7
OPM-135/C
VENTILATION REQUIREMENTS
OPEN SKID
WARNING: EQUIPMENT DAMAGE:
It is the installer’s responsibility to ensure that there is
sufficient cooling air available to prevent the engine
and generator from over heating. Damage caused by
overheating is not covered by warranty.
Providing proper air movement during your installation
planning is essential. You will need to provide a fresh air
inlet as well as a hot air outlet (to the outside of protection
housing) for proper engine performance. These engine-
generator sets are equipped with unit mount radiators and
the engine is equipped with a pusher type fan. The hot
air from the face of the radiator must be ducted out of the
enclosure to ensure proper cooling. Failing to do so will
allow the hot air to recirculate around the radiator causing
the engine to overheat, resulting in an engine shutdown
and damage. If louvers are used in front of the hot air duct
to protect the unit from outside weather, the louvers should
be 1½ times as large as the area of the radiator face to
prevent back pressure.
Foam or other seals can be used to form a tight lip forcing
all of the air from the engine fan out of the enclosure.
In addition to a hot air discharge, you must plan a fresh air
intake opposite the radiator discharge. Their fresh air inlets
should be 1½ to 2 times larger than the radiator face. The
extra air inlet area is required to minimize restriction and
to provide combustion air for the engine. Do not block
fresh air intakes with other equipment as this will result
in insufficient air flow to the engine for cooling. Installing
them opposite the hot air discharge will allow a sweeping
flow of cooling air across the engine, preventing hot spots.
The WINCO installation manual OPM-112 contains
additional information on indoor, open skid installations
and is available electronically through our website or by
requesting a copy from the factory.
EXHAUST INSTALLATION
WARNING: PERSONAL INJURY
Improper exhaust installation will allow dangerous gases to
seep into enclosed spaces causing a hazard to your health
and/or death.
All exhaust must be piped out of the enclosure. When
selecting a location to exhaust fumes make sure that the
potential for contact with people is controlled. Exhaust can
enter buildings through windows, ventilation systems and
other openings if proper precautions are not followed.
Radiator
Discharge
Air Inlet
Duct
Exhaust
Thimble
Flex
Piping
The exhaust must be isolated from the vibration of the
engine. If the exhaust is connected in a rigid system it will
result in damage to the engine. The generator comes
equipped with an engine mounted flex pipe to aid your
installation. Ensure proper alignment with the generator.
The flex can be eliminated if it is pushed to one side to make
a connection.
The most direct path possible should be used to get to the
outside of the enclosure. Each bend restricts the pipe and
increases back pressure. It may be necessary to increase the
exhaust pipe diameter in some applications.
The exhaust pipe is very hot. When passing through the
structure it is critical that a thimble or other appropriate
technique is used to dissipate the heat and prevent the
structure from catching on fire.
It is preferable to exhaust out the side of the enclosures.
Slope the pipe slightly downward away from the engine
to cause any water in the exhaust to run away from the
engine. Do not exhaust near intake. Once outside the
enclosure a rain cap or other technique must be used to
keep water out of the exhaust. In mobile applications make
sure the rain flap faces to the rear of the vehicle so that it is
not blown open during transportation.
The generator ships with a critical grade muffler that should
be installed to decrease noise. It can be mounted either
internally or externally to the enclosure. The muffler cannot
increase back pressure to more than 0.725 psi.
INSTALLING THE FUEL LINE
WARNING: FIRE DANGER:
Connecting rigid fuel line (i.e. steel or copper line) directly
to the inlet fuel filter or fuel pump may cause the fuel line to
crack during operation creating a serious fire hazard.
The fuel supply should be as close to the engine as
possible. This will reduce the installation cost of fuel runs
and minimize line losses. The diesel fuel supply should be
no more than 3 feet below the fuel inlet on the pump. If
your fuel supply is lower than three feet you may have to
install an additional lift pump to bring the fuel up to the
mechanical fuel pump on the engine.
The information in this manual is offered to assist you in
providing the proper fuel for your engine. However, this
information is only provided to inform you of the engine’s
requirements and assist in making you aware of the
decisions you must make. In no case should the instructions
or information provided be interpreted to conflict with any
local, state, or national codes. If in doubt, always consult
your local fire marshal or fuel supplier.
Engine generator sets are properly adjusted before they
leave the factory. Connecting a fuel supply with adequate
supply volume is critical to reliable operation. Diesel units
with optional base mounted fuel tanks are pre-plumbed to
the mechanical fuel pump on the engine.
Open skid mounted Diesel units are often supplied with
capped inlet and return lines. The use of a sustainable
customer supplied flexible fuel line is essential between
the engine and fuel supply to provide a vibration break
between your fuel supply and the engine.