background image

13

OPM-117/D

Wire Temperature Rating

Cu Conductor

Al Conductor

kW

Volts

PH Amp

75°C

90°C

75°C

90°C

60

120/240

1

250

300 

MCM

250 

MCM

500 

MCM

350 

MCM

60

120/208

3

200

4/0 AWG

3/0 

AWG

300 

MCM

250 

MCM

60

120/240

3

175

3/0 AWG

2/0 

AWG

250 

MCM

4/0 

AWG

60

277/480

3

90

#2 AWG

#3 AWG

1/0 

AWG

#2 

AWG

90

120/240

1

400

600 

MCM

500 

MCM

(NOTE 1)

600 

MCM

90

120/208

3

300

500 

MCM

350 

MCM

600 

MCM

500 

MCM

90

120/240

3

300

300 

MCM

250 

MCM

500 

MCM

350 

MCM

90

277/480

3

150

2/0 AWG

1/0 

AWG

4/0 

AWG

3/0 

AWG

Note 1 - Two 250 MCM may be used.

For additional information on wire sizing refer to table 310-
16 of the National Electrical Code ANSI/NFPA 70.

C - Ground Lug, These ground lugs are bonded to 

ground and are provided for you to connect your 

ground wire from the transfer switch to. The lugs on 

the 60kW will accommodate #1 AWG to 250 MCM and 

should be torqued to 250 in. lbs. The lugs on the 90kW 

will accommodate #1 AWG to 300 MCM and should be 

torqued to 250 in. lbs.

D. 120 Volt Terminal Block. These terminals are for shore 

power. For a power line with one lead, plug into either 

terminals, ensuring the jumper is still connected. To isolate 

two leads for use of two separate circuit breakers, the 

jumper must be removed.

WARNING: EQUIPMENT DAMAGE

When installing a three-phase 240 Volt system, be sure 

you know which lead is the high voltage “wild” leg (208 

Volt to neutral). The generator normally carriers the high 

voltage on the G2 lead.

The load current carrying wires (L) and (T) must be sized 

to handle the maximum load current without excessive 

voltage drop. By code, the wire must be heavy enough to 

handle the full current rating of the mainline circuit breaker 

(or fuse) in the entrance (or sub-panel) protecting the 

contactor switch.

All wires should be installed in rigid or flexible conduit. 

(knockouts are provided in the control box).

GROUNDING

A grounding lug has been provided on the engine 

generator set. Check your local codes for proper grounding 

requirements.

NOTICE:  

CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL 

FIELD WIRING CONNECTIONS TO TERMINAL OF A CLASS 

2 CIRCUIT.

WARNING

A mainline circuit breaker has been provided inside the 

generator housing. During all wiring installation, make 

sure the breaker is in the off position and the generator 

operators switch is in the off position. 

A - Neutral Lugs, These neutral lugs are isolated from 

ground and provided for you to connect your neutral wire 

from the transfer switch. The lugs on the 60 kW will handle 

wire sizes #4 AWG to 300 MCM and should be torqued to 

250 in lbs. The lugs on the 90 kW will accommodate #1 

AWG to 600 MCM and should be torqued to 300 in lbs.

B - Generator Circuit Breaker, This circuit breaker provides 

overload protection for the generator. Your power feeds 

from the transfer switch will connect to the bottom lugs on 

the circuit breaker. The generator power feeds have already 

been wired into the upper lugs.

The table below gives you the circuit breaker size, lug wire 

sizes and torque specification. (see the actual breaker for 

additional information and restrictions)

kW

Volts

PH Amp

Wire Capability

60

120/240

1

250

#1 AWG-600 MCM

60

120/208

3

200

#4 AWG-300 MCM

60

120/240

3

175

#4 AWG-300 MCM

60

277/480

3

90

#14 - #3/0 AWG

90

120/240

1

400

#1 AWG-600 MCM

90

120/208

3

300

#1 AWG-600 MCM

90

120/240

3

300

#1 AWG-600 MCM

90

277/480

3

150

#14 - #30 AWG

The following table shows the minimum conductor sizes 

between the generator and the ATS, based on wire type 

and temperature rating. Wire has been derated 40° C 

ambient temperatures.

 A

 

C

 

B

 

D

PSS60 CB PANEL

A

 

C

 

B

 

D

PSS90 CB PANEL

AC ELECTRICAL CONNECTIONS

Summary of Contents for PSS60/E

Page 1: ...r need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ________________________________________ www wincogen com 16200 016 ...

Page 2: ...L PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 11 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 13 GROUNDING MOUNTING THE ATS DC ELECTRICAL INTERCONNECTION 15 ASCO 185 UL SWITCH ASCO 300 UL SWITCH INITIAL START UP STARTING PROCEDURE 17 VOLTAGE REGULATOR WIRING 18 AUTOMATIC TRANSFER SWITCH ENGINE GENERATOR SET COLD WEATHER...

Page 3: ...NCO generator You have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is important that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty l...

Page 4: ...esent a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator set or fuel tank D Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved container and only in a well ventilated ...

Page 5: ...ms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E PSS90 F LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA 80 100 100 100 Phase Single Three Three Three Amps 333 278 240 120 CB Size 400 300 300 150 Hertz 60 60 60 60 Natural Gas Wattage 90 000 90 000 90 000 90 000 Volts 120 240 120 208 120 240 277 480 ...

Page 6: ...r outside installation The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 second transfer delay to allow the engine to warm up b...

Page 7: ...e received is the correct model and review the specification pages in this manual to ensure that this unit meets your job requirements CAUTION EQUIPMENT DAMAGE These units are shipped with oil and a 50 50 mix of coolant Be sure to check all fluid levels before operating See engine manufacturer s instruction manual for recommended oil requirements before initial starting Once generator set is on si...

Page 8: ...ator to the generator set INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery disconnected These engine generator sets are designed to be mounted on a pad where there is proper ventilation The transfer switch is mounted next to your electrical entrance or distribution panel inside or outside the building Consult a q...

Page 9: ... withdrawal a primary regulator is not required on the supply tank The supply line is connected to a liquid withdrawal valve on the supply tank and runs directly to the fuellock strainer mounted on the engine generator set Normally a 3 8 to 1 2 inch copper line is acceptable for this type of fuel installation You must be sure that the valve you have connected to on the supply tank is in fact a liq...

Page 10: ...he necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cause excessive engine wear and shorten its useful life Before starting the engine Check the coolant level in the radiator If it is low refill as specified in the engine manufacturer s maintenance instructions The radiator should be filled to about 1 inch below the filler neck The f...

Page 11: ...ttery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge condition INSTALLING THE BATTERY CAUTION In the following battery installation procedure check to be sure the selector switch rem...

Page 12: ...on without over charging them During this stage the green LED is constantly lit There are optional 5 and 10 amp chargers available that may be installed on some units The block heater is thermostatically controlled and when plugged in will maintain the engine coolant temperature between 100 and 120 degrees F NOTICE The trickle charger is not intended to recharge a battery which has become complete...

Page 13: ...el protecting the contactor switch All wires should be installed in rigid or flexible conduit knockouts are provided in the control box GROUNDING A grounding lug has been provided on the engine generator set Check your local codes for proper grounding requirements NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNECTIONS TO TERMINAL OF A CLASS 2 CIRCUIT WARNING A mainline circu...

Page 14: ...d in the emergency distribution panel The A T S is then installed between the main panel and the emergency distribution panel Suggested circuits freezer refrigerator furnace emergency lights sump pump emergency outlet circuits etc Total running load must not exceed generator rating WARNING A service disconnect must be installed in front of the ATS panel as the ATS is not service entrance rated Thi...

Page 15: ...y charger to DSE7310 MKII controller D Remote Display Panel Interface Terminals These interface terminals are pre wired to allow for the connection of a remote display This display allows for the remote annunciation of alarms at a location such as a nurses station or a control room E Battery Positive and Ground battery negative These terminals are dedicated for any accessory that will be installed...

Page 16: ...ncy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step is to check the voltage at the generator terminals in the Automatic Transfer Switch The voltage between the G1 and the G3 terminals should be the same as it was on the generator front panel The volta...

Page 17: ...ce as a lamp test function MENU NAVIGATION Used for navigating the instrumentation event log and configuration screens A small rocker switch is located on the underside of the engine control cabinet On gaseous models the engine timing is controlled by the ECU on the engine and you need to tell it what fuel you want to operate on LP or NG On diesel models this switch has been disconnected and will ...

Page 18: ... effect 4 LINK POWER RESPONSE A B 550kW Fast B C 100 550kW Fast A C 100kW Fast B D 100kW Slow 5 UFRO Under Frequency Roll Off Clockwise decreases KNEE point 6 SWITCH Select alternator frequency for UFRO SWITCH LEFT 60Hz SWITCH RIGHT 50Hz 7 LED Indicator Light LED light on in UFRO or O EXC condition 8 DROOP Adjust alternator droop to 5 at zero power factor Clockwise to increase increase droop 9 TRI...

Page 19: ... and not burned or pitted ENGINE GENERATOR SET Service the engine in accordance with the engine manufacturer s manual provided with your new equipment Routinely remove debris and dirt from around the inside generator enclosure Ensure that the air intakes are free from leaves and other debris at all times Clean and inspect battery terminals at least twice a year Also check the battery water level a...

Page 20: ...ust hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up engine generator set ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS 1 Insufficient fuel volume getting to the unit a Fuel line too small b Low fuel pressure 2 AC short circuit 3 Defective ECU on t...

Page 21: ...5 HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING DELTA AC D THREE PHASE DELTA 120 240V 5060 00 60708 165 T 1 TH W SINGLE PHASE 120 240 VOLTS SINGLE PHASE AC WIRING 4 LEAD SINGLE PHASE 120 240V ...

Page 22: ...7 D ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352 7 0 7 72 5 ...

Page 23: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 ƺ 1 855 17 66 7 50 1 2 803 56 6 2 1 29 25 2 7 5 255 6321 1 7 50 1 6 5 9 6 216 5 9 51 6 5 37 21 7 33 5 9 6 21 2 21752 5 6 5 83 7 7 5 567 3 27 8 6 5 36 8 21752 83 7 287387 6 5 1 335 7 7 6 0 1 1 21752 7 7 7 5 1 02 3 57 6 7 6 5 1 ...

Page 24: ...component of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE INCLUDING BUT NOT LIMITED TO WARRANTIES OF...

Reviews: