7

OPM-135/C

VENTILATION REQUIREMENTS

OPEN SKID 

WARNING: EQUIPMENT DAMAGE:

It is the installer’s responsibility to ensure that there is 

sufficient cooling air available to prevent the engine 

and generator from over heating. Damage caused by 

overheating is not covered by warranty.

Providing proper air movement during your installation 

planning is essential. You will need to provide a fresh air 

inlet as well as a hot air outlet (to the outside of protection 

housing) for proper engine performance. These engine-

generator sets are equipped with unit mount radiators and 

the engine is equipped with a pusher type fan. The hot 

air from the face of the radiator must be ducted out of the 

enclosure to ensure proper cooling. Failing to do so will 

allow the hot air to recirculate around the radiator causing 

the engine to overheat, resulting in an engine shutdown 

and damage. If louvers are used in front of the hot air duct 

to protect the unit from outside weather, the louvers should 

be 1½ times as large as the area of the radiator face to 

prevent back pressure.

Foam or other seals can be used to form a tight lip forcing 

all of the air from the engine fan out of the enclosure.

In addition to a hot air discharge, you must plan a fresh air 

intake opposite the radiator discharge. Their fresh air inlets 

should be 1½ to 2 times larger than the radiator face. The 

extra air inlet area is required to minimize restriction and 

to provide combustion air for the engine. Do not block 

fresh air intakes with other equipment as this will result 

in insufficient air flow to the engine for cooling. Installing 

them opposite the hot air discharge will allow a sweeping 

flow of cooling air across the engine, preventing hot spots.

The WINCO installation manual OPM-112 contains 

additional information on indoor, open skid installations 

and is available electronically through our website or by 

requesting a copy from the factory.

EXHAUST INSTALLATION

WARNING: PERSONAL INJURY

Improper exhaust installation will allow dangerous gases to 

seep into enclosed spaces causing a hazard to your health 

and/or death. 

All exhaust must be piped out of the enclosure. When 

selecting a location to exhaust fumes make sure that the 

potential for contact with people is controlled. Exhaust can 

enter buildings through windows, ventilation systems and 

other openings if proper precautions are not followed.

Radiator 

Discharge

Air Inlet 

Duct

Exhaust

Thimble

Flex 

Piping

The exhaust must be isolated from the vibration of the 

engine. If the exhaust is connected in a rigid system it will 

result in damage to the engine. The generator comes 

equipped with an engine mounted flex pipe to aid your 

installation. Ensure proper alignment with the generator. 

The flex can be eliminated if it is pushed to one side to make 

a connection. 

The most direct path possible should be used to get to the 

outside of the enclosure. Each bend restricts the pipe and 

increases back pressure. It may be necessary to increase the 

exhaust pipe diameter in some applications. 

The exhaust pipe is very hot. When passing through the 

structure it is critical that a thimble or other appropriate 

technique is used to dissipate the heat and prevent the 

structure from catching on fire. 

It is preferable to exhaust out the side of the enclosures. 

Slope the pipe slightly downward away from the engine 

to cause any water in the exhaust to run away from the 

engine. Do not exhaust near intake. Once outside the 

enclosure a rain cap or other technique must be used to 

keep water out of the exhaust. In mobile applications make 

sure the rain flap faces to the rear of the vehicle so that it is 

not blown open during transportation. 

The generator ships with a critical grade muffler that should 

be installed to decrease noise. It can be mounted either 

internally or externally to the enclosure. The muffler cannot 

increase back pressure to more than 0.725 psi.

INSTALLING THE FUEL LINE

WARNING: FIRE DANGER:

Connecting rigid fuel line (i.e. steel or copper line) directly 

to the inlet fuel filter or fuel pump may cause the fuel line to 

crack during operation creating a serious fire hazard.

The fuel supply should be as close to the engine as 

possible. This will reduce the installation cost of fuel runs 

and minimize line losses. The diesel fuel supply should be 

no more than 3 feet below the fuel inlet on the pump. If 

your fuel supply is lower than three feet you may have to 

install an additional lift pump to bring the fuel up to the 

mechanical fuel pump on the engine.

The information in this manual is offered to assist you in 

providing the proper fuel for your engine. However, this 

information is only provided to inform you of the engine’s 

requirements and assist in making you aware of the 

decisions you must make. In no case should the instructions 

or information provided be interpreted to conflict with any 

local, state, or national codes. If in doubt, always consult 

your local fire marshal or fuel supplier.

Engine generator sets are properly adjusted before they 

leave the factory. Connecting a fuel supply with adequate 

supply volume is critical to reliable operation. Diesel units 

with optional base mounted fuel tanks are pre-plumbed to 

the mechanical fuel pump on the engine. 

Open skid mounted Diesel units are often supplied with 

capped inlet and return lines. The use of a sustainable 

customer supplied flexible fuel line is essential between 

the engine and fuel supply to provide a vibration break 

between your fuel supply and the engine.

Summary of Contents for DR20I4-/1 Series

Page 1: ...AL 1 DEG ANGULAR 9 15 2016 ZJF COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact us on this unit it will help us to...

Page 2: ...FILTER CLEANING RADIATOR CHANGING THE FUEL FILTER STORAGE MAINTENANCE SCHEDULE TROUBLESHOOTING TABLE 16 ENGINE HARNESS SCHEMATIC 17 WIRING SIZE TABLE 17 DSE7310 WIRING DIAGRAM 18 WIRING DIAGRAMS 19 LI...

Page 3: ...k exhaust gas asphyxiation or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings...

Page 4: ...everal of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts Be sure to have the main WINCO uni...

Page 5: ...enerator for operation take a couple of minutes to ensure the unit you have received is the correct model and review the specification pages in this manual to ensure that this unit meets your job requ...

Page 6: ...aller The factory weather enclosures are acoustical housing intended for outdoor installation only Factory weather enclosed units are not intended to be used indoors and no support is available to ass...

Page 7: ...pipe to aid your installation Ensure proper alignment with the generator The flex can be eliminated if it is pushed to one side to make a connection The most direct path possible should be used to ge...

Page 8: ...ert the wire into the larger circular hole B Remove the screwdriver to secure the wire into place A B A C ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNE...

Page 9: ...ries of remote accessories that can help provide useful information to operators These accessories communicate over the DSE Net Terminal blocks are wired to the distribution panel to aid in installati...

Page 10: ...must be clean and tight Depending on your battery type check the electrolyte in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition...

Page 11: ...N PERSONAL INJURY Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Remove the dipstick and ensure the oil level is between the Min and Ma...

Page 12: ...AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE YOU KNOW WHERE THE HIGH VOLTAGE WILD LEG IS IT MUST BE IN THE SAME LOCATION ON THE LINE SIDE AS I...

Page 13: ...not connected to a battery charger A solar charger kit is the easiest way to always maintain the battery during storage in mobile applications The supplied battery charger can be plugged in to an exte...

Page 14: ...O NOT dispose or allow oil to seep into the ground or sewer systems doing so will cause environmental damage CHANGING OIL FILTER The filter must be replaced when the lubricant oil is changed Only use...

Page 15: ...iquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will cause environmental damage CLEANING RADIATOR The surfaces of the radiator come...

Page 16: ...citer stator AC short in the output leads Defective open generator output breaker Wiring error protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine fo...

Page 17: ...418 431 458 480 519 550 572 585 50 68 86 100 118 137 155 177 205 237 264 291 319 346 391 432 473 487 505 532 560 605 642 669 683 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 600 700 750 800 900 100...