ACW-DINDxxx_UG_EN_V1.8
Bounce time parameter
All inputs are affected by an anti-rebound time that can be adjusted between 1 and 250 ms depending
on the type of dry contacts used.
Periodic frame parameter
The periodic frames make it possible to regularly go back up the state of the inputs / counters. This
frequency is set to 1 hour by default but can be set from 10 minutes to 45 days, 12 hours and 15 minutes.
Depending on the setting you have chosen, it is possible that several frames are sent. In this case and
only in the Sigfox version the minimum periodicity can be affected:
⚫
If two frames are to be sent, the minimum period is 20 minutes.
⚫
If three frames are to be sent, the minimum period is 30 minutes.
⚫
If four frames are to be sent, the minimum period is 40 minutes.
⚫
If five frames are to be sent, the minimum period is 50 minutes.
Keep alive frame parameters
A life frame can be emitted periodically. This frame will remount the supply voltage of the product.
The available periods are as follows
⚫
Disabled
⚫
Every hour
⚫
Every two hours
⚫
Every four hours
⚫
Every eight hours
⚫
Everyday
⚫
Every two days
⚫
Every three days
⚫
Every four days (by default)
⚫
Every week.
⚫
Every month (30 days)
Temperature parameter (offset)
If a temperature sensor is connected, it is possible to assign an offset value for calibration of the sensor.
By default, a value of 0 ° C is affected and the possible values are from -10 to +10 ° C in steps of 0.1 ° C.
Pairing method setup
In the LoRaWAN version it is possible to choose the method of pairing between OTAA (Over The Air
Activation) and ABP (Activation By Personalization).
Note: The class of operation LoRaWAN is by default and not configurable, class C. This remains
compatible with a network configured for class A.
Note: Class C requires a first uplink broadcast before being able to receive downlinks. When starting up,
it will take a minute to send downlinks.