14
1 2 3 4 5 6 7 8
ON
1
0
1 2 3 4 5 6 7 8
ON
1
0
S1
J14
1 2 3 4 5 6 7 8
ON
1
0
Figure 12 - Positions of the S1 and J14 switches for the
first three air heaters in a system
NOTICE
If the J14 switch of more than one air heater is
set to the same number, the system will not work.
NOTICE
The air heater must be switched off when setting
the switches. Otherwise the settings will have no effect.
4.5.4 ON/OFF thermostat installation
To connect the air heater to an ON/OFF room thermostat,
do the following:
• Connect the two thermostat wires to terminal 6 and
7 (see figure 13 or the electrical wiring diagram in
§11). This is a 24 V connection for the thermostat
signal.
Figure 13 - ON/OFF thermostat connection
NOTICE
Never combine these connections with the
terminals 6 and 7 of other air heaters.
NOTICE
Always use separate relays for each air heater.
NOTICE
Do not connect an external power source to
these terminals. These terminals need a dry contact.
5 Flue systems
To ensure safe and proper use, this air heater must be
connected to a flue system. This flue system must be
installed according to this manual as well as national and
local regulations. A flue system consists of a flue terminal,
piping and an optional condensate discharge system.
CAUTION!
Do not use flue terminals for condensing
appliances on non-condensing heaters. This can lead to
water inside the flue system.
NOTICE
Only use the prescribed flue material for the
roof terminal, wall terminal and for the piping between
the heater and the terminal. This is the only way the
installation will be approved.
NOTICE
Local regulations can require the flue terminal to
be placed at least 0,6 m above roof level.
NOTICE
Local regulations can require a minimum
distance between the flue terminal and air ventilation
openings on the building.
5.1 Flue terminals
The following flue terminals are compatible with this air
heater:
Model(s)
Vertical discharge
Flue terminal
Art. Nr.
TR10 until TR28
DDV 80/125
IA8202*
TR40 until TR50
DDV100/150
IA8101**
TR60 until TR150
DDV130/200
IA8305
* For h > 0,5m above the roof, use art.nr. IA8218
** For h > 0,5m above the roof, use art.nr. IA8107