background image

Page 2 

 

Installer’s Information Manual 

TABLE OF CONTENTS 

SECTION 1. 

Important Safety Rules ........................................................................................................................... 2 

SECTION 2. 

Meeting Codes ....................................................................................................................................... 3 

SECTION 3. 

Determining Best Furnace Location ....................................................................................................... 3 

SECTION 4. 

Conversion To Downflow Configuration ................................................................................................. 5 

SECTION 5. 

Allowing For Clearances......................................................................................................................... 6 

SECTION 6. 

Providing Combustion And Ventilation Air.............................................................................................. 8 

SECTION 7. 

Providing Proper Venting...................................................................................................................... 11 

SECTION 8. 

Sidewall Venting ................................................................................................................................... 15 

SECTION 9. 

Installing Gas Piping............................................................................................................................. 15 

SECTION 10. 

Installing Electrical Wiring .................................................................................................................... 16 

SECTION 11. 

Sequence Of Operation........................................................................................................................ 17 

SECTION 12. 

Installing Duct System .......................................................................................................................... 19 

SECTION 13. 

Selecting And Installing Filter Cabinets................................................................................................ 20 

SECTION 14. 

Checks Before Starting Furnace .......................................................................................................... 22 

SECTION 15. 

Gas Supply Pressure Adjustment ........................................................................................................ 22 

SECTION 16. 

Manifold Pressure Adjustment ............................................................................................................. 23 

SECTION 17. 

Checking Gas Input Rate ..................................................................................................................... 23 

SECTION 18. 

Derating For High Altitude .................................................................................................................... 25 

SECTION 19. 

Determining Correct Orifice Size.......................................................................................................... 25 

SECTION 20. 

Changing Main Burner Orifices ............................................................................................................ 26 

SECTION 21. 

Adjusting Blower Speed ....................................................................................................................... 26 

SECTION 22. 

Measuring Duct System Static Pressure.............................................................................................. 28 

SECTION 23. 

Measuring Air Temperature Rise ......................................................................................................... 28 

SECTION 24. 

Checking Controls ................................................................................................................................ 29 

SECTION 25. 

Setting Blower Timings......................................................................................................................... 30 

SECTION 26. 

Maintaining Furnace In Good Working Order ...................................................................................... 30 

SECTION 27. 

Blower Assembly Removal................................................................................................................... 31 

SECTION 28. 

Accessories .......................................................................................................................................... 31 

SECTION 29. 

Other Information And Publications...................................................................................................... 32 

 

 

 

 

Figure 1.  Upflow Configuration. 

You may install this furnace in the upflow configuration in 
one of the three positions shown in Figure 1.  This furnace 
is usually shipped from the factory in the upflow 
configuration. 

 

Figure 2.  Downflow Configuration. 

You may install this furnace in the downflow configuration in 
one of the three positions shown in Figure 2.  Conversion 
from upflow to downflow can be done quickly and easily by 
following the instructions in Section 4, "Conversion to 
Downflow Configuration." 

 

SECTION 1.  IMPORTANT SAFETY 
RULES 

To alert you to potential hazards, we use the signal words 
"WARNING" and "CAUTION" throughout this manual. 

 

"WARNING" alerts you to situations that could cause or 

result in serious injury or death.  "CAUTION" alerts you to 
situations that could cause or result in minor or moderate 
injury or property damage.  For a safe and reliable 
installation be sure to read and follow all warnings and 
cautions. 

Summary of Contents for w 80

Page 1: ...ller should give you the important documents listed above You should immediately read the User s Information Manual for important safety information to keep you and your family safe Keep these as long...

Page 2: ...uring Air Temperature Rise 28 SECTION 24 Checking Controls 29 SECTION 25 Setting Blower Timings 30 SECTION 26 Maintaining Furnace In Good Working Order 30 SECTION 27 Blower Assembly Removal 31 SECTION...

Page 3: ...to check all connections Rule 8 Completely seal supply and return air ducts to furnace casing Duct system must run to an area outside furnace room or closet Seal duct work wherever it runs through wa...

Page 4: ...2 12 3 4 12 15 16 10 6 40 70 1235 80 000 1 2 4 17 1 2 15 3 4 15 15 16 10 8 50 80 1645 80 000 3 4 4 20 1 2 18 3 4 18 15 16 2 10 4 40 70 1930 100 000 1 3 4 17 1 2 15 3 4 15 15 16 10 6 55 85 1245 100 00...

Page 5: ...NFLOW CONFIGURATION Most furnaces are shipped from the factory in the upflow configuration with the vent collar extending out through the top plate at the supply end of the furnace In this configurati...

Page 6: ...added when installing the furnace WARNING If vent collar extension is shorter than 30 inches and the vent becomes blocked combustion products may be drawn into furnace causing the furnace to produce...

Page 7: ...stible floor base to correctly install See Figures 6 and 7 for rough in dimensions Figure 6 Downflow Floor Opening Figure 7 Furnace Plenum and Base Installed On A Combustible Floor HORIZONTAL CLEARANC...

Page 8: ...gure 9 Suspending Using Threaded Rod Figure 10 Suspended Using Pipe Strap SECTION 6 PROVIDING COMBUSTION AND VENTILATION AIR The total amount of combustion and ventilation air provided within the buil...

Page 9: ...and ventilation Otherwise follow the instructions for confined space installation below CONFINED SPACE INSTALLATION A furnace installed in a confined space may take combustion and ventilation air fro...

Page 10: ...ur furnace requires two openings of at least 100 000 4 000 or 25 square inches See Figure 12 and Table 3 Figure 12 All Air Directly From Spaces That Freely Access The Outdoors Table 3 Free Opening Are...

Page 11: ...vent and must be vented vertically or nearly vertically unless equipped with an approved mechanical venter In most cases proper venting is achieved by using a conventional vertical vent or chimney Ho...

Page 12: ...pliance common venting Refer to venting tables for correct size vent An undersized vent cannot adequately carry all combustion products outdoors An oversized vent will not heat up rapidly enough to av...

Page 13: ...NING Provide support when using a Type B vent liner in masonry chimney Maintain at least a 1 inch clearance on all sides to reduce possibility of condensate in vent Condensate may cause vent to deteri...

Page 14: ...o the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code A...

Page 15: ...venter manufacturer s installation instructions Adjust the power venter to provide a negative pressure of 0 1 to 0 5 inches W C in the vent pipe leaving the furnace SECTION 9 INSTALLING GAS PIPING PRE...

Page 16: ...ter than 1 2 psi 14 inches W C The furnace must be isolated from the gas supply piping system by turning off the equipment shut off valve during any pressure testing of the system at test pressures eq...

Page 17: ...nd main gas valve Inducer remains energized If flame is sensed within 7 seconds spark is de energized and control proceeds to heat blower on delay If flame is not sensed within 7 seconds control de en...

Page 18: ...Page 18 Installer s Information Manual Figure 22 Furnace Wiring Diagram...

Page 19: ...tage call for heat to the W on the second control SECTION 12 INSTALLING DUCT SYSTEM Properly size duct system based on heat loss and heat gain calculations to assure good heating and cooling installat...

Page 20: ...nflow furnace installation on wood flooring See Section 5 Allowing For Clearances Figure 24 Downflow Filter Application DUCT DAMPERS You may balance airflow with dampers installed in each branch run d...

Page 21: ...y washable filters Table 6 Recommended Filter Size Bottom Return GAS INPUT Btu Hr MOTOR HORSE POWER DISPOSABLE AIR FILTER two required HIGH VELOCITY WASHABLE AIR FILTER 40 000 1 4 1 3 14 X 25 X 1 14 X...

Page 22: ...Is vent connector securely fastened to vent collar 9 Did you completely check gas pipe and controls for gas leaks 10 Does electrical wiring follow current National Electrical Code ANSI NFPA 70 or Cana...

Page 23: ...manifold pressure by turning gas control regulator adjusting screw clockwise to increase pressure or turning counter clockwise to decrease pressure Manifold pressure must be within allowable range be...

Page 24: ...one oven pilot on allow Water heater pilot 1 000 Btu per hour Dryer pilot 500 Btu per hour 2 range burner pilots 1 000 Btu per hour 1 range oven pilot 500 Btu per hour 3 000 Btu per hour Subtracting...

Page 25: ...8001 9001 Heat to to to to to to to to to Value 2000 4000 4000 5000 6000 7000 8000 9000 10000 Btu cu ft Feet Feet Feet Feet Feet Feet Feet Feet Feet 800 849 2 35mm 2 30mm 2 30mm 2 25mm 2 20mm 2 20mm 2...

Page 26: ...otor speed CAUTION Heating speed tap should not be reduced below factory setting Doing so may result in inadequate air circulation and could cause excessive air temperature rise through furnace This c...

Page 27: ...tem airflow can be determined from the Product Data Sheet when duct system static pressure is known Improper airflow in heating mode may result in poor heating performance and reduced heat exchanger l...

Page 28: ...at on highest temperature setting Operate furnace 6 minutes Record supply air and return air temperatures 9 Calculate air temperature rise by subtracting return air temperature from supply air tempera...

Page 29: ...onds Heating blower off delay is factory set at 120 seconds If a different blower off delay is desired 1 Find two small switches located near the 24 volt terminal strip on Control 2 Determine switch s...

Page 30: ...ough the casing hem 5 Label blower motor wires for proper replacement 6 Disconnect blower motor wires from Control See Figure 30 7 Remove 2 screws holding blower door in place Remove blower door 8 Pul...

Page 31: ...dard For The Installation Of Warm Air Heating And Air Conditioning Systems ASHRAE NFPA 90 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances NFPA 211 For more information contact...

Reviews: