see pages 11 and 12

Maintenance-free 

FK90 fire dampers according to EN 15650

Fire classifications: 

 

EI 30/60/90/120 (v

e

 - h

o

, i 

 o) S C

10ooo

 

⇒ 

see page 11

Declaration of performance: 

DoP no.: CPR/FK120/002

EU Declaration of Conformity according to Directive 2014/34/EU  
for 

use in potentially explosive atmospheres

 

Environmental Product Declaration ISO 14025, EN 15804: 

EPD-WWB-20130081-IBA1-DE

Summary of Contents for FK90

Page 1: ...series FK120 Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification EI 30 60 90 120 ve ho i o S C10ooo Hygiene certificate Environmental Product Declaration according to IS...

Page 2: ...arge free cross section Maximum volume flows Minimum pressure drop Extremely low sound power level Connection holes for profiles from 20 mm in height Two control openings inspection openings for viewi...

Page 3: ...tability free dom of damper blade movement minimum pressure drop and low noise level Option Casing with epoxy resin powder coating Replaceable damper blade made of high temperature re sistant corrosio...

Page 4: ...ld smoke extraction are country specific Electric spring return actuators also close the fire dampers if the supply voltage is interrupted They reopen the fire dampers as soon as the voltage is presen...

Page 5: ...n ded and vertical positions on site Terminal box FK90 fire dampers Release mechanisms and actuators 2 Thermal mechanical release mechanism with 70 C release element Option with coated 70 C release el...

Page 6: ...ocations must not be changed on site H J3 K K400 K500 200 170 225 160 250 145 275 135 4 300 120 17 325 110 29 350 95 42 375 85 54 400 70 67 450 45 92 500 20 117 17 550 142 42 600 7 167 67 650 32 192 9...

Page 7: ...637 0 684 0 780 0 876 1050 0 117 0 142 0 167 0 192 0 217 0 268 0 318 0 368 0 418 0 469 0 519 0 569 0 620 0 670 0 720 1100 0 122 0 149 0 175 0 202 0 228 0 281 0 334 0 386 0 439 0 492 0 545 0 598 0 650...

Page 8: ...m m 0 0 5 1 B 1 2 0 0 M e t a l d a m p e r b l a d e B 1 5 0 0 m m 1 4 0 0 v 12 m s A Volume flow m h v 12 m s A Operating pressure User Manual 5 0 2 2016 10 8 Subject to change Series FK120 FK90 fir...

Page 9: ...400 800 500 600 Width B mm 200 250 300 350 400 500 600 700 800 Height H mm Volume flow V m h 225 275 200 300 400 600 800 1000 2000 3000 4000 6000 8000 10000 20000 30000 40000 50000 150 900 1000 900 10...

Page 10: ...Afree 0 098 m Dps 29 Pa vA 7 4 m s LWA 47 dB A Sound power level LW Oct for the octave mid frequencies f Hz 63 125 250 500 1000 2000 4000 8000 LWA dB A 47 47 47 47 47 47 47 47 DL7 4 m s dB 5 6 1 3 6...

Page 11: ...always located to the H side on the casing of the fire dampers see page 6 FK90 fire dampers Installation in rigid walls and ceilings and in metal stud walls 1 with cladding on both sides The fire damp...

Page 12: ...rete in solid construction Rigid walls and ceilings must have bulk density 450 kg m Metal stud walls should be clad on both sides in two or more layers with 12 5 mm GKF plasterboard Installation openi...

Page 13: ...nd tested periodically to ensure they are functioning correctly The intervals largely depend on the system operation Rele vant regulations should be followed FK90 fire dampers series FK120 are mainten...

Page 14: ...Option Explosion protected limit switch EX CLOSED EX OPEN Option Electric actuators M220 9 V M24 9 V M220 7 M24 7 Option Electric explosion protected actuators EM 1 RM 1 EM 2 see pages 5 and 6 FK90 f...

Page 15: ...metal stud walls Enclosed maintenance free thermal release mechanism 70C 95 C or 100 C for manual single handed operation corrosion resistant release element with two electrical limit switch es for s...

Page 16: ...nventional control systems in buildings is complex Special plug and play functionality allows control systems for fire dampers to be designed built and connected in parent hierarchy without any measur...

Reviews: