background image

User Manual 5.0-2 (2016-10)

 4

Subject to change

Series FK120

FK90 fire dampers

Release mechanisms and actuators (1)

Thermal-mechanical release mechanism

 - standard -

 

with 70°C release element.

Option:

   with coated 70°C release element.

Option: 

with coated 95°C release element.

Option:

  with 

limit switch

 

E

  Changeover with gold-plated contacts for 5 A 

 

 

at 250 V AC or 24 V DC; IP67;  

 

 

1 m silicone-free connection cable, 3 x 0.34 mm².

 

One  or  two  can  be  plugged  in  for  the  CLOSED  and/or  OPEN 

position indicator; instead of blind caps.

Enclosed 

relea-

se element

can be replaced 

from the front.

Blind cap 

can 

be replaced with 

the 

OPEN limit 

switch

.

Manual release

‘Red button’

Lever for opening

 the 

fire damper.

Inserted 

limit 

switch

 CLOSED

.

FK90 fire dampers, series FK120, are fitted with maintenance-free thermal-mechanical release mechanisms or with 

thermal-electrical release mechanisms on the spring return actuators. 

Release

 occurs at a nominal temperature of 

70°C

. Coated release elements provide increased corrosion protection. Release mechanisms with a release element 

for nominal temperatures of 

95°C

 and 

100°C 

are provided for warm air heating systems. The requirements for use in 

ventilation systems for "cold smoke extraction" are country-specific.
Electric spring return actuators also close the fire dampers if the supply voltage is interrupted. They reopen the fire 

dampers as soon as the voltage is present again. 
Release mechanisms and operation units can be replaced on site!

Release mechanism and 

remote release

 with lifting solenoid

Option:

  with additional 

remote release

 based on the:

 

closed circuit principle

.  The  fire  dampers  must  be  opened 

manually, and close after the electrical supply voltage is inter

-

rupted.

 

GU24 

with magnetic clamp 24 V DC; 1.6 W;  

 

 

100% duty cycle; IP42.

 WU220 

with magnetic clamp 230 V AC; 4 VA; 

100% duty  

 

cycle;IP42.

 

Open circuit principle

.  The  fire  dampers  must  be  opened 

manually, and close by means of electrical or pneumatic stimu

-

lus.

 

G24  

with lifting solenoid 24 V DC; 3.5 W; 100% duty  

 

cycle; IP42.

 

W220

  with lifting solenoid 230 V AC; 5.5 VA; 100% duty  

 

cycle; IP42.

  P  

with lift cylinder 4 to 8 bar.

 

P2  

with lift cylinder 1.2 to 8 bar.

Option:

 

Electric spring return actuator

 - standard -

 

with 70°C release element; IP54.

 

M220-9/V

  230 V AC; 9.2 VA; I

max 

 2 ms

 = 0.27 A.

 

M24-9/V

  24 V AC/DC; 6.1 VA / 3.5 W;I

max 

 2 ms

 = 3.5 A.

 

Runtime: Opening 

≈ 

60 s, closing 

≈ 

21 s.

 

CLOSED/OPEN position indicators via limit switches for 

5 A at 

 240 V AC.

 

Halogen-free connection cable; 0.9 m long; 2 x 0.75 mm² 

and 6 x 0.75 mm². The AMP connector plugs are 

detachable.

Option: 

with 100°C release element.

Enclosed 

release element

Summary of Contents for FK90

Page 1: ...series FK120 Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification EI 30 60 90 120 ve ho i o S C10ooo Hygiene certificate Environmental Product Declaration according to IS...

Page 2: ...arge free cross section Maximum volume flows Minimum pressure drop Extremely low sound power level Connection holes for profiles from 20 mm in height Two control openings inspection openings for viewi...

Page 3: ...tability free dom of damper blade movement minimum pressure drop and low noise level Option Casing with epoxy resin powder coating Replaceable damper blade made of high temperature re sistant corrosio...

Page 4: ...ld smoke extraction are country specific Electric spring return actuators also close the fire dampers if the supply voltage is interrupted They reopen the fire dampers as soon as the voltage is presen...

Page 5: ...n ded and vertical positions on site Terminal box FK90 fire dampers Release mechanisms and actuators 2 Thermal mechanical release mechanism with 70 C release element Option with coated 70 C release el...

Page 6: ...ocations must not be changed on site H J3 K K400 K500 200 170 225 160 250 145 275 135 4 300 120 17 325 110 29 350 95 42 375 85 54 400 70 67 450 45 92 500 20 117 17 550 142 42 600 7 167 67 650 32 192 9...

Page 7: ...637 0 684 0 780 0 876 1050 0 117 0 142 0 167 0 192 0 217 0 268 0 318 0 368 0 418 0 469 0 519 0 569 0 620 0 670 0 720 1100 0 122 0 149 0 175 0 202 0 228 0 281 0 334 0 386 0 439 0 492 0 545 0 598 0 650...

Page 8: ...m m 0 0 5 1 B 1 2 0 0 M e t a l d a m p e r b l a d e B 1 5 0 0 m m 1 4 0 0 v 12 m s A Volume flow m h v 12 m s A Operating pressure User Manual 5 0 2 2016 10 8 Subject to change Series FK120 FK90 fir...

Page 9: ...400 800 500 600 Width B mm 200 250 300 350 400 500 600 700 800 Height H mm Volume flow V m h 225 275 200 300 400 600 800 1000 2000 3000 4000 6000 8000 10000 20000 30000 40000 50000 150 900 1000 900 10...

Page 10: ...Afree 0 098 m Dps 29 Pa vA 7 4 m s LWA 47 dB A Sound power level LW Oct for the octave mid frequencies f Hz 63 125 250 500 1000 2000 4000 8000 LWA dB A 47 47 47 47 47 47 47 47 DL7 4 m s dB 5 6 1 3 6...

Page 11: ...always located to the H side on the casing of the fire dampers see page 6 FK90 fire dampers Installation in rigid walls and ceilings and in metal stud walls 1 with cladding on both sides The fire damp...

Page 12: ...rete in solid construction Rigid walls and ceilings must have bulk density 450 kg m Metal stud walls should be clad on both sides in two or more layers with 12 5 mm GKF plasterboard Installation openi...

Page 13: ...nd tested periodically to ensure they are functioning correctly The intervals largely depend on the system operation Rele vant regulations should be followed FK90 fire dampers series FK120 are mainten...

Page 14: ...Option Explosion protected limit switch EX CLOSED EX OPEN Option Electric actuators M220 9 V M24 9 V M220 7 M24 7 Option Electric explosion protected actuators EM 1 RM 1 EM 2 see pages 5 and 6 FK90 f...

Page 15: ...metal stud walls Enclosed maintenance free thermal release mechanism 70C 95 C or 100 C for manual single handed operation corrosion resistant release element with two electrical limit switch es for s...

Page 16: ...nventional control systems in buildings is complex Special plug and play functionality allows control systems for fire dampers to be designed built and connected in parent hierarchy without any measur...

Reviews: