Instructions condensing Air heaters type XR version XR-GB-4001-a
Page 13/27
On the smaller heaters like the TR10 and TR15 the forming of condensate is a risk.
When a heater often burns, and is placed in a normal heated room (temperature above 15
degrees) the condensate risk is low.
When a heater is placed in a room that only needs to be just above 5 degrees, it will only burn
for a very short time. In this short time the condensate that is formed will not evaporate. And the
condensate accumulates and will eventually result in pressure switch errors.
In general, when the flue pipe is long and is running through a cold space condensate can be
formed.
4.6 Installation Roof or Wall terminal
Algemeen
•
Check the components on possible damages.
•
Combine only with components from same materials and manufacturer.
•
Install after national regulation.
•
Outside can be cleaned with a wet towel or with some detergent.
Installation Roof terminal
1. Check the components on possible damages.
2. Taking the roofing into account, determine the type of weather collar synthetic file or universal
pitched roof flashing; for a flat roof an aluminium flat roof flashing.
3. Determine where the flue terminal will be positioned.
4. Make a hole for the flue terminal from the outside. Ensure that no
saw dust or dust gets into the appliance.
5. Fit the weather collar..
6. Carefully insert the flue terminal through from the
outside. Attention: do not tum the cap.
7.
Put the flue terminal into a vertical position using an
air level. (If desired, cover plates, to be supplied
separately,can be fitted)
8. Fix the supplied wall clamp round the flue terminal and fit it to the roof construction. Do not tighten
the clamp yet.
9. Fit the gasket and the twin-tube connection. Make sure that the gasket is not damaged. Ensure
that the flue tube and the air inlet tube are not exchanged; the flue tube is the pipe in the centre of
the flue terminal.
10.
Finally, secure the roof wall clamp and check that all steps have been carried out correctly.
Installing Wall terminal