5
OPM-160/A
SPECIFICATIONS
PSS60F4
LP Gas - Standby
Wattage
60,000
62,000
62,000
62,000
62,000
Volts
120/240 120/208 120/240 277/480
346/600
kvA
60.0
77.5
77.5
77.5
77.5
Phase
Single
Three
Three
Three
Three
Amps
250
215
186
93
75
CB Size
250
225
225
100
80
Hertz
60
60
60
60
60
Natural Gas - Standby
Wattage
60,000
62,000
62,000
62,000
62,000
Volts
120/240 120/208 120/240 277/480
346/600
kvA
60.0
77.5
77.5
77.5
77.5
Phase
Single
Three
Three
Three
Three
Amps
250
215
186
93
75
CB Size
250
225
225
100
80
Hertz
60
60
60
60
60
Engine
Model
Ford 6.2L
Starting System
12 Volt
Muffler
Standard
Fuel Consumption
LP
NG
Full Load
8.2 Gal/Hr - 750,685 BTU/Hr
760 Ft³/Hr - 797,416 BTU/Hr
Generator Testing Resistance
Note: Review the Stamford Newage nameplate on your
generator before selecting the correct information below.
Model
Stamford
UCI224F
Winding
Group
06
Resistances:
Rotor
0.83
Ohms
@22°C
Stator (L-L)
0.024 Ohms Per Ph @ 22°C
Exciter Rotor (L-L)
0.078 Ohms Per Ph @ 22°C
Exciter Stator (L-L)
20.0 Ohms @ 22°C
Voltage Regulator (L-l) AS440
Model
Stamford
UCI224F
Winding
Group
311
Resistances:
Rotor
0.83
Ohms
@22°C
Stator (L-L)
0.065 Ohms Per Ph @ 22°C
Exciter Rotor (L-L)
0.078 Ohms Per Ph @ 22°C
Exciter Stator (L-L)
20.0 Ohms @ 22°C
Voltage Regulator (L-L) AS440