5.11
again from the from the local LDU-20.
6
Do a check of the turning gear interlocks as follows:
6.1
Make sure that the turning gear is engaged.
6.2
Make sure that the pressure transmitter PT5017C and the switch ZS5016C do not
operate.
NOTE:
The pressure transmitter PT5017C operates at 2.0 bar.
6.3
Make sure that the indication Turning Gear Engaged shows on each LDU-20 (at
the control room console and local maneuvering stand).
6.4
Make sure that the engine is ready for operation as follows:
6.4.1
Make sure that the starting air shut-off valve 30-4325_E0_1 is in the
position CLOSED.
6.4.2
Make sure that there is no air in the starting air supply pipe.
6.5
On the LDU-20, select the button CTRL. TR. to get control.
6.6
Select the button START AHD.
6.7
Make sure that the indication Turning Gear Engaged is shown on each LDU-20.
6.8
Make sure that no start command is released.
6.9
again from the locations that follow:
•
LDU-20 on the ECR manual control panel
•
Remote control.
6.10
Disengage the turning gear.
NOTE:
On each LDU-20, the indication changes to Turning Gear Disengaged.
The start command is canceled in the remote control.
7
If there is a malfunction, find the cause and repair the fault, before you start the engine.
CLOSE UP
•
None
X52
AA00-0000-00AAA-340A-A
Operation Manual
Do regular safety checks
Winterthur Gas & Diesel Ltd.
- 299 -
Issue 002 2018-11