background image

6

REV B

OPM-101

ELECTRICAL TESTING

TESTING COILS FOR OPENS AND GROUNDS

1. Disconnect field leads from rectifier

2. Set multi-meter to read infinite resistance (very high ohms), repair or 

replace field if it is open. Typical resistance for these fields varies from 

12.8 to 14.1 ohms.

3. Leaving one meter lead connected to the field, connect the other 

meter lead to the field shell. If meter indicates continuity (any reading 

- should be infinite resistance), the field is grounded and should be 

repaired or replaced. To determine which of the fields is grounded, cut 

the connector between the two coils and retest to determine which coil 

has the low resistance path.

TESTING ARMATURE FOR OPENS AND GROUNDS

1. Remove all brushes

2. Ground fault test. Set multi-meter to read high resistance (mega-

ohms). Holding one meter lead against a clean spot on the armature 

shaft, touch the other lead to each of the slip rings (one at a time) while 

observing the meter. If the meter indicates continuity (any reading lower 

than one mega ohm), the armature is grounded. Dirt between the slip 

rings and on the insulator surface can cause grounding. If grounding 

was indicated, carefully clean all dirt off the slip rings and their 

insulators and then recheck it. Replace the armature if it is grounded 

and unrepairable.

3. Testing for opens. Set meter to read low resistance (Rx 1 ohms). 

Holding one meter lead on the surface of slip ring #1, touch the other 

lead to surface of slip ring #2 while observing the meter. Meter should 

indicate continuity (low resistance 0 less than one ohm is typical). If the 

meter indicates an open circuit (infinite resistance) part of the armature 

winding is open. This may be caused by a repairable defect in the 

connection at the slip ring, however, generally an open armature will 

have to be replaced.

TESTING RECTIFIERS

The field excitation is supplied through full wave bridge rectifier. This 

type of rectifier has four terminals: two AC and a DC positive (+) and 

DC negative (-). Nothing is connected to the DC negative (-) in this 

generator.

A rectifier may be tested in the following manner:

1. Disconnect all leads from rectifier.

2. Connect the red ohmmeter lead to the positive DC (+) terminal.

3. Connect the black lead to each of the AC terminals in turn. Either a 

high or low resistance reading will be obtained.

4. Reverse the meter lead, (black to the DC positive (+) and red to the 

AC terminals, each in turn. An opposite reading should be observed.

5. Check each terminal to the case. An open circuit (very high 

resistance) reading should be observed. If a battery powered test light 

is used, follow the same procedures and previously described. A good 

diode element will allow current to pass to the light in the test lamp 

when the leads are connected in the forward direction.

6. If the rectifier fails any of the afore mentioned tests, it should be 

considered defective and replaced.

thereafter. Remove brushes one at a time and check for length. Be 

sure that each move freely in the brush holder. Brushes should be 

replaced when worn down to 3/8”. Always replace brushes in complete 

sets, never singularly. When replacing brushes, be careful to connect 

the lead wire properly. Poor contact or “skipping” between brush 

and slip ring can cause oil and grit, flint, or other hard contaminant 

substances on the brushes, or by the brush not being properly shaped 

to fit the slip rings.

Remedy these defects by cleaning the rings and brushes and the fitting 

the brushes to the slip ring curvature. Place #00 sandpaper under the 

brushes with the abrasive side to the brushes, and work it back and 

forth until the brushes are the same shape as the slip rings.

SLIP RINGS

The continuous copper rings located at the end of armature are the 

power collector rings or ‘slip rings’. For proper generator output, the 

Surface of these slip rings must have a highly polished finish. Under 

sustained use, it is advisable to check and occasionally polish ring 

surfaces with a crocus cloth to maintain the finish under normal 

conditions. This should not be required more than once each thousand 

hours of operation.

Summary of Contents for UL2FS2MP-1

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS UL2FS2MP 1 2 BEARING GENERATOR MANUAL...

Page 2: ...l number as yours If you should ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ____________...

Page 3: ...shipped from the factory it is fully checked for performance The generator is loaded to its full capacity and the voltage current and frequency are carefully checked Rated output of generator is based...

Page 4: ...ult in deterioration of the insulation short circuits and grounds 2 The generator should be installed in a sheltered area If the unit must be left in the open it should always be protected with a weat...

Page 5: ...hen the load is applied and will reduce the wear and extend its life CAUTION EQUIPMENT DAMAGE Keep the generator load within the generator and receptacle nameplate ratings Overloading may cause damage...

Page 6: ...o AC and a DC positive and DC negative Nothing is connected to the DC negative in this generator A rectifier may be tested in the following manner 1 Disconnect all leads from rectifier 2 Connect the r...

Page 7: ...ith sensitive meter If very low i e 1 2 volt flash fields with a 12 VDC battery Output voltage too high Engine speed too high See engine manual Generator overheating 1 Generator overloaded 2 Armature...

Page 8: ...fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some sta...

Reviews: