WirelessHART Fieldgate SWG70
9 Diagnostics
Hauser
59
HART parameters
Parameter
Parameter
Meaning
Extended Device Malfunction
Manager fault
Non-recoverable hardware fault: Fieldgate manager
Non-Volatile Memory Defect
Non-recoverable hardware fault: Non-voltatile memory
Volatile Memory Defect
Non-recoverable hardware fault: Voltatile memory
Ethernet communication fault
Non-recoverable hardware fault: Ethernet controller
Electronic defect
Non-recoverable hardware fault: Other case
RS-485 communication fault
Non-recoverable hardware fault: RS-485 controller
Gateway Operation in Progress Block transfer
Fieldgate transferring block
Delayed answer
Fieldgate awaiting answer from device (buffer)
Self test
Fieldgate is in self test mode, see Chapter 8.6.5
File update
Fieldgate writing to non-volatile memory file
Start-up phase
Fieldgate is starting up and building the network
Extended List changes
Instrument List Changed
Instrument list has changed since last refresh
Active Device List Changed
Device list has changed since last refresh
Cumulative Device Status
Primary Variable Out of Limits PV of a device in the network is out of limits
Non-Primary Variable Out of
Limits
SV, TV, QV of a device in the network is out of limits
Loop Current Saturated
Loop current of a a device in the network above 20 mA
Loop Current Fixed
Loop current of a a device in the network is fixed to
4 mA (multidrop mode)
More Status Available
Device in the network has more status available flagged
Cold Start
Device in the network has cold start flagged
Configuration Changed
Configuration of a device in the network has changed
Device Malfunction
Device in the network has malfunctioned
Cumulative Extended Device
Status
Maintenance required
The status "Maintenance required" has been set for a
device in the network
Device Variable Alert
The status "Device Variable Alert" has been set for a
device in the network
Critical Power Failure
The status "Critical Power Failure" has been set for a
device in the network
Device Operation in Progress
"Configuration Changed bit
reset" procedure
Fieldgate has reset the "Configuration Changes" bit of
one of the devices
"Sub-Device update" procedure Fieldgate is carrying out the identification of a device
connected to an adapter
"Device update" procedure
Fieldgate is carrying out the identification of an adapter
Summary of Contents for Fieldgate SWG70
Page 2: ......
Page 119: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 117 For your notes ...
Page 120: ...D Appendix ANATEL Approval WirelessHART Fieldgate SWG70 118 Endress Hauser For your notes ...
Page 121: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 119 For your notes ...
Page 123: ......
Page 124: ...www endress com worldwide ...