background image

9

OPM-160/A

Feet*

Size of pipe

Up to 25 ft

1.25” pipe

Over 25 ft*

1.25” pipe

*Allow an additional 3 feet for each standard elbow. 

DO NOT use ‘street ells’ (restrictive).

WARNING: PERSONAL DANGER  

Do not use galvanized pipe in fuel line runs. The 

galvanized coating can become eroded and flake off, 

causing possible obstructions in the regulator or fuel 

valve. The results could range from inoperative engine to 

hazardous fuel leaks.

CAUTION

Be careful when sealing gas joints. Excessive sealing 

compound can be drawn into the solenoid, regulator or 

carburetor causing an engine malfunction.

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough. The most 

common cause for inoperative systems is an inadequate 

or incorrect fuel pressure. Performance of the engine is in 

direct relation to the correctness of the fuel system. Shown 

below is a diagram of a typical LP vapor fuel installation. 

Notice the following tables give two different units of 

measuring fuel pressure. The first and most accurate is 

the use of a simple water manometer. A manometer is 

calibrated in inches of water column . The second is with a 

pressure gauge calibrated in ounces per square inch. 

The following diagrams are for LP installation. Reference 

numbers 1 through 3 in the diagram above are system 

parts supplied by the customer. Reference number 4 is on 

the generator.

Single low pressure regulator (LP vapor only)

Ref#

1

3

4

Unit off

Line PSI

7-11 in
4-6 oz

7-11 in 
4-6 oz

Starting

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

No load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

Full load

Line PSI

7-11 in
4-6 oz

7-11 in
4-6 oz

size of 3/4 to 1 inch is generally adequate for distances up 

to 300 feet from the primary to the low pressure regulator. 

Consult your local fuel supplier for your exact requirements. 

The appropriate line size from the following table is then 

installed from the low pressure regulator to the generator 

set.

Feet*

Size of pipe

Up to 25 ft

¾” pipe

25 - 100 ft

1” pipe

Over 100 ft

Use a two regulator system

*Allow an additional 3 feet for each standard elbow. 

DO NOT use ‘street ells’ (restrictive).

 LP TANK SIZING

Tank size is based off of 75% load, tank level has more 

than 20% capacity, and tank is dedicated for the generator 

supply. 

Tank Temperature

Tank Size

32° F (0° C)

1000 Gallons

0° F (18° C)

2000 Gallons

-20° F (-29° C)

3000 Gallons

LIQUID WITHDRAWAL SYSTEMS

When installing a unit equipped with the LP liquid 

withdrawal, a primary regulator is not required on the 

supply tank. The supply line is connected to a liquid 

withdrawal valve on the supply tank and runs directly to 

the fuellock strainer mounted on the engine generator 

set. Normally a 3/8 to 1/2 inch copper line is acceptable 

for this type of fuel installation. You must be sure that the 

valve you have connected to on the supply tank is in fact a 

liquid supply valve and has a drop tube inside the tank that 

is pulling fuel from the bottom of the supply tank. Before 

starting the unit, you must confirm that you have a good 

liquid supply at the unit. Engine generator sets equipped for 

liquid withdrawal will not run properly when supplied with 

vapor fuel.

NATURAL GAS (NG)

The primary regulator (fuel meter) on the building should 

deliver the correct volume and pressure to the generator 

set. This regulator must be sized to deliver the required 

BTU’s to the generator set and all other appliances in the 

building. If the primary regulator (fuel meter) is a high 

pressure regulator, then a low pressure regulator must be 

installed to bring the pressure down to 4-6 oz. (7-11 inches 

water column) of pressure. This low pressure regulator must 

be at least 10 feet from the engine generator set; any closer 

installation will require a larger line be installed to provide 

a fuel reservoir. If this is not done, the demand regulator 

on the unit and the pressure regulator in the fuel line will 

interfere with each other. This regulator must be sized to 

accommodate the demand of the generator set and any 

other appliance connected to it. See the following table for 

the correct size of pipe to be installed.

Summary of Contents for PSS60F4 Series

Page 1: ...need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHAS...

Page 2: ...AL GAS NG FUEL PRESSURE NG LP FUEL CONVERSION INSTALLING THE BATTERY 11 SERVICING BATTERIES BATTERY CHARGING BATTERY CHARGER BLOCK HEATER GROUNDING MOUNTING THE ATS AC ELECTRICAL CONNECTIONS 13 DC ELE...

Page 3: ...CO generator You have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is imp...

Page 4: ...cause cancer birth defects or other reproductive harm and developmental issues For more information go to www P65Warning ca gov C Do not smoke or use open flame near the generator set or fuel tank D K...

Page 5: ...60 60 60 Engine Model Ford 6 2L Starting System 12 Volt Muffler Standard Fuel Consumption LP NG Full Load 8 2 Gal Hr 750 685 BTU Hr 760 Ft Hr 797 416 BTU Hr Generator Testing Resistance Note Review th...

Page 6: ...nt The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 sec...

Page 7: ...ceived is the correct model and review the specification pages in this manual to ensure that this unit meets your job requirements CAUTION EQUIPMENT DAMAGE These units are shipped with oil and a 50 50...

Page 8: ...rue for the single low pressure regulator it should also be a minimum of 10 feet from the unit If this is not done the demand regulator on the unit and the pressure regulator in the fuel line will int...

Page 9: ...Up to 25 ft pipe 25 100 ft 1 pipe Over 100 ft Use a two regulator system Allow an additional 3 feet for each standard elbow DO NOT use street ells restrictive LP TANK SIZING Tank size is based off of...

Page 10: ...the oil level in the crankcase If it is low refill to the full mark with the proper weight grade of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the...

Page 11: ...tery terminal is connected to the negative cable ground from the engine generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it...

Page 12: ...ational Electric Code It is suggested that this circuit be fused to 20 Amps Low Charge Mode The illuminated blue power LED and red low charging LED This indicates the Low Charge mode is in process Whe...

Page 13: ...connected to the generator there can be absolutely no feedback from the generator to the power line or the power line to the generator When properly installed the normal A T S Control and safety syst...

Page 14: ...ice disconnect must be installed in front of the ATS panel as the ATS is not service entrance rated This will allow you to test the generator under load Should you ever have to work on the switch you...

Page 15: ...charger to DSE7310 MKII controller D Remote Display Panel Interface Terminals These interface terminals are pre wired to allow for the connection of a remote display This display allows for the remot...

Page 16: ...r WINCO Service Department for your warranty to become valid After completing the checklist the engine generator set is ready for initial start up WARNING EQUIPMENT DAMAGE Before attempting to start t...

Page 17: ...it is in the manual mode Pressing the STOP RESET button will stop the unit immediately Pressing the AUTO mode button will stop the unit but only after the cool down timers have timed out and there is...

Page 18: ...dampening effect 4 LINK POWER RESPONSE A B 550kW Fast B C 100 550kW Fast A C 100kW Fast B D 100kW Slow 5 UFRO Under Frequency Roll Off Clockwise decreases KNEE point 6 SWITCH Select alternator frequen...

Page 19: ...or preventative maintenance required as long as the generator is run bi weekly to keep it dry and in good working order COLD WEATHER OPERATION Extreme cold weather operation requires special considera...

Page 20: ...Governor is defective ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Defective spark plug 5 Defective engine ignition mo...

Page 21: ...8 165 HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WI...

Page 22: ...8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 1 1 51 66 8 211 725 5 9 6 216 5 9 51 6 5 37 21 7 33 3 1 3 57 6 0 3 6 7 1 335 7 7 1 1 51 66 366 25 7 7 7 5 1 02 3 57 096 7 6 5 1 217 16 35235 7 5 1 250...

Page 23: ...57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2...

Page 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: