OPM-160/A

STARTING PROCEDURE

CONTROL LAYOUT

 

 

STOP/RESET - This button places the module into its Stop/
Reset mode. This will clear any alarm conditions for which 
the triggering criteria have been removed. The fuel supply 
de-energizes and the engine comes to a standstill. Should a 
remote start signal be present while operating in this mode, 
a remote start WILL NOT occur.
MANUAL MODE - This button places the module into its 
Manual Mode. Once in Manual Mode, the model responds 
to the Start button to start the generator and run it off load.

START - Pressing this button from STOP/RESET will start the 
engine and run the load. 

AUTO MODE - This button places the module into its Auto 
Mode. This mode allows the module to control the function 
of the generator automatically. 

ALARM/LAMP TEST - This button silences the audible alarm 
in the controller, deactivates the Audible Alarm output (if 
configured) and illuminates all of the LEDs on the module’s 
face as a lamp test function.

MENU NAVIGATION - Used for navigating the 
instrumentation, event log, and configuration screens. 

A small rocker switch is located on the 

underside of the engine control cabinet.

On gaseous models, the engine timing is 

controlled by the ECU on the engine and you 

need to tell it what fuel you want to operate 

on; LP or NG.  

On diesel models, this switch has been 

disconnected and will do nothing.

PROTECTIONS

When an alarm is present, the common alarm LED if 

configures will illuminate. The LCD display will show an icon 

to indicate the failure.

WARNINGS

Warnings are non-critical alarm conditions and do not 

affect the operation of the generator system, they serve to 

draw the operator’s attention to an undesirable condition. 

Warning alarms are self-resetting when the fault condition 

is removed. The icon will appear steady in the display.

SHUTDOWN

Shutdowns are critical alarm conditions that stop the 

engine and draw the operator’s attention to an undesirable 

condition. Shutdown alarms are latching. The fault must be 

removed and the STOP/RESET button pressed to reset the 

module. The icon will be flashing in the display.

PRE-START CHECK LIST

F-153 Pre-Start & Warranty Form was sent with your 

generator. This form must be filled out by an Authorized 

WINCO Service Center and submit it to our WINCO Service 

Department for your warranty to become valid. After 

completing the checklist, the engine-generator set is ready 

for initial start-up. 

WARNING: EQUIPMENT DAMAGE:

Before attempting  to start this unit, complete your pre-

start checklist and ensure the generator mainline circuit 

breaker is in the proper position prior to starting. Starting 

this unit without it properly connected can cause serious 

personal injury or equipment damage.

 

DO NOT jump start these engine-generator sets. Starting 

these units on a low battery or jump starting them will 

cause damage to the engine control module. 

MANUAL MODE

1. Press and release the MANUAL MODE button. The small 

LED light next to it should come on. 

Note: There is no start delay in this mode of operation.

2. Press and release the green START ENGINE button. The 

DSE 7310 MKII will send two signals to the engine. The first 

signal wire #21 will engage the fuel solenoid, the second 

wire, #22, will engage the starter on the engine. At this 

point the DSE7310 will start the cranking cycle (10 seconds 

on and 10 seconds off).

Note: Wire #93 is energized to turn on the glow plugs for 

15 seconds first and then the starter and fuel solenoid are 

engaged.

If the engine fails to start during this cranking period, the 

starter motor is disengaged and goes into a rest mode after 

which a second attempt is made to start the engine. Should 

this sequence continue through 3 cranking cycles the start 

sequence will be stopped and the display will show ‘FAILED 

TO START”. 

3. During manual operation, the load will not normally be 

applied to the generator. But caution must be used, if the 

line power should fail or be turned off the transfer switch 

during manual operation the load may be applied to the 

generator.

With the engine running smoothly check the no load 

voltage and frequency on the digital display. The voltage 

should be 208/240/480/600 AC depending on which 

model you have and a frequency of 59.5 to 60.5 hertz (Hz). 

If you have the proper voltage at the generator the next 

step is to check the voltage at the generator terminals in 

the Automatic Transfer Switch. The voltage between the 

G1 and the G3 terminals should be the same as it was 

on the generator front panel. The voltage should also be 

checked between the hot terminals (G1 and G3) and the 

G-N to be certain of a balanced voltage output and a solid 

neutral connection. The voltage between G1 and G-N 

should be about 120 volts AC (277 on 480 units). The same 

Summary of Contents for PSS60F4 Series

Page 1: ...need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHAS...

Page 2: ...AL GAS NG FUEL PRESSURE NG LP FUEL CONVERSION INSTALLING THE BATTERY 11 SERVICING BATTERIES BATTERY CHARGING BATTERY CHARGER BLOCK HEATER GROUNDING MOUNTING THE ATS AC ELECTRICAL CONNECTIONS 13 DC ELE...

Page 3: ...CO generator You have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is imp...

Page 4: ...cause cancer birth defects or other reproductive harm and developmental issues For more information go to www P65Warning ca gov C Do not smoke or use open flame near the generator set or fuel tank D K...

Page 5: ...60 60 60 Engine Model Ford 6 2L Starting System 12 Volt Muffler Standard Fuel Consumption LP NG Full Load 8 2 Gal Hr 750 685 BTU Hr 760 Ft Hr 797 416 BTU Hr Generator Testing Resistance Note Review th...

Page 6: ...nt The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 sec...

Page 7: ...ceived is the correct model and review the specification pages in this manual to ensure that this unit meets your job requirements CAUTION EQUIPMENT DAMAGE These units are shipped with oil and a 50 50...

Page 8: ...rue for the single low pressure regulator it should also be a minimum of 10 feet from the unit If this is not done the demand regulator on the unit and the pressure regulator in the fuel line will int...

Page 9: ...Up to 25 ft pipe 25 100 ft 1 pipe Over 100 ft Use a two regulator system Allow an additional 3 feet for each standard elbow DO NOT use street ells restrictive LP TANK SIZING Tank size is based off of...

Page 10: ...the oil level in the crankcase If it is low refill to the full mark with the proper weight grade of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the...

Page 11: ...tery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it...

Page 12: ...ational Electric Code It is suggested that this circuit be fused to 20 Amps Low Charge Mode The illuminated blue power LED and red low charging LED This indicates the Low Charge mode is in process Whe...

Page 13: ...connected to the generator there can be absolutely no feedback from the generator to the power line or the power line to the generator When properly installed the normal A T S Control and safety syst...

Page 14: ...ice disconnect must be installed in front of the ATS panel as the ATS is not service entrance rated This will allow you to test the generator under load Should you ever have to work on the switch you...

Page 15: ...charger to DSE7310 MKII controller D Remote Display Panel Interface Terminals These interface terminals are pre wired to allow for the connection of a remote display This display allows for the remot...

Page 16: ...r WINCO Service Department for your warranty to become valid After completing the checklist the engine generator set is ready for initial start up WARNING EQUIPMENT DAMAGE Before attempting to start t...

Page 17: ...it is in the manual mode Pressing the STOP RESET button will stop the unit immediately Pressing the AUTO mode button will stop the unit but only after the cool down timers have timed out and there is...

Page 18: ...dampening effect 4 LINK POWER RESPONSE A B 550kW Fast B C 100 550kW Fast A C 100kW Fast B D 100kW Slow 5 UFRO Under Frequency Roll Off Clockwise decreases KNEE point 6 SWITCH Select alternator frequen...

Page 19: ...or preventative maintenance required as long as the generator is run bi weekly to keep it dry and in good working order COLD WEATHER OPERATION Extreme cold weather operation requires special considera...

Page 20: ...Governor is defective ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Defective spark plug 5 Defective engine ignition mo...

Page 21: ...8 165 HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WI...

Page 22: ...8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 1 1 51 66 8 211 725 5 9 6 216 5 9 51 6 5 37 21 7 33 3 1 3 57 6 0 3 6 7 1 335 7 7 1 1 51 66 366 25 7 7 7 5 1 02 3 57 096 7 6 5 1 217 16 35235 7 5 1 250...

Page 23: ...57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2...

Page 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: