background image

Page 30 

 

Installer’s Information Manual 

 

Furnace-room or closet combustion and ventilation air 
openings must be clear and free. 

 

Furnace combustion air openings must be clear and 
free. 

 

Return air duct must be physically sound, sealed to the 
furnace casing and ending outside the space 
containing the furnace. 

 

Supply air ducts and return air ducts must be clear and 
free, and without air leaks. 

  Registers and return grilles must be open and 

unobstructed by rug, carpet or furniture. 

 

The furnace must be well supported without sagging, 
cracks, gaps, etc.  around the base. 

 

There must be no obvious signs of deterioration of the 
furnace.  Inspection must include burners, heat 
exchanger, inducer pan and draft inducer. 

 

Inspect all electrical wiring and connections, including 
electrical ground. 

  Gas pipes must be checked for leaks using a 

commercial soap solution made to detect leaks.  

 

Main burners must be in good adjustment as shown in 
the User’s Information Manual.  Main burner flame 
must be clear blue and centered within the heat 
exchanger openings. 

  Flame holders, located inside each main burner, 

should be checked for lint and debris. 

  Check the furnace area for combustible materials, 

flammable liquid near the furnace, corrosive materials, 
insulation material within 12 inches of the furnace and 
signs of high water levels. 

 

Inspect, clean, or repair as needed the following items: 
blower housing, blower motor, blower wheel, air filters, 
draft inducer and cooling coil. 

NOTE: Blower motor and inducer motor do not require 
oiling. 

SECTION 27.  BLOWER ASSEMBLY 
REMOVAL 

Follow these steps to remove blower assembly: 

1.  Turn off furnace electrical power. 

2.  On downflow furnaces, remove vent pipe inside 

furnace. 

3.  Disconnect room thermostat wires from 24-volt terminal 

strip on Control. 

4.  Locate the five blower motor wires that feed though the 

casing hem. 

5.  Label blower motor wires for proper replacement. 

6.  Disconnect blower motor wires from Control.  See 

Figure 30. 

7.  Remove 2 screws holding blower door in place. 

 

Remove blower door. 

8.  Pull blower motor wires through casing hem. 

9. Remove 

power-disconnect 

assembly located in the 

middle of the blower deck. 

10.  Remove 2 screws holding blower assembly to blower 

deck. 

11.  Slide blower assembly out. 

12. After cleaning blower assembly, re-assemble in 

reverse order making sure speed selections are in 
original positions. 

SECTION 28.  ACCESSORIES 

THERMOSTATS:  These are quality thermostats. Choose 
from the T87 (round w/subbase), T834 (heating and 
cooling) or the T8699 (Chronotherm III), available in white 
only. 

NATURAL GAS TO PROPANE CONVERSION KIT 
(BELOW 6,000 ft): Includes propane regulator spring kit 
and main-burner orifices. 

PROPANE TO NATURAL GAS CONVERSION KIT 
(BELOW 6,000 ft): Includes natural gas regulator spring kit 
and main-burner orifices. 

U.S. HIGH-ALTITUDE NATURAL GAS TO PROPANE 
CONVERSION KIT (ABOVE 6,000 ft): Includes propane 
regulator spring kit, main-burner orifices, and high-altitude 
pressure switch. 

U.S. HIGH-ALTITUDE PROPANE TO NATURAL GAS 
CONVERSION KIT (ABOVE 6,000 ft): Includes natural gas 
regulator spring kit, main-burner orifices, and high-altitude 
pressure switch. 

BOTTOM FILTER CABINET: Four sizes - one size for each 
furnace casing size.  Includes one high velocity, washable 
filter. 

SIDE FILTER CABINET: Attaches to either side of the 
furnace.  One size fits all.  Includes one 16" x 25" x 1" high 
velocity, washable filter. 

BOTTOM CLOSURE: Seals bottom of furnace when only 
side return is used. DOWNFLOW FILTER KIT: Filter 
support mounts between furnace and downflow return 
plenum.  Requires an access panel in plenum.  Includes 
two 16" x 20" x 1" high velocity, washable filters. 

FILTERS: High velocity, washable filters, available in 
cartons of 10.  Sizes include 14 x 25 x 1, 16 x 25 x 1, 20 x 
25 x 1, and 16 x 20 x 1 inches. 

COMBUSTIBLE FLOOR BASE: Allows downflow 
installation on wood flooring.  One size fits all.  

Summary of Contents for w 80

Page 1: ...ller should give you the important documents listed above You should immediately read the User s Information Manual for important safety information to keep you and your family safe Keep these as long...

Page 2: ...uring Air Temperature Rise 28 SECTION 24 Checking Controls 29 SECTION 25 Setting Blower Timings 30 SECTION 26 Maintaining Furnace In Good Working Order 30 SECTION 27 Blower Assembly Removal 31 SECTION...

Page 3: ...to check all connections Rule 8 Completely seal supply and return air ducts to furnace casing Duct system must run to an area outside furnace room or closet Seal duct work wherever it runs through wa...

Page 4: ...2 12 3 4 12 15 16 10 6 40 70 1235 80 000 1 2 4 17 1 2 15 3 4 15 15 16 10 8 50 80 1645 80 000 3 4 4 20 1 2 18 3 4 18 15 16 2 10 4 40 70 1930 100 000 1 3 4 17 1 2 15 3 4 15 15 16 10 6 55 85 1245 100 00...

Page 5: ...NFLOW CONFIGURATION Most furnaces are shipped from the factory in the upflow configuration with the vent collar extending out through the top plate at the supply end of the furnace In this configurati...

Page 6: ...added when installing the furnace WARNING If vent collar extension is shorter than 30 inches and the vent becomes blocked combustion products may be drawn into furnace causing the furnace to produce...

Page 7: ...stible floor base to correctly install See Figures 6 and 7 for rough in dimensions Figure 6 Downflow Floor Opening Figure 7 Furnace Plenum and Base Installed On A Combustible Floor HORIZONTAL CLEARANC...

Page 8: ...gure 9 Suspending Using Threaded Rod Figure 10 Suspended Using Pipe Strap SECTION 6 PROVIDING COMBUSTION AND VENTILATION AIR The total amount of combustion and ventilation air provided within the buil...

Page 9: ...and ventilation Otherwise follow the instructions for confined space installation below CONFINED SPACE INSTALLATION A furnace installed in a confined space may take combustion and ventilation air fro...

Page 10: ...ur furnace requires two openings of at least 100 000 4 000 or 25 square inches See Figure 12 and Table 3 Figure 12 All Air Directly From Spaces That Freely Access The Outdoors Table 3 Free Opening Are...

Page 11: ...vent and must be vented vertically or nearly vertically unless equipped with an approved mechanical venter In most cases proper venting is achieved by using a conventional vertical vent or chimney Ho...

Page 12: ...pliance common venting Refer to venting tables for correct size vent An undersized vent cannot adequately carry all combustion products outdoors An oversized vent will not heat up rapidly enough to av...

Page 13: ...NING Provide support when using a Type B vent liner in masonry chimney Maintain at least a 1 inch clearance on all sides to reduce possibility of condensate in vent Condensate may cause vent to deteri...

Page 14: ...o the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code A...

Page 15: ...venter manufacturer s installation instructions Adjust the power venter to provide a negative pressure of 0 1 to 0 5 inches W C in the vent pipe leaving the furnace SECTION 9 INSTALLING GAS PIPING PRE...

Page 16: ...ter than 1 2 psi 14 inches W C The furnace must be isolated from the gas supply piping system by turning off the equipment shut off valve during any pressure testing of the system at test pressures eq...

Page 17: ...nd main gas valve Inducer remains energized If flame is sensed within 7 seconds spark is de energized and control proceeds to heat blower on delay If flame is not sensed within 7 seconds control de en...

Page 18: ...Page 18 Installer s Information Manual Figure 22 Furnace Wiring Diagram...

Page 19: ...tage call for heat to the W on the second control SECTION 12 INSTALLING DUCT SYSTEM Properly size duct system based on heat loss and heat gain calculations to assure good heating and cooling installat...

Page 20: ...nflow furnace installation on wood flooring See Section 5 Allowing For Clearances Figure 24 Downflow Filter Application DUCT DAMPERS You may balance airflow with dampers installed in each branch run d...

Page 21: ...y washable filters Table 6 Recommended Filter Size Bottom Return GAS INPUT Btu Hr MOTOR HORSE POWER DISPOSABLE AIR FILTER two required HIGH VELOCITY WASHABLE AIR FILTER 40 000 1 4 1 3 14 X 25 X 1 14 X...

Page 22: ...Is vent connector securely fastened to vent collar 9 Did you completely check gas pipe and controls for gas leaks 10 Does electrical wiring follow current National Electrical Code ANSI NFPA 70 or Cana...

Page 23: ...manifold pressure by turning gas control regulator adjusting screw clockwise to increase pressure or turning counter clockwise to decrease pressure Manifold pressure must be within allowable range be...

Page 24: ...one oven pilot on allow Water heater pilot 1 000 Btu per hour Dryer pilot 500 Btu per hour 2 range burner pilots 1 000 Btu per hour 1 range oven pilot 500 Btu per hour 3 000 Btu per hour Subtracting...

Page 25: ...8001 9001 Heat to to to to to to to to to Value 2000 4000 4000 5000 6000 7000 8000 9000 10000 Btu cu ft Feet Feet Feet Feet Feet Feet Feet Feet Feet 800 849 2 35mm 2 30mm 2 30mm 2 25mm 2 20mm 2 20mm 2...

Page 26: ...otor speed CAUTION Heating speed tap should not be reduced below factory setting Doing so may result in inadequate air circulation and could cause excessive air temperature rise through furnace This c...

Page 27: ...tem airflow can be determined from the Product Data Sheet when duct system static pressure is known Improper airflow in heating mode may result in poor heating performance and reduced heat exchanger l...

Page 28: ...at on highest temperature setting Operate furnace 6 minutes Record supply air and return air temperatures 9 Calculate air temperature rise by subtracting return air temperature from supply air tempera...

Page 29: ...onds Heating blower off delay is factory set at 120 seconds If a different blower off delay is desired 1 Find two small switches located near the 24 volt terminal strip on Control 2 Determine switch s...

Page 30: ...ough the casing hem 5 Label blower motor wires for proper replacement 6 Disconnect blower motor wires from Control See Figure 30 7 Remove 2 screws holding blower door in place Remove blower door 8 Pul...

Page 31: ...dard For The Installation Of Warm Air Heating And Air Conditioning Systems ASHRAE NFPA 90 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances NFPA 211 For more information contact...

Reviews: