SmartPAC PRO User Manual
1143100
Chapter 2 – Installing SmartPAC PRO
73
Wiring Setup Mode Circuit
SmartPAC PRO Setup mode allows you to disable green sensors and parts/batch counters, using a
remote switch. Typically, the Setup mode circuit is enabled when Inch mode is selected on your
clutch/brake control. When you inch the press, SmartPAC PRO will not stop the press when a fault
condition is detected. The Setup mode terminal can be wired to an extra contact on the Inch position
of the Stroke Select keyswitch of your press control, or you can use an external switch to activate the
circuit. If you intend to use the Setup mode circuit, plan how you will run your wiring for this
connector now so you do not have to disconnect conduit or rerun wires through conduit later.
For Setup mode, you must provide contact closure when a non-Wintriss press control is in Inch mode.
Connect a wire from SmartPAC PRO terminal block TB5, terminal #252 (labelled IN/SU) to one side
of a normally open switch (see Table 2-11, and Figure 4 at the end of the manual). Connect the other
side of the switch to GND (TB5, terminal #247). Refer to your electrical prints or the manual for your
press control to plan your wiring.
Table 2-11. Aux I/O (TB5) Wiring
Pin #
Signal
245
+24 V
246
POSITION SENSOR
247
GND
248
ZERO
249
REMOTE RESET
250
GND
251
LOCKOUT
252
INCH/SETUP
253
OP STA 2
254
OP STA 1
Wiring a Remote Reset Switch (Optional)
Like the Setup mode terminal, the Remote Reset terminal can be wired to a normally open switch to
activate the circuit. Be sure to plan how you will run your wiring for this connector so that you do not
have to disconnect conduit or re-run wires through conduit later. Connect a wire from SmartPAC
PRO TB5, terminal #249 (labelled RST) to a normally open switch (see Table 2-11, and wiring
diagram Figure 4 at the end of the manual). Connect another wire from the switch to GND (TB5,
terminal #250). SmartPAC PRO is reset with a momentary connection to ground.
Wiring a Sensor-Disabled Output (Optional)
You can wire a Sensor-disabled Output such as a warning light to a customer-supplied solid-state
relay to warn personnel that the die protection capability, if installed, is disabled.
Connect the positive input wire from your user-supplied 12VDC solid-state relay to terminal #302
(Relay Pwr) on TB553 on the DiProPAC board. Connect the negative input wire from the relay to
terminal #306 (Aux 1) on TB553. You cannot use more than 8 mA for your relay.
Summary of Contents for SmartPAC PRO
Page 1: ......
Page 2: ......
Page 4: ......
Page 6: ......
Page 20: ......
Page 22: ......
Page 24: ......
Page 42: ...1143100 SmartPAC PRO User Manual 42 Chapter 1 Introduction to SmartPAC PRO ...
Page 142: ...1143100 SmartPAC PRO User Manual 142 Chapter 4 SmartPAC PRO Program Mode ...
Page 200: ...1143100 SmartPAC PRO User Manual 200 Chapter 6 Using DiProPAC Die Protection Optional ...
Page 222: ...1143100 SmartPAC PRO User Manual 222 Chapter 7 ProCamPAC Instructions ...
Page 254: ...1143100 SmartPAC PRO User Manual Appendix C SmartView Remote Viewing and E mail Setup 254 ...
Page 280: ...SmartPAC PRO User Manual 1143100 280 Appendix C Reporting Downtime and Scrap to SFC ...
Page 290: ...SmartPAC PRO User Manual 1143100 290 Index Y yellow fault 232 yellow sensor 169 ...
Page 292: ......
Page 294: ......
Page 296: ......
Page 298: ......
Page 300: ......
Page 301: ......
Page 302: ......
Page 303: ......
Page 304: ......
Page 305: ......
Page 306: ......
Page 307: ......
Page 308: ......
Page 309: ......
Page 310: ......
Page 311: ......
Page 312: ......
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ......
Page 317: ......
Page 318: ......