All dimensions in mm:
Minimum room height: 1850 mm
Minimum clearances between exhaust pipe (connection piece to flue) and combustible components
400
1
mm
for an uninsulated exhaust pipe
100
1
mm
for an insulated exhaust pipe (min. insulation thickness of 2 cm)
50
2
mm
for approved, double-walled system flues
1
DIN V 18 160-1
2
in accordance with approval/identification of system flue
2.4.4 Minimum service clearances for fire protection, cleaning and
maintenance
The following minimum service clearances from flammable materials and for connections, cleaning and mainte-
nance must be complied with.
Attention!
Follow the installation guidelines for boiler rooms! The configuration of the exhaust line must com-
ply with technical fire protection requirements in accordance with the applicable regulations, stan-
dards and guidelines.
1075
min. 30
min. 30
710 (BW 102/152)
780 (BW 212/262)
min. 550
Fig. 20 BioWIN 2 Exklusiv/Premium/Exklusiv-S/Klassik –
view from above
1422
min. 30
min. 50
710
(BW 102/152)
780
(BW 212/262)
min. 650
Minimum clearances when flue connection at the top
Fig. 21 BioWIN 2 Exklusiv-SL/Klassik-L – view from above
Flue connection top