background image

 

Instructions premix Air heaters type XR10.. 60

   

 

 

 

 

Page 12/15 

It can also be that the DBC does not send a 230 Volt signal to the coils. In this case, try 

another DBC. 

b)  There are sparks and the gascontrol opens, but the mixture does not ignite. Check if the 

flame does ignite if the coloured air inlet ring on the pre-mixfan is closed partially between 

thumb and forefinger. There will be less air, so the mixture is richer and  ignite  easyer. If the 

flame  now ,becomes established, check the CO2-content when the heater is warm at high 

fire. Adjust it if necessary with the adjusting-screw on the gascontrol. 

Only

 do this with a 

good (calibrated) CO2-meter in the outlet of the heater. 

 

The burner ignites briefly, then the heater goes to lock-out 

This points to problems with the flame-ionisation. Check first for a sound earth connection in 

the heater, by pulling shortly on various earth wires. 

The ionisation current itself must be circa 2 microampère. This can be measured, provided 

the connections of the multimeter are jumpered during the sparking period in order to prevent 

the meter from damage. 

Most of the time, problems with the ionisation current, can be solved by replacing the DBC. 

 

Heater does start, but shows other problems. 

a) Heater stays on starting speed and does not modulate to a higher work speed : Check if the 

pre-mixfan speed does vary if you press the service button of the DFC. Press one time; the 

heater will go to  low-fire, press one more time; the heater will go to high fire. Pressing a 

further time will de-activate the servicemode. After 10 minutes of servicemode this function 

will switch off automatically. Check if the heater does function normally if the wires of the 

roomthermostat are jumpered (heater must start up and go to full load), and if it switches off 

when the wires are opened again. Try first another OpenTherm thermostat. If this does not 

work, the DFC must be replaced. It can also be the pre-mixfan itself that does not modulate 

inspite of a good input signal. The heat output of the heater will also be insufficient if there is 

too much resistance in the inlet- or outlet flue system. In this case the pre-mixfan will be on 

full speed, but because of the high resistance too little air is moved and therefore also too 

little gas. The pressure in the outlet flue for example, will normally never be above 30 Pascal.  

 

b)  Systemfan (M1) does not start or does not vary in speed; Check first the functioning of this 

fan by connecting it to 230 Volt. Check with a multimeter if the different lower tensions are 

secondary present on the transformator as well. The fuse could have failed. If the motor and 

transformer are OK, the cause of the probleem must be in the DFC, as the DFC dictates the 

different voltages from  the transformer to the fanmotor. In that case, replace the DFC. 

 

c)  Delta-T-regulation problems: For this regulation, potentiometer P2 on the DFC is used. This 

controls the desired difference in temperature between the room sensor (the OpenTherm) 

and the sensor in the heater (NTC). A smaller difference in temperature (potentiometer P2 

anti clock wise) will keep the systemfan running on higher speed for longer periods.  

 Check the functioning of the OpenTherm thermostat by putting it on heathdemand for a 

 little while. In case this functions well, then check the NTC (measure the Ohm resistance). 

 The problem may be the DFC. In this case, the DFC must be reprogrammed, or  replaced. 

 Resistance value NTC sensor at 20°C=  25 kOhm. 

 

 

#

  #

  5'&#  &# '

#

  #

  5'&#  &# '

#

  #

  5'&#  &# '

#

  #

  5'&#  &# '

The heater must be inspected and cleaned regularly (once  a year) by a qualified installer who 

understands this appliance.  

This is all the more important as the circumstances are heavier, especially in case of dust, 

humidity, high frequency of switching on/off etc. 

 

 

 

 

 

 

Summary of Contents for XR10

Page 1: ...UMENT MUST ABSOLUTELY BE READ BEFORE STARTING THE INSTALLATION INSTRUCT USER AND LEAVE THIS DOCUMENT WITH HEATER FOR REFERENCE Instruction manual version GB 82b date 12 05 2005 heaters only for natural gas G20 ...

Page 2: ...URE CONTROLLED DESTRATIFICATION FAN 8 6 4 HIGH LIMIT PROTECTION 8 6 5 DESCRIPTION SPARE PARTS 8 6 6 FUNCTIONS OF THE DFC 9 7 PUTTING INTO OPERATION AND ADJUSTMENT 9 8 1 GENERAL 9 8 2 START BY USING THE SERVICE BUTTON 10 8 3 START BY BYPASSING THERMOSTAT 10 8 4 START BY USING THE THERMOSTAT 10 8 5 TO SIMULATE A LOCK OUT CONDITION 10 8 ADJUSTING THE GAS CONTROL 10 9 PROBLEM SOLVING 11 9 1 GENERAL 11...

Page 3: ...on of the air heater must be in accordance with the relevant requirements of the Gas Safety regulations for example in GB The Institute of Gas Engineers IGE UP 1 and 2 building regulations and the IIE regulations also incorporating the gas safety installation and use regulations Other national and or local regulations may apply The competent installer must make sure the heater operates correctly a...

Page 4: ... 230 230 Thermostat Open Therm yes yes yes yes yes yes Power Consumption W 250 250 250 450 450 600 Gas connection G 1 2 1 2 1 2 3 4 3 4 3 4 Minimum suspension height horizontal throw m 1 7 1 7 1 7 2 7 2 7 2 7 Minimum suspension height vertical throw m 4 4 4 5 6 6 Weight kg 36 37 38 78 80 82 Min supply pressure G20 H mbar 20 20 20 20 20 20 Gas category Cat I2H Class Clas B23 C13 C33 Max gas consump...

Page 5: ...r 4 for further installation restrictions 6 2 Gas connection The gas supply line has to meet the national valid requirements and possibly the local requirements of the building inspector police or fire brigade In GB it must comply with Gas Engineers publication UP 1 and UP 2 together with BS 6891 A manual isolation valve in the supply line must be placed within reach of the heater and all gas line...

Page 6: ...n this manual 24V is available on the connection terminals for possible use with this fault indication This contact is closed in a lockout condition 6 3 5 Reset The heater can be reset in 3 ways On the TCW thermostat On the DFC printed circuit board within the heater push the lower red button On a remote reset button For the connection see the diagram towards the end of this manual 6 3 6 Fuses The...

Page 7: ...of level Do not connect a standard flue terminal to this heater nor a terminal for a condensing boiler Use only pipes and bends for overpressure with profiled sealing rings 6 1 General The unit can heat as well as ventilate By using the temperature sensor on the unit and the one in the room thermostat the temperature difference between the two in the room is monitored Should the difference become ...

Page 8: ...15 C maximum by turning Potentiometer 2 P2 fully clockwise See below 6 4 High limit protection The unit contains 2 temperature protections The NTC thermostat monitors the air temperature electronically Should the temperature become too high the burner will switch off When the unit has cooled down it will automatically restart Should the temperature increase to an unacceptable level the STB capilla...

Page 9: ...ter reference Use only a calibrated instrument The CO2 value may be adjusted if necessary only do this in case it turns out that the CO2 value is not correct Do not ever turn injudiciously the adjusting screws Adjustment of the gascontrol without a supporting flue gas analysis will invalidate the warranty Once the unit is installed according this manual the unit can be put into operation Make sure...

Page 10: ... room Thermostat if installed will now flash Check also the function of the reset button with gasvalve open again and observe if heater starts smoothly 0 0 0 0 1 1 1 1 In principle it is not necessary to adjust the gascontrol after putting the unit into operation In case it needs to be adjusted f e after fitting a new one this must be done only by a qualified person Only use calibrated instruments...

Page 11: ...sure the resistance of the NTC pull plug from DFC This must be approx 20 kilo Ohm at 25 C or 40 kOhm at 10 c Check that a 230V signal is being received at the DBC d Check that a230V signal is being received on the plug of the pre mix fan between the brown and the blue wire e It is possible that there is no PWM signal to the pre mix fan for the starting speed This can be checked on the 24V plug of ...

Page 12: ...d if it switches off when the wires are opened again Try first another OpenTherm thermostat If this does not work the DFC must be replaced It can also be the pre mixfan itself that does not modulate inspite of a good input signal The heat output of the heater will also be insufficient if there is too much resistance in the inlet or outlet flue system In this case the pre mixfan will be on full spe...

Page 13: ...correctly 10 3 Spare parts Description 10 20 30 40 50 60 Burner XR IX 3206 IX 3206 IX 3208 IX 3208 IX 3210 IX 3212 Ignition Ionisation electrode IX 3458 IX 3458 IX 3458 IX 3458 IX 3458 IX 3458 Premix fan MVL RG128 M2 IX 4500 IX 4500 IX 4500 IX 4500 IX 4500 IX 4500 Inspection glass IX 6812 IX 6812 IX 6812 IX 6812 IX 6812 IX 6812 Gas AirMixer SIT 391 AGM IX 4506 IX 4504 IX 4502 Gascontrol SIT SIGMA ...

Page 14: ...g to the diagram terminal 4 5 6 and 7 11 3 Installation with extra reset possibility Connect the heater to 230VaC Connect the thermostat can be OpenTherm or on off Reset is possible by mounting a pressbutton between terminals 6 and 7 230 Vac Open therm 24 Vdc L 230 Vac N neutral 20 C Room Thermostat 2 1 3 12 4 5 7 6 11 13 14 F3 N neutral L 230 Vac 2 1 3 5 4 6 7 230 Vac 20 C Room Thermostat Open th...

Page 15: ...EV1 2 Gas valve Transformer for Fanregulation Fuse TR1 F Pre mix fan Connections for installation purposes Limmit thermostat manual reset 3 Fan motor STB M1 M2 n F3 M1 1 white red braun braun black black blue black 12 13 grey T 14 blue 11 TR1 L 230V AC 1 N Neutral 2 X6 5 X 6 8 13 14 F3 X6 6 violet transp black black blue orange black yellow grey yellow red black blue green yellow Room thermostat O...

Reviews: