2.3
Simulate oil mist to activate an alarm in the safety system.
3
For a DF engine: Do a calibration and a function check of the gas detectors, refer to the
related documentation of the manufacturer.
4
Do a check of the auxiliary blowers as follows:
4.1
Set to ON the main bearing oil supply.
4.2
If applicable, set to ON the turbocharger oil supply.
4.3
Do a check of the applicable lubricating oil pressure, refer to
values and safeguard settings - general
4.4
Set to ON the electrical power supply for each auxiliary blower.
4.5
On the LDU-20 MAIN page, select the button CTRL. TR. to get control at the local
control panel.
4.6
Start the auxiliary blowers.
4.6.1
Make sure that the auxiliary blower 1 starts immediately.
4.6.2
Make sure that the auxiliary blower 2 starts after an interval of between 3
seconds to 6 seconds.
4.7
Make sure that the two auxiliary blowers turn in the correct direction.
4.8
and
again from the LDU-20 in the ECR.
4.9
Connect the pressure calibration hand-pump to the pressure transmitters
PT4043C and PT4044C.
4.10
Operate the pressure calibration hand-pump to simulate a scavenge air pressure
of 0 bar to 6.0 bar.
4.11
On the MCM-11 (PT4043C), disconnect the cable from X41 terminal 1.
4.12
On the IOM-10 (PT4044C) disconnect the cable from X13 terminal 2.
4.13
Connect an ampere meter between the connection and the related cable.
4.14
Make sure that the transmitter output (4 mA to 20 mA) is related to the simulated
pressure (0 bar to 6.0 bar). If necessary replace the applicable transmitter.
4.15
On the MCM-11 (PT4043C), connect the cable to X41 terminal 1.
4.16
On the IOM-10 (PT4044C), connect the cable to X13 terminal 2.
NOTE:
The ECS adjusts the auxiliary blower start/stop hysteresis (0.8 bar to 1.0
bar).
4.17
Disconnect the pressure calibration hand-pump.
4.18
Stop the auxiliary blowers.
5
Do a check of the auxiliary blowers from the LDU-20 in the engine control room as follows:
5.1
On the MCM-11, disconnect terminal X33.
5.2
Start the auxiliary blowers.
5.3
Make sure that the command and feedback of auxiliary blowers continue to
operate.
NOTE:
If the auxiliary blowers do not operate, do a check of the wiring to the
starter box.
5.4
Stop the auxiliary blowers.
5.5
On the MCM-11, connect terminal X33.
5.6
On the IOM-10, disconnect terminal X11.
5.7
Start the auxiliary blowers. Command and feedback of auxiliary blowers must
continue to operate.
5.8
If the auxiliary blowers do not operate, do a check of the wiring to the starter box.
5.9
Stop the auxiliary blowers.
5.10
On the IOM-10, connect terminal X11.
X52
AA00-0000-00AAA-340A-A
Operation Manual
Do regular safety checks
Winterthur Gas & Diesel Ltd.
- 298 -
Issue 002 2018-11