CAUTION
Never run the AC and DC wiring on the same conduit.
ASCO 185 UL SWITCH
Your DC connection points in the ASCO 185 UL ATS are on
the terminal block on the bottom of the controller in the
lower left hand corner of the ATS panel. The terminal block
(TB7) is numbered 1 through 9. These terminals will accept
# 22 - # 14 AWG stranded wire. It is recommended that you
use # 16 AWG for distances up to 200 feet. You need to run
two (2) wires from the engine generator set to the transfer
switch. You will be using terminals 4 and 5, wire Start # 23
will connect to terminal # 5 and wire Battery Negative #
1 will connect to terminal # 4. See the following table and
illustration.
Wire #
Purpose
Recommended Color
#23
Start
Black
#1
Battery negative
White
DC ELECTRICAL INTERCONNECTION