background image

 

 

 

 
 

PLEASE READ ENTIRE INSTRUCTION BEFORE PROCEEDING. 

INSTALLATIONS MUST COMPLY WITH ALL LOCAL CODES. 

IMPORTANT:

 Save these Instructions for the Local Electrical Inspector's use. 

INSTALLER:

 Please leave these Installation Instructions with this unit for owner. 

OWNER:

 Please retain these Instructions for future reference 

 

 

IMPROTANT SAFETY INSTRUCTIONS

  

 

WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, 
HOODS SHOULD BR INSTALLED WITH VENTILATORS APPROVED FOR USE WITH THE HOOD. 
SEE TABLE   1 OF THIS INSTRUCTION FOR APPROVED VENTILATORS. 
 

WARNING - TO REDUCE THE 
RISK OF FIRE, ELECTRIC 
SHOCK, OR INJURY TO 
PERSONS, OBSERVE THE 
FOLLOWING: 

A. Installation work and Electrical 
Wiring Must be Be Done By Qualified 
Person(s) In Accordance With All 
Applicable Codes & Standards. 
Including Fire-Rated Construction. 

 To Reduce The Risk Of 

Fire, Use Only Metal Duct Work. 

B. Sufficient air is needed for proper 
combustion and exhausting of gases 
through the flue (chimney) of fuel 
burning equipment to prevent 
backdrafting. Follow the heating 
equipment manufactures guideline and 
safety standard such as those published 
by the National Fire Protection 
Association (NFPA) and the American 
Society for Heating, Refrigeration and 
Air Conditioning Engineers 

(ASHRAE), 

and the local code authorities. 

C. When cutting or drilling into wall or 
ceiling, do not damage electrical wiring 
and other hidden utilities. 
D. Before Servicing or Cleaning Unit, 
Switch Power off At Service Panel And 
Lock Service Disconnecting Means to 
Prevent Power From Being Switched On 
Accidentally. When The Service 
Disconnecting Means Cannot be Locked, 
securely Fasten A Prominent Warning 
Device, Such As A Tag, To The Service 
Panel 

 
CAUTION - TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR, BE SURE TO 
DUCT AIR OUTSIDE FOR DUCTED FANS   DO NOT VENT EXHAUST AIR INTO SPACE WITHIN 
WALLS OR CEILING OR INTO ATTICS, CRAWL SPACES OR GARAGES. 
 
 

Read this instruction completely before starting installation. Planning the complete installation before starting any work is 
highly recommended. This includes all aspects of the installation including hood location, ducting, electrical requirements, 
and adequacy of mounting surfaces. 
 

 
 
 
 
 
 
 
 

DUCTING:

 Use a minimum 8" round duct for VEN030I, VEN060I and VEN060E installations. Use a minimum 10" round 

duct for VEN120E, VEN100E, VEN140E and VEN060I-Dual installations. Use #10100 8" - round transition or #10287 10"-
round transition from hood to ducting. Other Transition options are available   See your Dealer for details. 
 
 
 
 
 

INSTALLATION INSTRUCTIONS

 

HOOD MODELS   WSL, WCL, & WER

 

 

TABLE - 1 
Use model VEN030I or VEN060I 
for internal ventilator. Use 
VEN060E, VEN120E, VEN100E 
or VEN140E for remote ventilator

 

This hood has been designed to be used with the ventilators shown in Table-1. 
Before cutting into cabinets, it is necessary to confirm that the correct ventilator 
is being used. Your dealer should have reviewed your needs prior to your 
purchase. Be sure you have the correct ventilation system. 
CAUTION: To Reduce The Risk Of Fire And Electrical Shock, Install This  
Rangehood Only With Blowers Manufactured By Wind Crest.

 

                By CNP INDUSTRIES, INC. 

P.O. Box 18645    Anaheim, Ca 92817   (877) 387-6721 

Summary of Contents for WCL

Page 1: ...ice Disconnecting Means to Prevent Power From Being Switched On Accidentally When The Service Disconnecting Means Cannot be Locked securely Fasten A Prominent Warning Device Such As A Tag To The Service Panel CAUTION TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR BE SURE TO DUCT AIR OUTSIDE FOR DUCTED FANS DO NOT VENT EXHAUST AIR INTO SPACE WITHIN WALLS OR CEILING OR INTO ATTICS CRAWL SPAC...

Page 2: ...tric appliances Not recommended for use over solid fuel fired appliances After installing the hood install the internal blower see FIG 1 unit by positioning the blower onto bracket A notched blower bracket will center blower Rotate into position against hood top and secure with 8 sheet metal screws via bracket B To ease assembly you should predrive and then remove the 8 screws before installing th...

Page 3: ...CK WALL 1 10 2 4 1 4 12 18 24 27 ALL HOODS 2 12 8 OR 10 DUCT TO DISCHARGE W ROOF OR WALL CAP TRANSITION 10100 OR 10287 FIG 4 THE 8 DISCHARGE WITH THE TRANSITION 10100 WILL BE ON THE CENTER LINE OF HOOD WIDTH AND ON CENTER LINE OF 12 DIMENSION OR 10 DISCHARGE WITH TRANSITION 10287 WER MODELS WSL WCL MODELS 30 36 REMOVE COVER PLATE 2 BOTTOM SURFACE FOR THE HOOD MOUNTING ADD FURRING STRIPS TO PROVIDE...

Page 4: ... 3 4 5 6 18 W 5 1 2 2 1 1 2 3 4 4 3 2 1 RIGHT HEAT LIGHT HEAT LIGHT LEFT LIGHT LEFT RIGHT LIGHT 12 B 1 18 R 22 18 BL 23 18 B 24 18 B 14 18 B 15 18 W 21 18 B 16 18 B 18 18 B 19 18 B 17 18 W 20 18 W 10 18 W 18 B 18 BL 18 R 18 W 25 18 B 12 18 W 13 18 G 11 18 BL 3 18 B 2 18 R 4 BLOWER MOTOR 18 W 26 HEAT LIGHT SWITCH LEFT SWITCH HEAT LIGHT RIGHT BOX RECEPTACLE RECEPTACLE PLUG POWER SUPPLY N G L1 WIRING...

Page 5: ...ly See FIG 5 Break the metal webs by placing a screwdriver at one corner of the plate and hitting screwdriver sharply with a hammer After breaking a second web the plate can be flexed to break other webs Wear eye protection when using tools Attach the transition See DUCTING pg 1 obtained separately from your local hardware or available through your dealer and install the hood as described previous...

Page 6: ...K WALL 4 3 WIRING ACCESS 18 R 22 18 BL 23 18 B 24 18 W 25 18 B 12 18 W 13 18 G 11 BOX RECEPTACLE RECEPTACLE PLUG POWER SUPPLY N G L 1 WIRING DUAL INTERNAL BLOWERS BLOWER MOTOR BLOWER MOTOR 1 1 2 2 3 3 4 4 2 4 3 1 2 4 3 1 WIRE HARNESS 10220 HOOD CONTROL PANEL SEE WIRING DIAGRAM FOR DETAILS RECEPTACLE BOX WIRING SHOWN IS FOR MODELS WITH HEAT LAMP FIG 7 2 4 1 5 5 5 12 8 3 7 5 A 7 3 8 3 7 8 7 3 8 3 4 ...

Reviews: