background image

8

OPM-160/A

FUEL INSTALLATION

The fuel supply should be as close as possible to the 

engine. This will reduce the installation cost of fuel runs. 

The information in this manual is offered to assist you in 

providing the proper fuel for your engine. However, this 

information is only provided to inform you of the engine’s 

requirements and assist in making you aware of the 

decisions you must make. In no case should the instructions 

and information provided be interpreted to conflict with 

any local, state or national codes. If in doubt, always consult 

your local fire marshal, gas supplier or building inspector.

WARNING: FIRE HAZARD

All fuel runs should be installed by a licensed fuel supplier.

To connect the fuel line to the generator set you will 

connect your incoming fuel line to the .75 inch NPT fitting 

located on the left side of the engine-generator set. This 

fitting is shipped with a plastic plug installed to insure 

the fuel system stays clean. For all vapor fuel systems the 

delivery pressure of the fuel to the fuel solenoid on the unit 

must be four to six ounces psi (per square inch) or 7 to 11 

inches W.C. (water column). These fuel pressures are critical; 

failure to provide the proper pressure can cause many 

problems including failure to start, inability to produce full 

power, or damage to the equipment.

These generators have been tested with both natural gas 

and LP at the factory. Before starting the engine you must 

verify it is configured for the proper fuel. See additional 

information in the NG/LP conversion section. 

INSTALLING THE FUEL LINE

NOTICE: The engine generator sets are properly adjusted 

before they leave the factory. The electronic control panel 

will indicate if the LP mode is active

NATURAL GAS or LP VAPOR PIPE SIZE

Size of pipe normally required for generators operating on 

natural gas or LP vapor. Unit location will determine the 

size of fuel line that is required to supply the engine with a 

constant fuel pressure and volume.

LIQUID PROPANE VAPOR (LP)

Refer to the tables on the following pages for fuel line size 

and recommended tank size. For distances of 25 feet or 

over, a two regulator fuel system is recommended. This is 

accomplished by installing a primary regulator at the tank 

which will reduce the tank pressure down to 10 to 15 lbs. 

A low pressure regulator is installed to further reduce the 

fuel pressure to the required six (6) oz. operating pressure. 

This low pressure regulator must be at least 10 feet from 

the engine generator set; any closer installation will require 

a larger line be installed to provide a fuel reservoir. This is 

also true for the single low pressure regulator, it should 

also be a minimum of 10 feet from the unit. If this is not 

done, the demand regulator on the unit and the pressure 

regulator in the fuel line will interfere with each other. 

When the two (2) regulator system is used on LP, a fuel line 

INSTALLATION

This unit should be installed in a well ventilated area, 

ensuring the exhaust air cannot be recirculated back into 

the engine. 

WARNING

Before proceeding with the installation, be sure 

the engine control is in the “stop” position and the 

emergency stop depressed. Also, be sure the generator 

MLCB (main line circuit breaker) is in the “off” position and 

the unit starting battery is disconnected.

These engine generator sets are designed to be mounted 

on a pad where there is proper ventilation. The transfer 

switch is mounted next to your electrical entrance or 

distribution panel inside or outside the building. Consult 

a qualified, licensed electrician or contractor to install and 

wire the transfer switch. The installation must comply with 

all national, state and local codes. Before beginning the 

installation process check the rating of the generator set 

and its transfer switch rating. Be certain they can handle 

the intended load and are compatible with the entrance 

voltage, phase and current ratings. Plans for installation 

should be prepared with proper attention to mechanical 

and electrical engineering detail to assure a satisfactory 

system installation. The information in this manual is offered 

only as a guide to finalizing your installation plans.

ENGINE-GENERATOR SET MOUNTING

WARNING: PERSONAL INJURY

The enclosures on these units can become very hot 

adjacent to the exhaust areas. Special care must be taken 

when installing these units to insure that the risk of 

contact by people is minimized.

The unit’s main frame should be bolted to a pad that meets 

local code. Various materials, including concrete and 

composites, are acceptable as long as they are structurally 

sound supporting the weight of the unit and preventing 

movement during operation. The mounting holes on the 

base of this unit is 0.625” in diameter. The engine-generator 

is mounted on a sub-frame which is isolated with special 

shock mounts on the main frame. This allows the engine-

generator to vibrate without affecting the control panel on 

the main frame.

 

Do not install any shock mounts between the base frame 

and the pad. Engine vibration will be transmitted to the 

control panel causing erroneous start/stop cycles and 

premature control failure.

These units should be mounted a minimum of 24” from a 

structure. This will allow for ample room to maintain and 

work on the generator set.

Units must be installed in accordance with all local, state, 

and national codes. Consult your local agency for specific 

requirements.

 

Summary of Contents for PSS60F4 Series

Page 1: ...need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHAS...

Page 2: ...AL GAS NG FUEL PRESSURE NG LP FUEL CONVERSION INSTALLING THE BATTERY 11 SERVICING BATTERIES BATTERY CHARGING BATTERY CHARGER BLOCK HEATER GROUNDING MOUNTING THE ATS AC ELECTRICAL CONNECTIONS 13 DC ELE...

Page 3: ...CO generator You have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is imp...

Page 4: ...cause cancer birth defects or other reproductive harm and developmental issues For more information go to www P65Warning ca gov C Do not smoke or use open flame near the generator set or fuel tank D K...

Page 5: ...60 60 60 Engine Model Ford 6 2L Starting System 12 Volt Muffler Standard Fuel Consumption LP NG Full Load 8 2 Gal Hr 750 685 BTU Hr 760 Ft Hr 797 416 BTU Hr Generator Testing Resistance Note Review th...

Page 6: ...nt The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 sec...

Page 7: ...ceived is the correct model and review the specification pages in this manual to ensure that this unit meets your job requirements CAUTION EQUIPMENT DAMAGE These units are shipped with oil and a 50 50...

Page 8: ...rue for the single low pressure regulator it should also be a minimum of 10 feet from the unit If this is not done the demand regulator on the unit and the pressure regulator in the fuel line will int...

Page 9: ...Up to 25 ft pipe 25 100 ft 1 pipe Over 100 ft Use a two regulator system Allow an additional 3 feet for each standard elbow DO NOT use street ells restrictive LP TANK SIZING Tank size is based off of...

Page 10: ...the oil level in the crankcase If it is low refill to the full mark with the proper weight grade of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the...

Page 11: ...tery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it...

Page 12: ...ational Electric Code It is suggested that this circuit be fused to 20 Amps Low Charge Mode The illuminated blue power LED and red low charging LED This indicates the Low Charge mode is in process Whe...

Page 13: ...connected to the generator there can be absolutely no feedback from the generator to the power line or the power line to the generator When properly installed the normal A T S Control and safety syst...

Page 14: ...ice disconnect must be installed in front of the ATS panel as the ATS is not service entrance rated This will allow you to test the generator under load Should you ever have to work on the switch you...

Page 15: ...charger to DSE7310 MKII controller D Remote Display Panel Interface Terminals These interface terminals are pre wired to allow for the connection of a remote display This display allows for the remot...

Page 16: ...r WINCO Service Department for your warranty to become valid After completing the checklist the engine generator set is ready for initial start up WARNING EQUIPMENT DAMAGE Before attempting to start t...

Page 17: ...it is in the manual mode Pressing the STOP RESET button will stop the unit immediately Pressing the AUTO mode button will stop the unit but only after the cool down timers have timed out and there is...

Page 18: ...dampening effect 4 LINK POWER RESPONSE A B 550kW Fast B C 100 550kW Fast A C 100kW Fast B D 100kW Slow 5 UFRO Under Frequency Roll Off Clockwise decreases KNEE point 6 SWITCH Select alternator frequen...

Page 19: ...or preventative maintenance required as long as the generator is run bi weekly to keep it dry and in good working order COLD WEATHER OPERATION Extreme cold weather operation requires special considera...

Page 20: ...Governor is defective ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Defective spark plug 5 Defective engine ignition mo...

Page 21: ...8 165 HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WI...

Page 22: ...8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 1 1 51 66 8 211 725 5 9 6 216 5 9 51 6 5 37 21 7 33 3 1 3 57 6 0 3 6 7 1 335 7 7 1 1 51 66 366 25 7 7 7 5 1 02 3 57 096 7 6 5 1 217 16 35235 7 5 1 250...

Page 23: ...57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2...

Page 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: