background image

Installer’s Information Manual 

 

Page 5 

Provide ample space for servicing and cleaning, and 
around air openings into the combustion chamber. 

 

Location must allow 30 inches minimum front clearance for 
service. 

You may install furnace on non-combustible flooring or for 
upflow or horizontal installations on wood flooring.  A 
combustible floor base, available from the manufacturer, is 
required for downflow furnace installation on wood flooring.  
See Section 5, "Allowing For Clearances." 

Install the furnace so all electrical components are 
protected from water. 

Install the furnace level. 

When the furnace is in a repair garage or inside the heated 
space, exhaust fans can adversely affect its operation.  
Exhaust fans in kitchen, bathrooms, clothes dryers or 
anywhere within heated space increase combustion and 
ventilation air requirements.  This is because exhaust fans 
reduce the amount of combustion and ventilation air 
available to the furnace.  A fireplace also reduces amount 
of combustion and ventilation air. 

 

 

WARNING

:  You must allow for these reductions 

or there could be inadequate combustion and ventilation 
air.  This could cause nausea, death by asphyxiation, or 
fire. 

Sufficient air must be provided to ensure there will not be a 
negative pressure in furnace room or space.  In addition, 
there must be a positive seal between furnace and return 
air duct to avoid pulling air from burner area. 

When a cooling unit is installed with this furnace, the 
furnace must be installed on the upstream side of the 
cooling unit to avoid condensation in the furnace heat 
exchanger. 

When furnace is in a residential garage, it must be installed 
so that the main burners are located no less than 18 inches 
above the floor.  Also, furnace should be protected from 
physical damage by vehicles.  

When furnace is in a public garage, airplane hanger, or 
other building having hazardous atmosphere, install unit in 
accordance with recommended good practice requirements 
of the National Fire Protection Association, Inc. Consult 
local code authorities for additional location requirements. 

See Figure 3 for dimensions and specifications. 

SECTION 4.  CONVERSION TO 
DOWNFLOW CONFIGURATION 

Most furnaces are shipped from the factory in the upflow 
configuration with the vent collar extending out through the 
top plate at the supply end of the furnace.  In this 
configuration, the furnace can be installed as an upflow 
furnace or as a horizontal furnace on its left or right side. 

In the downflow configuration, the inducer assembly is 
repositioned - locating the vent collar inside the furnace 

vestibule near the manifold pipe.  In this configuration the 
furnace can be installed as a downflow furnace or as a 
horizontal furnace on its left or right side. 

Before starting the conversion, lay the furnace on its back 
with the front door removed.  Read the following 
instructions all the way through and study the components 
described.  See Figure 4 for component identification and 
location. 

NOTE:  If possible, decide on direction of gas entry now, 
because the screws to change direction of the furnace gas-
control-inlet elbow are accessible during this conversion.  
See Section 9, "Installing Gas Piping." 

1.  Remove the two junction box mounting screws and the 

four top plate mounting screws.  Save all screws.  
Remove the top plate and front duct flange. 

2.  Disconnect  pressure switch wires and inducer motor. 

3.  Remove and save ten screws from the inducer pan.  

Do not drop screws into heat exchanger openings. 

4.  Lift inducer/pan assembly about 1/4 inch and tilt left 

side up to clear top casing flanges. 

5.  Rotate inducer/pan assembly 180 degrees as shown in 

Figure 5.  Line up mounting holes and replace the ten 
screws in inducer pan. 

6.  If nessessary, remove wire tie(s) from the excess 

length of the wire harness containing the pressure 
switch wires (blue and purple). 

7.  Re-connect pressure switch wires as follows. (Wires 

are numbered on insulation near terminals). 

a)  Purple wire (#6) to pressure switch common 

(C) terminal. 

b)  Blue wire (#5) to pressure switch normally 

open (NO) terminal. 

c)  Route pressure switch wires around inducer 

motor and away from hot flue box. 

8.  Re-connect inducer motor. 

9.  Replace wire tie in the same area such that wires do 

not touch hot flue box or inducer pan. 

10.  Remove and save the four screws that secure base 

panel to casing sides.  Remove base panel. 

11.  Install top plate removed in step 1 in place of the base 

panel.  Secure with four screws.  Vent collar is now 
lined up with vent outlet hole in top plate. 

 

Summary of Contents for w 80

Page 1: ...ller should give you the important documents listed above You should immediately read the User s Information Manual for important safety information to keep you and your family safe Keep these as long...

Page 2: ...uring Air Temperature Rise 28 SECTION 24 Checking Controls 29 SECTION 25 Setting Blower Timings 30 SECTION 26 Maintaining Furnace In Good Working Order 30 SECTION 27 Blower Assembly Removal 31 SECTION...

Page 3: ...to check all connections Rule 8 Completely seal supply and return air ducts to furnace casing Duct system must run to an area outside furnace room or closet Seal duct work wherever it runs through wa...

Page 4: ...2 12 3 4 12 15 16 10 6 40 70 1235 80 000 1 2 4 17 1 2 15 3 4 15 15 16 10 8 50 80 1645 80 000 3 4 4 20 1 2 18 3 4 18 15 16 2 10 4 40 70 1930 100 000 1 3 4 17 1 2 15 3 4 15 15 16 10 6 55 85 1245 100 00...

Page 5: ...NFLOW CONFIGURATION Most furnaces are shipped from the factory in the upflow configuration with the vent collar extending out through the top plate at the supply end of the furnace In this configurati...

Page 6: ...added when installing the furnace WARNING If vent collar extension is shorter than 30 inches and the vent becomes blocked combustion products may be drawn into furnace causing the furnace to produce...

Page 7: ...stible floor base to correctly install See Figures 6 and 7 for rough in dimensions Figure 6 Downflow Floor Opening Figure 7 Furnace Plenum and Base Installed On A Combustible Floor HORIZONTAL CLEARANC...

Page 8: ...gure 9 Suspending Using Threaded Rod Figure 10 Suspended Using Pipe Strap SECTION 6 PROVIDING COMBUSTION AND VENTILATION AIR The total amount of combustion and ventilation air provided within the buil...

Page 9: ...and ventilation Otherwise follow the instructions for confined space installation below CONFINED SPACE INSTALLATION A furnace installed in a confined space may take combustion and ventilation air fro...

Page 10: ...ur furnace requires two openings of at least 100 000 4 000 or 25 square inches See Figure 12 and Table 3 Figure 12 All Air Directly From Spaces That Freely Access The Outdoors Table 3 Free Opening Are...

Page 11: ...vent and must be vented vertically or nearly vertically unless equipped with an approved mechanical venter In most cases proper venting is achieved by using a conventional vertical vent or chimney Ho...

Page 12: ...pliance common venting Refer to venting tables for correct size vent An undersized vent cannot adequately carry all combustion products outdoors An oversized vent will not heat up rapidly enough to av...

Page 13: ...NING Provide support when using a Type B vent liner in masonry chimney Maintain at least a 1 inch clearance on all sides to reduce possibility of condensate in vent Condensate may cause vent to deteri...

Page 14: ...o the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code A...

Page 15: ...venter manufacturer s installation instructions Adjust the power venter to provide a negative pressure of 0 1 to 0 5 inches W C in the vent pipe leaving the furnace SECTION 9 INSTALLING GAS PIPING PRE...

Page 16: ...ter than 1 2 psi 14 inches W C The furnace must be isolated from the gas supply piping system by turning off the equipment shut off valve during any pressure testing of the system at test pressures eq...

Page 17: ...nd main gas valve Inducer remains energized If flame is sensed within 7 seconds spark is de energized and control proceeds to heat blower on delay If flame is not sensed within 7 seconds control de en...

Page 18: ...Page 18 Installer s Information Manual Figure 22 Furnace Wiring Diagram...

Page 19: ...tage call for heat to the W on the second control SECTION 12 INSTALLING DUCT SYSTEM Properly size duct system based on heat loss and heat gain calculations to assure good heating and cooling installat...

Page 20: ...nflow furnace installation on wood flooring See Section 5 Allowing For Clearances Figure 24 Downflow Filter Application DUCT DAMPERS You may balance airflow with dampers installed in each branch run d...

Page 21: ...y washable filters Table 6 Recommended Filter Size Bottom Return GAS INPUT Btu Hr MOTOR HORSE POWER DISPOSABLE AIR FILTER two required HIGH VELOCITY WASHABLE AIR FILTER 40 000 1 4 1 3 14 X 25 X 1 14 X...

Page 22: ...Is vent connector securely fastened to vent collar 9 Did you completely check gas pipe and controls for gas leaks 10 Does electrical wiring follow current National Electrical Code ANSI NFPA 70 or Cana...

Page 23: ...manifold pressure by turning gas control regulator adjusting screw clockwise to increase pressure or turning counter clockwise to decrease pressure Manifold pressure must be within allowable range be...

Page 24: ...one oven pilot on allow Water heater pilot 1 000 Btu per hour Dryer pilot 500 Btu per hour 2 range burner pilots 1 000 Btu per hour 1 range oven pilot 500 Btu per hour 3 000 Btu per hour Subtracting...

Page 25: ...8001 9001 Heat to to to to to to to to to Value 2000 4000 4000 5000 6000 7000 8000 9000 10000 Btu cu ft Feet Feet Feet Feet Feet Feet Feet Feet Feet 800 849 2 35mm 2 30mm 2 30mm 2 25mm 2 20mm 2 20mm 2...

Page 26: ...otor speed CAUTION Heating speed tap should not be reduced below factory setting Doing so may result in inadequate air circulation and could cause excessive air temperature rise through furnace This c...

Page 27: ...tem airflow can be determined from the Product Data Sheet when duct system static pressure is known Improper airflow in heating mode may result in poor heating performance and reduced heat exchanger l...

Page 28: ...at on highest temperature setting Operate furnace 6 minutes Record supply air and return air temperatures 9 Calculate air temperature rise by subtracting return air temperature from supply air tempera...

Page 29: ...onds Heating blower off delay is factory set at 120 seconds If a different blower off delay is desired 1 Find two small switches located near the 24 volt terminal strip on Control 2 Determine switch s...

Page 30: ...ough the casing hem 5 Label blower motor wires for proper replacement 6 Disconnect blower motor wires from Control See Figure 30 7 Remove 2 screws holding blower door in place Remove blower door 8 Pul...

Page 31: ...dard For The Installation Of Warm Air Heating And Air Conditioning Systems ASHRAE NFPA 90 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances NFPA 211 For more information contact...

Reviews: