with or without a load transfer. Normally, WINCO
generators exercise without a load transfer. This is because
you may not with to have a momentary interruption of
power. Turn the exerciser dip switch on. Then set the “with
load” or “without load”. See the following table.
Function
Factory
Setting
Dip
Switch
Dip
Actuator
Actuator
Position
Clock
Battery
Off
S2
10
On (up)
Off (down)
Exerciser
Off
S1
7
On (up)
Off (down)
With load
or without
load
Without
Load
S1
8
With (up)
Without (down)
SETTING THE EXERCISER
Press and hold (5 seconds) the Set Engine Exerciser button.
The exercise period occurs immediately and at the same
time weekly thereafter. The status light below the button
blinks during the exercise period (including cool down). The
light stays on to indicate that the exerciser has been set. If
the light is off, the exerciser has not been set.
CANCELING AN ACTIVE EXERCISE PERIOD
Press the Bypass Time Delay button to stop an exercising
generator. If exercise with load is set, the ATS retransfers the
load to the utility, then stops the generator after cooldown.
WARNING
With a total power failure (utility power fails and the
generator fails to start and run), the exerciser must be
resest after the power is restored.
The ASCO 185 has settings that can be changed for various
applications. The dipswitch options are explained in the
ASCO 185 Operator’s Manual.
This completes your installation and unit testing. ALWAYS
leave the system in automatic mode unless servicing the
unit. For automatic operation, the auto mode icon must be
displayed on the engine control module display.
Summary of Contents for PSS20B2W/A
Page 19: ...19 60706 229 G...
Page 24: ...24 60706 229 G OUTLINE DRAWING...
Page 25: ...25 60706 229 G PAD LAYOUT 60706 229 23 12270 01 60706 229 ET A ENGINE GENERATOR SET PAD LAYOUT...
Page 26: ...26 60706 229 G AC AND DC GENERATOR SCHEMATIC...
Page 27: ...27 60706 229 G AC WIRING SCHEMATIC PSS20 3 A PSS20 17 A PSS20 18 A PSS20 4 A...