1.9.

 

CONNECT SUPPLY AND RETURN 

DUCTS 

1.9.1.

 

Duct sizing 

1.9.1.1.

 

Determine airflow CFM 

The temperature rise through the furnace must not exceed 85

o

F, but 

should be at least 55°F for comfort. When calculating airflow, 
assume a temperature rise of 70°F. 
The noticeable temperature change for cooling would be 
approximately 27-30°F. Actual temperature change will be 
approximately 18-21°F due to humidity of the air. 
To calculate noticeable heat temperature change (

Δ

T), you can use 

the formula: 

Δ

T = BTU/h / (1.1 x CFM) 

Eq. 3 - 1 

To calculate air flow when you know temperature change (

Δ

T), you 

can use: 

CFM = BTU/h / (1.1 x 

Δ

T) 

Eq. 3 - 2 

You can estimate air flow using the following rules of thumb:  

Heating:  

14 CFM per 1,000 BTU/h

 output 

Eq. 3 - 3 

Cooling: 

400 CFM per ton

 air conditioning 

Eq. 3 - 4 

Determine the required airflow based on whichever is larger: heating 
mode or air conditioning mode. 

Examples: 

1.

  What would the temperature rise be for a 100,000 BTU/h output 

furnace with an airflow rate of 1200 CFM? 
Use Equation 3-1 since you know CFM and BTU/h: 

Δ

T = 100,000 / (1.1 x 1200) = 76°F 

  The temperature rise would be 76°F. 

  If the air enters the furnace at 70°F, it would leave the 

furnace at 70°F + 76°F = 146°F. 

2.

  What would the airflow be to obtain a 70°F rise through a 

120,000 BTU/h output furnace? 
Use equation 3-2 since you know 

Δ

T and BTU/h: 

CFM = 120,000 / (1.1 x 70) = 1558 CFM 

  The air flow would have to be 1558 CFM to obtain a 

temperature rise of 70°F. 

3.

  Estimate the required airflow for a 75,000 BTU/h output furnace 

installed with a 2-ton air conditioning evaporator coil. 
Heating mode air flow (use Equation 3 - 3): 
CFM = 75 x 14 = 1050 CFM 
Cooling mode air flow (use Equation 3 - 4): 
CFM = 2 x 400 = 800 CFM 

  The larger number is 1050 CFM (heating), so the duct 

system should be sized for 1050 CFM. 

  The supply duct would need to be 16” round or a rectangular 

equivalent such as 8” x 25" or 12" x 18", using Table 3. 

4.

  Estimate the required airflow for the same furnace installed with 

a 4-tons air conditioning evaporator coil. 
Heating mode airflow is still 1050 CFM. 
Cooling mode air flow (use Equation 3 - 4): 
CFM = 4 x 400 = 1600 CFM 

  The larger number is 1600 CFM (cooling), so the duct 

system should be sized for 1600 CFM. 

  The supply duct would need to be 18” round or a rectangular 

equivalent such as 8" x 36" or 12" x 23", using Table 3 

 

Always check the size of existing ducts, 
particularly if you are adding air conditioning. 
The air pressure loss through the cooling 
evaporator coil reduces available airflow. If the 
ducts are too small as well, the system may not 
work satisfactorily on either heating or cooling. 

1.9.1.2.

 

Determine duct dimensions 

Tables 3 and 4, provide typical round and rectangular duct sizes for 
rectangular and flat oval galvanized ducts. Do not apply these tables 
to size ductwork if the total equivalent length of the duct exceeds 
approximately 100 feet. For longer systems or for duct board, 
fiberglass-lined or flexible duct sizing, use the ACCA Manual D or 
the ACCA duct sizing slide rule. These tables are based on pressure 
loss of approximately 0.10” water column per 100 feet equivalent 
length of duct. 
Use Table 2 below to size or check sizing of take-offs to supply 
registers or return grills. 
Verify the size and type of registers, diffusers and grills from the 
manufacturer’s ratings. Do not exceed the recommended flow rate. 
The pressure drop allowance for each should not exceed 
approximately 0.05” water column. 
Install a return air filter, sized per specifications in Table 10. 
Use only a return air filter mounted to the furnace. Do not add 
additional filters unless the duct system is carefully sized to allow for 
the additional pressure drop. 

Table 2: Suggested maximum flow to run outs 

 

TAKE-OFF SIZE

(Inches)

SUPPLY

RETURN

5 Round

60

45

6 Round

100

75

7 Round

140

110

8 Round

210

160

3 ¼ x 8 Stack

70

55

3 ¼ x 10 Stack

100

75

3 ¼ x 14 Stack

140

110

2 ¼ x 12 Stack

70

55

2 ¼ x 14 Stack

90

70

6 Round

55

40

8 Round

120

90

10 Round

200

160

12 Round

320

250

14 Round

480

375

16 Round

660

530

18 Round

880

680

20 Round

1200

900

CFM

Sheet metal or ductboard

Flexible  duct (keep bends to minimum)

Summary of Contents for PLB-098 LOW-BOY

Page 1: ...y could result in severe personal injury death or substantial property damage When calling or writing about the furnace Please indicate furnace model number and serial number from rating label You may...

Page 2: ...bows 20 Always connect and seal a return air duct to the furnace unless the furnace is located in a large space such as an unpartitioned basement Route the return air duct to an adjacent room if no re...

Page 3: ...to a hazardous electrical condition and to premature failure of the equipment The minimum clearances from combustible material for each of the positions are specified in Table 1 If the furnace is inst...

Page 4: ...to the burner manufacturer s instructions Also the burner must be installed always in the same way independently of the furnace orientation 1 Position the mounting gasket between the mounting flange a...

Page 5: ...re the draft is either high or variable due to external conditions Follow the instructions provided with the regulator 1 5 4 Side wall Venting The heating unit is approved for side wall venting This s...

Page 6: ...xposure to the following substances a Permanent wave chemicals for hair b Chlorinated waxes and cleaners c Chlorine based swimming pool chemicals d Water softening chemicals e De icing salts or chemic...

Page 7: ...furnace installed with a 4 tons air conditioning evaporator coil Heating mode airflow is still 1050 CFM Cooling mode air flow use Equation 3 4 CFM 4 x 400 1600 CFM The larger number is 1600 CFM cooli...

Page 8: ...7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 13...

Page 9: ...600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 120...

Page 10: ...he position of the wires on the electronic board of the unit and consult the wiring diagrams If the heating and air conditioning speeds are the same the RED wire must be moved to UNUSED LEADS on the e...

Page 11: ...BVSO is installed according to instructions for chimney venting 4 The oil supply valve is open 5 The burner Reset button is well pushed in or re armed 6 The preliminary air adjustments on the burner...

Page 12: ...ise is lower or exceeds the temperature specified in Table 10 change to the next lower or higher blower speed tap until the temperature rise falls to the target If the excessive temperature rise canno...

Page 13: ...6 Re mount lock and fasten the control box with the 2 screws removed in step 4 7 Re attach the assembly cover with the screws removed in step 2 8 Re establish power to the unit 3 3 CLEANING OF THE BUR...

Page 14: ...rough furnace checked not to exceed 85 F and the blower speed adjusted if necessary 19 Was the thermostat heat anticipator set per wiring diagram 20 Was the burner started and tested per burner manual...

Page 15: ..._____________________________Date installed_____________________________ Installation instructions have been followed Checkout sequence has been performed Above information is certified to be correct...

Page 16: ...000 0 70 MED HIGH HIGH 1255 1180 77 000 65 000 0 55 98 000 81 000 0 70 Model Input BTU h Blower motor HP Blower motor Speed adjustment 3 0 1 2 HP ECM 1 3 HP 4 speeds PLB098 DD PLB098 VS 10 x 10 Outpu...

Page 17: ...h Firing rate USGPH AFUE Nozzle Delavan Pump pressure PSIG Burner tube insertion length Inch Combustion air adjustment Turbulator Damper 77 000 0 55 86 6 0 50 70A 150 0 2 0 98 000 0 70 85 2 0 60 70A...

Page 18: ...1 ON 2 ON 1 5 600 660 540 SW4 DELAY DIP switch position HEAT INPUT USGPH PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 7 13 45 sec 19 30 sec...

Page 19: ...PLB 098 Oil Furnaces Furnace Manual 11 13 19 5 DIMENSIONS AND RATINGS continued Figure 9 Wiring Diagram 4 Speed Motor PSC...

Page 20: ...PLB 098 Oil Furnaces Furnace Manual 20 11 13 5 DIMENSIONS AND RATINGS continued Figure 10 Wiring Diagram Variable Speed Motor ECM...

Page 21: ...PLB 098 Oil Furnaces Furnace Manual 11 13 21 6 COMPONENTS AND REPLACEMENT PARTS Figure 11 Parts List With 4 Speed motor PSC B50126A...

Page 22: ...B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B03118 01 ELECTRICAL KIT BVSO EXT 32 B03596 BURNER WIRE CHANEL 33 Z06G001 BLOCKED VENT SHUT OF...

Page 23: ...PLB 098 Oil Furnaces Furnace Manual 11 13 23 6 COMPONENTS AND REPLACEMENT PARTS continued Figure 12 Parts List With variable speed motor ECM B50127A...

Page 24: ...AL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B03118 01 ELECTRICAL KIT BVSO EXT 32 B03596 BURNER WIRE CHANEL 33 Z06G001 BLOC...

Page 25: ...f the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary control button NE...

Page 26: ...PLB 098 Oil Furnaces Furnace Manual 26 X40205 Rev B 11 13...

Reviews: