background image

 
 

PMP

 

Oil Furnaces

 – 

Furnace Manual

 

6

 

 670-000-003/1010 

2

 

Prepare furnace and place in position 

 

Inspect & prepare furnace 

Remove furnace from carton 

Remove the furnace from its shipping carton and inspect thoroughly. 
Remove access panels to inspect the furnace interior. 

Immediately file a claim with the transportation 
company if you discover concealed damage. 

Do not install or attempt to operate the furnace if the 
heat exchanger, burner or controls have been 
damaged. Immediately contact your furnace 
supplier. Operating a damaged furnace could result 
in severe personal injury, death or substantial 
property damage. 

 
 

Prepare burner 

Remove the burner from its shipping carton and inspect thoroughly. 
Read the burner manual and follow instructions for preparing and 
installing the burner. 

Install the correct nozzle for the required firing rate, using the burner 
manual and the information on Section 12, p. 28 and 29 of this 
manual. Follow the burner manual instructions for nozzle installation. 
Verify the correct settings of electrodes after nozzle and burner oil 
tube assembly are in place. 
 
 
 
 
 

Openings in walls, floor & ceiling 

General 

Ensure that the finished door opening to the furnace room is large 
enough to install and remove the furnace, water heater or any other 
appliances in the room. 

Before placing furnace in a closet or small room, cut all openings 
required in floor, ceiling or walls for ducts and vent. This will simplify 
the work and prevent construction dust from entering the furnace 
heat exchanger. 

Verify that all clearances to combustible construction 
and for service accessibility will be met. The vent 
must be no closer than 18 inches to any combustible 
surface unless a type “L” double-wall vent pipe is 
used or the vent is constructed per the requirements 
of the NFPA 31. Provide a ventilated thimble per all 
applicable codes where vent pipe passes through a 
wall or ceiling. Failure to comply could result in 
severe personal injury, death or substantial property 
damage. 

 

Duct locations and sizing 

Verify that the size of the supply and return duct system is sufficient 
for the application. The pressure drop through the duct system must 
not exceed 0.2” water column. 
 

 

Openings in walls, floor… 

(continued)

 

The total drop through the duct system and air conditioning 
condensing coil (if used) must not exceed 0.5” water column. 

See suggested duct sizing in this manual. For more detailed sizing 
information, refer to ACCA Manual D. 
 

Return air duct 

You must install a return air duct, sealed to the furnace, even if no 
return manifold is used. The only exception is when the furnace is 
located in a large unpartitioned room, such as a basement. (A room 
whose volume is at least 50 cubic feet per 1,000 BTU/h input of all 
appliances in the room is considered large). For large rooms, return 
air may be taken directly at the furnace, without a return air duct. No 
return air register should be within 20 feet of the furnace. 
 
Cut the required opening for the return air duct in the wall (or floor or 
ceiling) of the room before placing the furnace. 
 

Install filter 

Install return air filter of the size listed on Section 12, p. 28. 

The filter rack is provided with the unit. You will need to attach the 
filter rack to the furnace for all Model PMP. 
 

Verify that the filter will be easily accessible for 
removal after the furnace is in place. 

When installing on 

combustible flooring

, provide supply plenum 

size and floor opening as given in Table 3. 
 
 

Install furnace and burner 

Place furnace 

Place the furnace in the desired location. Measure clearances and 
verify per page 3 of this manual. 

Use a spirit level on the front and one side of the furnace. Make sure 
each of the legs is firmly in contact with the floor. 

Inspect combustion chamber 

Inspect the combustion chamber. Verify it is in good condition and 
correctly in position inside the heat exchanger. The burner opening 
in the chamber must align with the burner heat exchanger opening. 

The combustion chamber is constructed of ceramic 
fiber materials See the WARNING information on 
page 21 of this manual. Comply with these 
instructions when handling any ceramic fiber or 
fiberglass materials. Failure to adhere to these 
guidelines could result in severe personal injury or 
death. 

Insert burner 

Following the burner manual instructions, install the burner and its 
gasket in the burner opening.  

Secure the burner in place with the four nuts and washers provided. 
Wire and pipe fuel to the burner as per the burner manual and this 
manual. 
 

Burner orientation 

For a horizontal installation, you must turn the burner 90

o

, to the 

normal position. Always keep the motor shaft in horizontal position. 

Summary of Contents for PMP210

Page 1: ...sportation company by the consignee Do not store or use gasoline or other flammable liquids or vapors near this furnace or any other appliance Ventilate house while operating furnace for the first tim...

Page 2: ...o use gasoline a mixture of gasoline and oil waste fuel refuse or any other substance in the burner of furnace Installation 18 Do not block flow of combustion or ventilation air to furnace Do not bloc...

Page 3: ...aintained 2 Always apply whichever clearance is LARGER combustible construction or service accessibility Flooring and foundation Flooring If a combustible floor is used follow these instructions Upflo...

Page 4: ...yer and fireplace When outside air is used Connect each opening directly by ducts to the outdoors or to crawl or attic space that freely connects with outdoors Size per below Through outside wall or v...

Page 5: ...o avoid Spray cans containing chloro fluorocarbons Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for...

Page 6: ...The total drop through the duct system and air conditioning condensing coil if used must not exceed 0 5 water column See suggested duct sizing in this manual For more detailed sizing information refer...

Page 7: ...he cause of this shut down Refer to the figures 5 6 at section 6 Wiring Diagrams and detailed instructions supplied with the BVSO for the installation and wiring procedures It is also essential that t...

Page 8: ...furnace installed with a 4 ton air conditioning evaporator coil Heating mode airflow is still 1 050 CFM Cooling mode airflow use Equation 3 4 CFM 4 x 400 1 600 CFM The larger number is 1 600 CFM cool...

Page 9: ...7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 13...

Page 10: ...600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 120...

Page 11: ...nal injury or death 1 The horizontal vent must slope upwards away from the furnace a minimum of inch per foot 2 Connection must be made above bottom of chimney to avoid blockage Vent pipe must not ent...

Page 12: ...use Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Use only flare fittings Do not use compression fittings Failure to comply could result in severe personal injury dea...

Page 13: ...PMP Oil Furnaces Furnace Manual 670 000 003 1010 13 Notes...

Page 14: ...t must be used Supply wiring to furnace must be sized for the load required see Section 12 p 27 Provide electrical ground at furnace as required by codes Connect 120 VAC 60 Hertz single phase separate...

Page 15: ...ure 5 Blocked Vent Shut Off device wiring Optional 1 Blocked Vent Shutt Off device BVSO 2 Electrical kit supplied 3 Connect one red wire to limit switch 4 Disconnect red wire from limit switch and con...

Page 16: ...PMP Oil Furnaces Furnace Manual 16 670 000 003 1010 6 Wire furnace burner continued Figure 6 Wiring PMP furnace with direct drive blowers Beckett Carlin and Riello burners...

Page 17: ...nd 11 with 0 smoke To start furnace continued Make final burner adjustments using combustion test equipment to assure proper operation 8 Check furnace and duct system for proper operation and conditio...

Page 18: ...lector box to prevent possible flue gas leakage and carbon monoxide emissions leading to severe personal injury or death 24 Was Limit Control tested per To start up in this manual 25 Was furnace cycle...

Page 19: ...ignment of the cad cell to assure it is aimed at the fire Check nozzle and electrode position Check ignition transformer output Reference burner manufacturers instructions Check tube insertion and ali...

Page 20: ...NING and guidelines given on page 21 Failure to comply could result in severe personal injury death or substantial property damage Consult with homeowner to see if there were any Check sequence of ope...

Page 21: ...e it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh...

Page 22: ...handle loosen the soot from the heat exchanger surfaces Remove as much soot as possible using a vacuum 6 Replace cleanout cover or flue collector box 7 Re install burner and mounting plate Obtain gas...

Page 23: ...west setting Burner should turn off 6 Furnace blower will continue to run until the Limit Fan switch senses air temperature below the fan OFF setting 7 Set the room thermostat to call for heat again A...

Page 24: ...PMP Oil Furnaces Furnace Manual 24 670 000 003 1010 Notes...

Page 25: ...PMP Oil Furnaces Furnace Manual 670 000 003 1010 25 Components and Replacement Parts...

Page 26: ...PMP Oil Furnaces Furnace Manual 26 670 000 003 1010 11 Components and replacement parts Figure 7 Model PMP 210 furnaces Component locations B50110 Rev A...

Page 27: ...R004 33 15 MF capacitor L01I005 10 Limit Control cover B02826 01 34A Electronic fan timer R99G004 11 Gasket smoke box B02714 34B Electrical wire harness board B02797 12 Smoke box cover B02799 01 35 Ro...

Page 28: ...e quantity load ampacity for fuse size weight o F and size amps wiring sizing amps pounds PMP 210 65 85 1 20 X 30 115 60 1 15 7 18 1 20 0 250 Model Volt Hertz Phase DNS 0909 Rev A Maximum cooling capa...

Page 29: ...1 50 1 50 60B 100 1 50 PMP 210 1 10 1 25 1 35 1 50 1 35 1 50 CARLIN BURNER EZ 1 Tube insertion 2 1 2 Model Input Firing rate USGPH Nozzle Delavan Head Setting A BECKETT BURNER Model AFG 3450 RPM Tube...

Page 30: ...om thermostat 2 If the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary...

Page 31: ...PMP Oil Furnaces Furnace Manual X40104 Rev I...

Reviews: