background image

9

REV B

60706-232

WARNING: PERSONAL DANGER

DO NOT OPERATE THIS GENERATOR INDOORS,

 

The unit should 

be stored in a warm, dry location. During a power outage, move the 

unit outdoors to a flat, dry location such as a driveway or sidewalk. 

WIRING

Plug your tools such as drills, saws, blowers, sump pump, and 

other items to be powered directly into the generator receptacles. 

Before plugging in all the tools and cord sets, recheck the rating 

of the generator set. Be sure it can handle the intended load and 

is compatible with the voltage, phase, and current ratings. ‘Hard 

wiring’ this unit directly into a temporary construction site electrical 

system is 

NOT A SIMPLE DO-IT-YOURSELF JOB. 

For your safety, 

all wiring must be done by a qualified electrician and conform to the 

National Electric Code and comply with all state and local codes and 

regulations. Check with local authorities before proceeding.

WARNING: PERSONAL DANGER

A fully isolated, double pole double throw manual transfer switch must 

be installed any time a generator is being connected to an existing 

distribution system.

1. These engine-generator sets are designed for portable heavy duty 

commercial use. Receptacles are provided on the control panel to 

permit 120 and 240 Volt portable appliances and tools to be plugged 

directly into them. Please note that the 3-wire 240 Volt receptacle(s) 

on these units are designed to power only 240 Volt tools. There are 

two hot leads and a ground wire, but no neutral connection, in the 

3-wire 240Volt receptacle. A 4-wire receptacle (two hot, one ground, 

and one neutral) has been provided on the control panel for use in 

temporary power applications requiring 120/240 Volt power. Consult a 

licensed electrician for wiring the TemPower plug and connecting it as 

temporary service.

To connect these units directly to an un-powered, isolated construction 

site TemPower panel, have your electrician connect to the control 

panel  using a 120/240 Volt, 4-wire twist-lock plug (14-60P).

NOTE:

 Never attempt to use the 240 Volt 3-wire receptacle to wire 

into a building. This is a GFCI circuit and is designed for 240 Volt 

output only. It has no neutral connection. If you attempt to draw 120 

Volt from this receptacle, the GFCI breaker will trip.

2. If the generator set is connected to an existing distribution system, 

a fully isolated manual transfer switch must be installed. The transfer 

switch prevents damage to the generator and the other circuit 

components if main line power is restored while the generator is 

connected. Installing a transfer switch also permits the use of normal 

fusing.

3.Many homes and construction sites are wired for at least 60 to 

100 Amp entrance service, much greater than the capacity of this 

portable generator. When installing the generator at these sites, a 

secondary emergency distribution panel may have to be installed. 

The emergency distribution panel must be installed by a licensed 

electrician according to all applicable codes. The electrician will move 

the critical circuits to be powered during the outage to the emergency 

panel. Keep in mind only a limited amount of amperage is available 

from the generator set. Some circuit breakers may still have to be 

turned off to prevent an overload on the generator during the initial 

start up. See the nameplate on your generator for the amperage 

capabilities of your unit.

CAUTION: EQUIPMENT DAMAGE

Failure to properly limit and balance the load a[[lied to the generator 

will cause the generator to produce low voltage and may damage 

the engine generator set. It may also cause severe damage to the 

loads connected to the generator at that time. Improper loading of the 

generator set constitutes abuse and will not be covered by warranty.

ENGINE CARE

MAINTENANCE SCHEDULE

If major engine service or repair is required, contact an authorized

engine service center. The manufacturer of these engines has

established an excellent world-wide engine service organization.

Engine service is very likely available from a nearby authorized dealer

or distributor.

CHECKING THE OIL LEVEL

The oil level must always be checked before the engine is started. 

Refer to page 5 of this manual for instructions on checking the oil level. 

Take care to remove any dirt or debris from around the oil plug before 

removing. Be sure the oil level is maintained. 

11

3110-00

60706-239

ENGINE CARE

If major engine service or repair is required, contact 

an authorized engine service center.  The manufac-

turer of these engines has established an excellent 

world-wide engine service organization.  Engine ser-

vice is very likely available from a nearby authorized 

dealer or distributor.  Check the yellow pages of your 

local telephone directory under “Engines-Gasoline” 

for the closest engine repair center or ask the dealer 

from whom you purchased the power plant. 

1.

 Change the oil

 after the 

rst 5 hours of operation 

and yearly or 100 hours thereafter under normal op-

erating conditions.  Change engine oil every 50 hours 

of operation if the engine is operated under heavy 

load, or in high ambient temperatures.

a.  Start the engine and warm it up, stop the engine  

  and remove the spark plug wire to prevent it 

  from accidently being started.

b.  Remove oil drain plug at base of the engine 

  (Ref “B”) and drain the oil into an approved 

 container.

c.  Remove the oil 

lter (Ref “C”) and dispose of it

 properly.

d.  Before you install the new oil 

lter, lightly lubri- 

  cate the oil 

lter gasket with fresh clean oil.

e.  Install the oil 

lter by hand until the gasket 

  contacts the oil 

lter adapter, then tighten the oil  

lter 1/2 to 3/4 turns. 

f.  Replace oil drain plug.

g.  Remove oil 

ller plug and re

ll with new oil.

  Refer to the table on page 5 for the proper    

  grade of oil based on your operating  

 temperature. 

NOTE:  This engine requires 78 to 80 ounces of oil 

if it is completely drained.  Use caution when re

lling

the engine as some residual oil may have remained 

in the engine.  Always use the dipstick when 

lling

the engine with oil to prevent over

lling.

h. Replace 

ller plug.

I.  Start the engine and warm it up.

J.  After warming up the engine, recheck the oil   

  level and re

ll as necessary to bring it to the 

  proper level.  See page 5 for proper oil level.

2.

Checking the Oil Level

:  The oil level must al-

ways be checked before the engine is started.  Take 

care to remove any dirt or debris from around the 

oil

ll plug before removing.  Be sure the oil level is 

maintained.  Fill to the “

FULL

” mark on the dipstick.

3.

Dual Element Air Filter

:  Clean and/or replace 

foam pre-cleaner and air 

lter annually or every 100 

hours.  Service more often under dusty conditions.

WARNING:  EQUIPMENT DAMAGE

Never start or run the engine with the air 

lter re-

moved

a.  Loosen snaps (Ref “A”) and remove cover.   

  Ref “B”

Maintenance Chart

First 5 Hours

x

Change oil

Every 8 Hours or Daily

x

Check engine oil level

x

Clean area around muffler and controls

Every 100 Hours or Annually

x

Clean or change air filter

*

x

Clean pre-cleaner (if equipped)

*

x

Change engine oil and filter

x

Replace spark plug

x

Check muffler and spark arrester

Every 250 Hours or Annually

x

Check valve clearance. Adjust if necessary.

Every 400 Hours or Annually

x

Change air filter

x

Replace fuel filter

x

Clean air cooling system

*

x

Clean oil cooler fins

*

*

In dusty conditions or when airborne debris is present, clean more often.

A

B

F

E

D

G

C

B

CHANGING THE OIL

Refer to the Maintenance Schedule Chart for required oil change 

intervals.

 

Summary of Contents for WC10000VE

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS WC10000VE E G GENERATOR MANUAL...

Page 2: ...ou have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is important that yo...

Page 3: ...d know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved container and only in a well ventilated area F Follow local codes for closeness to combustib...

Page 4: ...this 9 600 watt rated output generator A B represent the 120 volt output legs of this generator Up to 4 800 watts at 120 volts 40 Amps can be drawn from the receptacles attached to either A or B outp...

Page 5: ...system The necessity of using the correct oil and keep ing the crankcase full cannot be overemphasized Engine failures resulting from inadequate or improper lubricant are considered abuse and not cove...

Page 6: ...an 5 to 10 Watts they will not turn the Conserv R off resulting in low voltage being supplied to them This low voltage can do permanent damage to these appliances BATTERY INSTALLATION This engine gene...

Page 7: ...TICE ENGINE START LOCKOUT This unit will not start if it is low on oil The lu bricating oil level must be at the full mark before the engine will start and run BASIC OPERATION MANUAL STARTING Refer to...

Page 8: ...odically to ensure continued proper operation of the generating plant and appliances If the generator is not equipped with a voltmeter it can be checked with a portable meter CONNECTING THE LOADS APPL...

Page 9: ...d by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in mind only a limited amount...

Page 10: ...dual oil may have remained in the engine Always use the dipstick when lling the engine with oil to prevent over lling h Replace ller plug I Start the engine and warm it up J After warming up the engin...

Page 11: ...ufflers equipped with spark arresters the spark arrester must be removed every 50 hours for cleaning and inspection Replace if damaged TROUBLESHOOTING Problem Possible Causes Won t start Low oil level...

Page 12: ...rticular purpose are limited to 24 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied...

Reviews: