background image

Enterprise Gateway 

Doc No. A3930_UM Rev 2 

 

3.5

 

Gateway Mounting  

Care must be taken when choosing the location for the Spotlight Gateway.  A few 
considerations must be taken into account: 

a.

 

Location is within unobstructed line-of-sight of Gateway, ideally less than 50 

feet from the furthest Controller.  Communications over greater distances may 

require that directional WiFi antennas be fitted to the more distant Controllers, 

or that additional Gateways be installed. 

b.

 

Do not position the Gateway so that it is difficult to operate the disconnecting 

device. 

c.

 

Mount the Gateway such that the router indicators are easily visible through 

the windowed enclosure.   

d.

 

In order to provide reliable uptime, the Gateway power supply must be 

separate from all Controller power supplies. 

e.

 

Location should have a strong cell phone signal.     

The Spotlight Gateway is intended to be mounted 
on the exterior of any sheet metal enclosure or 
flat wall surface.   

Prior to mounting, some assembly is required.  To prevent damage during 
shipment, the router is packaged separately within the Gateway enclosure.  Mount 
the router onto the DIN rail and reconnect internal power cable and Ethernet cable 
as shown in Figure 2-1. 

The Gateway can be structurally mounted in two different ways.  The first way 
(Option # 1, Figure 3-2) uses two slotted aluminum mounting bars that accept  
#10-32 screws.  Windrock recommends using this mounting method.  Attach the 
mounting bars to the enclosure using the flathead screws included with the plastic 
mounting feet (Option # 2, Figure 3-3).     

Once done, the enclosure should be mounted using the 
fastener stack shown in Figure 3-4.  These fasteners are 
included with a standard system: 

 

 

Item 1, 1/4-20 X 1” screw 

 

Item 2, 1/4" flat washer 

 

Item 3, 1/4" split lock washer 

 

Item 4, 1/4-20 hex nut 

Depending on site conditions, longer screws may be needed to complete installation.  Mount the 
Gateway such that the router indicators are easily visible through the windowed enclosure.   

Gateway Mounting Option #2 can also be used to secure the Gateway Enclosure.  The OEM 
polycarbonate enclosure includes a plastic mounting foot kit.  If this option is better suited for the installation, install each of 
the four feet to the enclosure using the included flat head screws.  #10 screws (not included) must then be used to fasten the 
enclosure to a structure. 

Mounting hole dimensions are shown in Figure 3-2 and Figure 3-3 as well as the Spotlight Datasheet.    

3.6

 

Power Requirements 

The Enterprise Gateway is designed to be powered from an approved SELV LPS 10VDC – 60VDC power source.  Locations that 
do not have 10VDC – 60VDC available will require the addition of 10VDC – 60VDC power supplies rated for the installed 
location.  Refer to the Spotlight Datasheet for further details. 

Figure 3-2, Gateway Option #1 Mounting  

Figure 3-4, Option # 1 Mounting Fasteners 

Figure 3-3, Gateway Option #2 Mounting 

Summary of Contents for Enterprise A3930

Page 1: ...User Manual Enterprise Gateway...

Page 2: ...r use of this material Information in this document is subject to change without notice and does not represent a commitment on the part of Windrock Incorporated Any software described in this document...

Page 3: ...6 2 Gateway Control Drawing 12 IMPORTANT POWER REQUIREMENTS If voltage and power requirements are not met system integrity will be compromised Review power requirements and warnings as laid forth in t...

Page 4: ...with the possibility to use an Ethernet based local network connection instead Other models are restricted to an Ethernet connection and do have have cellular service configured at all 4G LTE Antenna...

Page 5: ...ce Contact your sales representative or Windrock directly AVERTISSEMENT Si A3930 ne fonctionne pas correctement puis doit tre renvoy Windrock des r parations Contactez votre repr sentant commercial ou...

Page 6: ...ce Contacter votre vendeur Windrock ou Windrock service client le pour toute question concernant l installation 3 2 Hazardous Locations THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2 GROUPS...

Page 7: ...by customer 6 Customer must provide supply voltage at desired mounting location For details see Section 3 6 and the Spotlight Datasheet Ensure power is de energized 7 Install disconnecting device clea...

Page 8: ...ing bars that accept 10 32 screws Windrock recommends using this mounting method Attach the mounting bars to the enclosure using the flathead screws included with the plastic mounting feet Option 2 Fi...

Page 9: ...and Cleaning The Windrock Spotlight contains no user serviceable parts and requires no routine maintenance Repair and support are provided by Windrock Inc only Firmware and software updates are availa...

Page 10: ......

Page 11: ......

Reviews: