11.2
List of usual values and safeguard settings - general
For each system of the engine the tables in the chapter that follows give the values for usual
operation and the trigger values for safeguard settings.
11.2.1
Tables - identification
The tables give the data that follow:
•
Description
This list gives the description of the object or of the system.
•
Medium / physical value / location
This list gives the data that follow:
○
Medium that is monitored
○
Physical parameter and unit
○
Location of the measurement
•
Usual operation (value or range)
This list gives the setpoint or the approximate range for usual operation. During operation
the current values can have small differences to the given values.
•
Signal number
This list gives the signal number as follows (refer also to
):
○
First two letters (XX) - Function code
○
Four digit number of the signal (for example 10NN)
•
First two numbers - Function group
•
Second two numbers - Running number
○
-nn - If more than one signal of the same type is applicable (for example TE2501-nnA
is TE2501A, TE2502A, TE2503A)
○
Last letter - Applied system
•
Function
This list gives one of the functions that follow:
○
ALM - Alarm
○
GTrip - Gas Trip (the ECS changes to diesel mode)
○
SLD - Slowdown
○
SHD - Shutdown
•
Level
This list gives one of the levels that follow:
○
D - Deviation
○
H - High
○
L - Low
X72-B
AA00-0000-00AAA-030K-A
Operation Manual
List of usual values and safeguard settings - general
Winterthur Gas & Diesel Ltd.
- 484 -
Issue 003 2021-12