3 Technical specifications
3.1 Performance
Technical specification
Unit
Type DXC v4.1
DXC60
DXC80
DXC100
Net nominal heat input (max.)
kW
65.5
83.0
108
Net nominal heat input (min.)
kW
44.0
53.5
73.5
Heat output (max.)
kW
59.9
75.9
99.1
Heat output (min.)
kW
39.4
47.9
65.8
Efficiency at max. power
%
91.5
91.5
91.8
Efficiency at min. power
%
89.5
89.5
89.5
Air output (max.)
m
3
/h
6000
8000
10,000
Throw horizontal (max.)
m
40
45
50
Gas connection
G”
3/4"
3/4"
3/4"
Electrical connection (50 Hz)
V
230
230
230
Electrical power consumption
kW
0.8
0.9
1.4
Stand-by electrical power
consumption
kW
0.004
0.004
0.004
Electrical current (max.)
A
3.5
3.9
6.1
Protection class
-
IPX4D
NOx emission (GCV)
mg/kWh
139
126
135
NOx class
-
3
3
3
Flue gas amount (max.)
kg/h
122
150
199
Chimney flue pressure (max.)
Pa
25
40
60
Pressure switch point
Pa
180
160
180
Thermostat connection
-
2-wire low voltage communication bus or ON/OFF
Flue length (max.)
m
9
9
9
Weight
kg
140
150
175