Instructions condensing Air heaters type XR version XR-GB-4001-a
Page 5/27
3
Technical details:
Typ TR-4.5 (ERP2018)
TR10
TR15
TR20
TR24
TR28
TR40
TR50
Maximum nominal heat input (Nett)
kW
10,8
15,7
19,5
23,5
29,0
41,5
51,0
Minimum nominal heat input (Nett)
kW
9,0
14,0
14,5
20,0
24,0
35,0
40,0
Maximum heat output
kW
10,1
14,6
18,2
21,7
26,7
38,8
47,2
Minimum heat output
kW
8,3
11,6
13,5
18,4
22,0
32,5
36,6
Efficiency max. power
%
93.3
93,0
93,4
92,3
92,1
93,4
92,6
Efficiency min. power
%
92,2
92,8
92,8
92,2
91,8
92,9
91,5
Max. air output (+temp. increase)
m3/h
2000
2000
1850
3150
3200
4250
5800
Throw horizontal (max.)
m
12
12
12
16
16
22
26
Throw vertical (max. warm)
m
4
4
4
5
5
6
6
Gas connection
G”
1/2”
1/2”
1/2”
1/2”
1/2”
3/4”
3/4”
Electrical connection (50Hz)
V
230
230
230
230
230
230
230
Electrical power consumption max.
kW
0,200
0,200
0,200
0,190
0,200
0,300
0,425
Electrical power consumption min.
kW
0,200
0,200
0,200
0,190
0,200
0,300
0,425
Electrical power consumption
standby
kW
0,004
0,004
0,004
0,004
0,004
0,004
0,004
Electrical consumption Amps max.
A
0,9
0,9
0,9
0,8
0,9
1,3
1,8
Emission efficiency, (
η
s, flow)
%
95.9
93,7
92,5
94,3
93,1
92,4
93,6
Seas. Space heating efficiency
%
74,2
72.7
72.9
73,4
72,4
72,5
72.9
NOx emissie (GCV)
mg/kWh
93
99
93
97
94
95
96
NOx klasse
4
4
4
4
4
4
4
Flue gas amount max.
kg/h
20
30
40
50
55
80
100
Thermostat communication
bussystem (low voltage)
Argus
link
Pressure switch point
Pa
120
135
160
135
120
150
150
Sound level
dBA
42
42
42
45
45
48
50
Min. suspension height horz. throw
M (min.)
1,7
1,7
1,7
1,7
1,7
1,7
1,7
Min. suspension height vertical. throw
M (min.)
4,0
4,0
4,0
4,0
4,0
4,0
4,0
Maximum flue / air length
m
9
9
9
9
9
9
9
weight
kg
50
50
55
67
70
85
100
Natural gas G20 (I2H) ,
Nominal supply pressure G20 (H)
mbar.
20
Supply pressure (min-max) G20 (H)
mbar.
17-25
Gas category
II2H3P B/P
Class
B23, C13, C33
Max gas consumption G20 (H)
m3/h
1,1
1,7
2,1
2,5
3,1
4,4
5,4
d injectors
n x Ømm
2x 1,9
3x 1,9
4x 1,9
5x 1,9
6x 1,9
8x 1,9
10x 1,9
Burner pressure high G20 (H)
mbar
15,0
14,5
13,0
12,0
13,0
16,0
15,0
Burner pressure low G20 (H)
mbar
10,5
11,5
7,0
8,5
9,0
11,0
9,5
CO2 High (indication) G20 (H)
%
8,0
8,2
8,0
8,0
8,0
9,0
8,5
Propane, G31,
Nominal supply pressure G31 (P)
mbar.
30-50
Supply pressure (min-max) G31 (P)
mbar.
25-50
Gas category
II2H3P B/P
Class
B23, C13, C33
Max gas consumption G31 (P) kg/h
0,9
1,2
1,6
1,9
2,4
3,3
4,1
d injectors
n x Ømm
2x 1,4
3x 1,4
4x 1,4
5x 1,4
6x 1,3
8x 1,4
10x 1,4
Burner pressure high G31(P)
mbar
23,0
21,3
18,5
16,5
22,5
20,5
20,3
Burner pressure low G31(P)
mbar
16,0
17,0
10,0
12,3
15,5
14,5
12,4
CO2 High (indication G30 (B/P)
%
9,0
9,3
9
8,8
9,5
9,5
9,7
Butane, G30,
Nominal supply pressure G30 (B/P) mbar.
30-50
Supply pressure (min-max) G30 (B/P)
mbar.
25-50
Gas category
II2H3P B/P
Class
B23, C13, C33
Max gas consumption G30 (B/P)
kg/h
0,7
0,9
1,2
1,4
1,7
2,5
3,1
d injectors
n x Ømm
2x 1,4
3x 1,4
4x 1,4
5x 1,4
6x 1,3
8x 1,4
10x 1,4
Burner pressure high G30(B/P) mbar
18,0
16,5
14,0
13,0
17,5
16,0
16,0
Burner pressure low G30 (B/P)
mbar
13,0
13.0
8,0
9,5
12,0
11,5
9,3
CO2 High (indication G30 (B/P)
%
9,2
9,2
9,2
9,2
9,2
9,2
9,2