12 Measurement
WirelessHART Fieldgate SWG70
80
Hauser
12 Measurement
The Measurement table provides a comprehensive overview of all cached parameters and values of
all sub-devices.
• As the the list is stored in a non-volatile memory, the card and channel number assignment
will remain the same after a restart of the gateway or software
• The dynamic values of each sub-device (analogue value, PV, SV, TV, QV) are cached by the
gateway only if the sub-device publishes these values
• After a network restart, the instrument list needs time to rebuild. During this time, some
information is set to 0 or replaced by wildcard characters
• To remove a device from the list, use the Instrument List, see Chapter 10.1
Whenever a new wireless device joins the network, it is automatically inserted into the list. Wired
devices connected to a WirelessHART adapter are also inserted.
1 Click on the
Measurement
leaf to open the dialogue:
–
In FieldCare right click on the Fieldgate SWG70 node and select
Observe
–
The significance of the parameters is described in the table below
Parameter/Field
Meaning
Long Tag
Identifies Fieldgate within the plant network
– For devices less than HART 6.0 the Message field is used as the long tag
IO card
Identifier of Fieldgate card used by the device
Channel
Identifier of card channel used by the device
Device Type
Designation of connected device
Status
Communication status of the associated device
–
Connected
–
Flashing: Device connected, being identified
Continuous: Device connected but not identified
–
Communication failure
Dev. Status
Device status of the associated device
–
Good
–
Out of specification
–
Failure
The device status displayed in the Operating Modes list may differ from the actual device
status because the HART status bits may be interpreted differently.
Loop current
Current in mA (for HART Multidrop = 4 mA)
PV
Primary value of the device
SV
Secondary variable of the device
TV
Tertiary variable of the device
QV
Quaternary variable of the device
"+", "–"
Expands or contracts the tree view
Refresh
Updates the instrument list
Summary of Contents for Fieldgate SWG70
Page 2: ......
Page 119: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 117 For your notes ...
Page 120: ...D Appendix ANATEL Approval WirelessHART Fieldgate SWG70 118 Endress Hauser For your notes ...
Page 121: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 119 For your notes ...
Page 123: ......
Page 124: ...www endress com worldwide ...