PLEASE READ ENTIRE INSTRUCTION BEFORE PROCEEDING.
INSTALLATIONS MUST COMPLY WITH ALL LOCAL CODES.
IMPORTANT:
Save these Instructions for the Local Electrical Inspector's use.
INSTALLER:
Please leave these Installation Instructions with this unit for owner.
OWNER:
Please retain these Instructions for future reference
IMPROTANT SAFETY INSTRUCTIONS
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS,
HOODS SHOULD BR INSTALLED WITH VENTILATORS APPROVED FOR USE WITH THE HOOD.
SEE TABLE 1 OF THIS INSTRUCTION FOR APPROVED VENTILATORS.
WARNING - TO REDUCE THE
RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO
PERSONS, OBSERVE THE
FOLLOWING:
A. Installation work and Electrical
Wiring Must be Be Done By Qualified
Person(s) In Accordance With All
Applicable Codes & Standards.
Including Fire-Rated Construction.
To Reduce The Risk Of
Fire, Use Only Metal Duct Work.
B. Sufficient air is needed for proper
combustion and exhausting of gases
through the flue (chimney) of fuel
burning equipment to prevent
backdrafting. Follow the heating
equipment manufactures guideline and
safety standard such as those published
by the National Fire Protection
Association (NFPA) and the American
Society for Heating, Refrigeration and
Air Conditioning Engineers
(ASHRAE),
and the local code authorities.
C. When cutting or drilling into wall or
ceiling, do not damage electrical wiring
and other hidden utilities.
D. Before Servicing or Cleaning Unit,
Switch Power off At Service Panel And
Lock Service Disconnecting Means to
Prevent Power From Being Switched On
Accidentally. When The Service
Disconnecting Means Cannot be Locked,
securely Fasten A Prominent Warning
Device, Such As A Tag, To The Service
Panel
CAUTION - TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR, BE SURE TO
DUCT AIR OUTSIDE FOR DUCTED FANS DO NOT VENT EXHAUST AIR INTO SPACE WITHIN
WALLS OR CEILING OR INTO ATTICS, CRAWL SPACES OR GARAGES.
Read this instruction completely before starting installation. Planning the complete installation before starting any work is
highly recommended. This includes all aspects of the installation including hood location, ducting, electrical requirements,
and adequacy of mounting surfaces.
DUCTING:
Use a minimum 8" round duct for VEN030I, VEN060I and VEN060E installations. Use a minimum 10" round
duct for VEN120E, VEN100E, VEN140E and VEN060I-Dual installations. Use #10100 8" - round transition or #10287 10"-
round transition from hood to ducting. Other Transition options are available See your Dealer for details.
INSTALLATION INSTRUCTIONS
HOOD MODELS WSL, WCL, & WER
TABLE - 1
Use model VEN030I or VEN060I
for internal ventilator. Use
VEN060E, VEN120E, VEN100E
or VEN140E for remote ventilator
This hood has been designed to be used with the ventilators shown in Table-1.
Before cutting into cabinets, it is necessary to confirm that the correct ventilator
is being used. Your dealer should have reviewed your needs prior to your
purchase. Be sure you have the correct ventilation system.
CAUTION: To Reduce The Risk Of Fire And Electrical Shock, Install This
Rangehood Only With Blowers Manufactured By Wind Crest.
By CNP INDUSTRIES, INC.
P.O. Box 18645 Anaheim, Ca 92817 (877) 387-6721