8 Fieldgate Configuration
WirelessHART Fieldgate SWG70
46
Hauser
8.3
Wired Communication
8.3.1
Serial
The parameters contained in this leaf pertain to the set up of the serial interface offered by Fieldgate
SWG70.
1 Click on the
Wired Communication => Interfaces => Serial
to display the associated
parameter:
–
The significance of the parameters can be taken from the table below
2 Configure the serial interface for HART or MODBUS RTU as required
3 After configuration, set up the interface protocol parameters in the appropriate "Protocol" leaf,
see Chapters 8.3.3 and 8.3.4
–
Modbus serial allows access for one master
–
HART serial allows access for one primary master and one secondary master
Serial parameters
Parameter
Meaning
Example
Default
Terminal Resistor
Selection
Specifies whether hardware (DIP switch 6) or software termination
settings are to be used
DIP-Switch
Software
Terminal Resistor
Sets the termination of the wireless fieldgate when Terminal
Resistor Selection is set to Software
– When DIP-Switch is selected, displays the setting
Connected
Dis-
connected
Protocol Selection
Sets the protocol to be used over the serial port
HART
MODBUS
RTU