background image

 

 

 

 

 

PLEASE READ ENTIRE INSTRUCTION BEFORE PROCEEDING. 

INSTALLATION MUST COMPLY WITH ALL LOCAL CODES. 

IMPORTANT:

 Save these Instructions for the Local Electrical Inspector's use. 

INSTALLER:

 Please leave these Installation Instructions with this unit for owner. 

OWNER:

 Please retain these Instructions for future reference 

 

 

IMPROTANT SAFETY INSTRUCTIONS

  

 

WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, 
HOODS SHOULD BE INSTALLED WITH VENTILATORS APPROVED FOR USE WITH THE HOOD. 
SEE TABLE 

 1 OF THIS INSTRUCTION FOR APPROVED VENTILATORS. 

 

WARNING - TO REDUCE THE 
RISK OF FIRE, ELECTRIC 
SHOCK, OR INJURY TO 
PERSONS, OBSERVE THE 
FOLLOWING: 

A. Installation work and Electrical 
Wiring Must be Be Done By Qualified 
Person(s) In Accordance With All 
Applicable Codes & Standards, 
Including Fire-Rated Construction. 

“WARNING”

 To Reduce The Risk Of 

Fire, Use Only Metal Duct Work. 

 
B. Sufficient air is needed for proper 
combustion and exhausting of gases 
through the flue (chimney) of fuel 
burning equipment to prevent 
backdrafting. Follow the heating 
equipment manufactures guideline and 
safety standard such as those published 
by the National Fire Protection 
Association (NFPA) and the American 
Society for Heating, Refrigeration and 
Air Conditioning Engineers 

(ASHRAE), 

and the local code authorities. 

C. When cutting or drilling into wall or 
ceiling, do not damage electrical wiring 
and other hidden utilities. 
D. Before Servicing or Cleaning Unit, 
Switch Power off At Service Panel And 
Lock Service Disconnecting Means to 
Prevent Power From Being Switched On 
Accidentally. When The Service 
Disconnecting Means Cannot be Locked, 
Securely Fasten A Prominent Warning 
Device, Such As A Tag, To The Service 
Panel

CAUTION - TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR, BE SURE TO 
DUCT AIR OUTSIDE FOR DUCTED FANS 

 DO NOT VENT EXHAUST AIR INTO SPACE WITHIN 

WALLS OR CEILING OR INTO ATTICS, CRAWL SPACES OR GARAGES. 
 
 

Read this instruction completely before starting installation. Planning the complete installation before starting any work is 
highly recommended. This includes all aspects of the installation including hood location, ducting, electrical requirements, 
and adequacy of mounting surfaces. 
 

 
 
 
 
 
 
 
 

DUCTING:

 Use a minimum 8" round duct for VEN030I, VEN060I and VEN060E installations. Use a minimum 10" round 

duct for VEN120E, VEN100E, VEN150E and VEN060I-Dual installations. Use #10100 8" - round transition or #10287 10"-
round transition from hood to ducting. Other Transition are available 

 See your Dealer for details. 

 
 
 
 
 
 

INSTALLATION INSTRUCTIONS

 

HOOD MODELS 

 WPN

 

 

TABLE - 1 
Use model VEN030I or VEN060I 
for internal ventilator. Use 
VEN060E, VEN120E, VEN100E 
or VEN150E for remote ventilator

 

This hood has been designed to be used with the ventilators shown in Table-1. 
Before cutting into cabinets, it is necessary to confirm that the correct ventilator 
is being used. Your dealer should have reviewed your needs prior to your 
purchase. Be sure you have the correct ventilation system. CAUTION: To 
Reduce The Risk Of Fire And Electrical Shock, Install This RangeHood Only 
With Blowers Manufactured By Wind Crest.

 

          By CNP INDUSTRIES, INC. 

P.O. Box 18645    Anaheim, Ca 92817   (877) 387-6721 

Summary of Contents for WPN

Page 1: ...d Lock Service Disconnecting Means to Prevent Power From Being Switched On Accidentally When The Service Disconnecting Means Cannot be Locked Securely Fasten A Prominent Warning Device Such As A Tag To The Service Panel CAUTION TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR BE SURE TO DUCT AIR OUTSIDE FOR DUCTED FANS DO NOT VENT EXHAUST AIR INTO SPACE WITHIN WALLS OR CEILING OR INTO ATTICS...

Page 2: ...rigidize mounting Connect 120 volts 15 amp 60 Hz power supply through the conduit hole in the top of hood connecting to pigtail in hood junction box white to white black to black and connect green ground wire to power supply ground wire per local codes The VEN100E 150E ventilator will require revision of some wiring in the hood receptacle box and possible modification of air discharge opening See ...

Page 3: ...OF WALL CAP TRANSITION 10100 15 FIG 3 THE 8 DISCHARGE WITH THE TRANSITION 10100 WILL BE ON THE CENTER LINE OF HOOD WIDTH AND ON CENTER LINE OF 12 DIMENSION VERTICAL DISCHARGE FIG 4 14 4 1 8 1 7 5 2 1 4 10 2 1 10 C L HOOD A CUT HOLE IN DRYWALL TO ACCEPT TRANSITION 10100 HORIZONTAL DISCHARGE A CENTER OF ROUND DUCT USING 10100 TRANSITION SECURE TRANSITION TO HOOD USING TWO 6 X 3 8 SHEET METAL SCREWS ...

Page 4: ...over which can be used as an alternate installation method to enclose the ventilation duct The hood can also be mounted under a cabinet HOOD UNDER CABINET INSTALLATION INSTALLATION HOOD WITH DUCT COVER Two typical installation options shown above When used the duct cover is designed to accommodate typical ceiling heights of 8 ft to 10 ft USING DUCT COVER SECTION 1 2 ONLY SECTION 2 ONLY USING DUCT ...

Page 5: ...be used to this gap at the ceiling interface SPACING TO BE 1 8 LARGER THAN DUCT COVER BEING USED 2 When using the duct cover and hood locate hood centerline on wall and mount the Duct Cover Bracket to ceiling centered on the hood centerline use 8 x 1 1 2 screws to mount bracket Mount the bracket to the ceiling with edge A against the hood mounting wall Wood framing should be located behind wallboa...

Page 6: ...ing of hood top to ceiling DESIRED DUCT COVER HEIGHT SCREW BOTH SIDES WITH 8 X 3 8 SCREWS 15 SECTION 19 SECTION 15 SECTION FLANGE 19 SECTION FLANGE 5 Predrive 8x1 2 screws into bottom flange of duct cover Remove screws and aside for use when mounting duct cover to hood 6 Install the duct cover onto the hood flanges facing down and spread the sides of the Duct Cover slightly and position the cover ...

Page 7: ...4 5 6 18 W 5 1 2 2 1 1 2 3 4 4 3 2 1 RIGHT HEAT LIGHT HEAT LIGHT LEFT LIGHT LEFT RIGHT LIGHT 12 B 1 18 R 22 18 BL 23 18 B 24 18 B 14 18 B 15 18 W 21 18 B 16 18 B 18 18 B 19 18 B 17 18 W 20 18 W 10 18 W 18 B 18 BL 18 R 18 W 25 18 B 12 18 W 13 18 G 11 18 BL 3 18 B 2 18 R 4 BLOWER MOTOR 18 W 26 HEAT LIGHT SWITCH LEFT SWITCH HEAT LIGHT RIGHT BOX RECEPTACLE RECEPTACLE PLUG POWER SUPPLY N G L1 WIRING DI...

Reviews: