background image

A3091000/A3091250

ProMIX™ 101 Radiant

Heating Reset Control

2

Basic Operation

On installation, five design parameters must be
set:

O

utdoor 

A

ir 

L

ow - the anticipated coldest

outdoor design temperature.  The same
figure used to calculate heat loss and
equipment loads.

O

utdoor 

A

ir 

H

igh - The average room

setpoint temperature, for example 65

°

F.

This value will also serve as the warm
weather shutdown.  Once outdoor tem-
perature reaches the room setpoint
temperature, the heat loss is zero and the
control is deactivated.

P

rimary 

L

oop 

L

ow (minimum boiler return

water temperature) - Some types of
boilers require a minimum return water
temperature to protect the boiler from
condensing such as cast iron boilers.  If
no boiler return protection is required, this
dial should be turned counter-clockwise
to the "Cold Start" setting.

S

econdary 

L

oop 

H

igh (maximum radiant

loop temperature) - the hottest water
temperature required to satisfy the radiant
panel at design conditions or coldest
outdoor temperature.  Refer to 

OAL

S

econdary 

L

oop 

L

ow (minimum radiant

loop temperature) - the minimum water
temperature required to meet the de-
mands in the beginning and end of the
heating season.

The design temperatures are read from the
potentiometer dial settings when the system is
first started up, and may be displayed and
changed at anytime.

Three sensors are continuously monitored and
displayed:  Outdoor Air (

OA

), Primary Loop

(

PL

), and Secondary Loop (

SL

).  Also dis-

played is the optimum Secondary Loop Setpoint
(

SLS

), calculated based on the design settings

and the current OA temperature.  (The colder it
is outside, the warmer the desired water tem-
perature.)

The 

SL

 sensor provides feedback for the

control loop.  To provide the proper temperature
in the radiant loop, the control positions the
valve using a proportional-integral algorithm.  If
the 

PL

 sensor indicates a possibility of the

return temperature falling below the selected
minimum, the opening of the valve is reversed
to prevent condensation of the flue gases, and
the boiler is turned on (if not already running) to
raise the primary loop temperature.

The heat demand LED light when any of the
heating zones calls for heat. Then the “Heat
Demand” input causes the control to turn on the
secondary circulator and the Circ. LED.  The
boiler and its LED are not turned on until the
valve reaches 50% open.  When the 

SL

 tem-

perature is high enough to allow the modulation
valve to close down to 10% open, the boiler
output is turned off.  The control will keep the
boiler running for at least five minutes before the
boiler shuts off.

When the 

OA

 temperature reaches the room

setpoint temperature or warm weather shut-
down setting, the control will close the propor-
tional valve, turn off the circulator and the boiler,
and turn on the warm weather shut down LED.

At anytime during setup or operation, an error
caused by a faulty sensor will be indicated on
the display by the sensor name (

OA

/

PL

/

SL

),

Err

”, and whether the sensor is open (

Opn

) or

shorted (

Sht

).  The test mode allows the inputs

and outputs to be checked for proper operation.

Temperature Setting Guidelines

OAL:

The outside design temperature should
be set according to the standard design
temperature for the geographic area.

OAH:

The warm weather shutdown tempera-
ture should be set to the average ther-
mostat setpoint temperature.  This will
also be the outdoor temperature at
which no heat is desired.

Summary of Contents for A3091000

Page 1: ...is compatible with other types of hydronic heat distribution systems where the use of a weather responsive control is desired Installation and Operating Instructions Features Provides outdoor reset co...

Page 2: ...warmer the desired water tem perature The SL sensor provides feedback for the control loop To provide the proper temperature in the radiant loop the control positions the valve using a proportional in...

Page 3: ...ete Design Assistance Manual SLH setting should never exceed the recommended water temperatures for the method in which the tubing is installed SLL The minimum radiant loop temperature should be set t...

Page 4: ...with 18 22 AWG wire 4 Wire the control as indicated by the termi nal block labels or by the wiring schematic provided in Section 6 Be sure to provide an earth ground to the case 5 The ProMIX 101 Contr...

Page 5: ...op High Max Radiant Loop Temp potentiometer adjustable Secondary Loop Low Min Radiant Loop Temp potentiometer adjustable Outdoor Air Temperature Current Outdoor Temp sensor input Primary Loop Temperat...

Page 6: ...SLL SLS SLH F range C range Open sensor error Shorted sensor error Circulator boiler off valve closed blank if below 15 0 VAC OA 60 122 51 50 Err OPn Err Sht PL 32 221 0 105 Err OPn Err Sht SLS 65 110...

Page 7: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 7 Typical Piping Arrangement using the Wirsbo ProMIX 101 Controller A B...

Page 8: ...Heating Reset Control 8 Typical wiring using the ProMIX 101 Controller and a Wirsbo DT10 Thermostat Typical wiring using the ProMIX 101 Controller Wirsbo Zone Control Module and a Single Pump Relay to...

Page 9: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 9 Typical wiring using the ProMIX 101 Controller with Wirsbo Zone Control Module...

Page 10: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 10 Typical wiring using the ProMIX Controller Wirsbo Zone Control Module and Multiple Pump Relay...

Page 11: ...mperature is below OAL the SL temperature should be at its maximum SLH should not be increased above the maximum tempera ture limitation for the installation method 4 If the heat output is excessive a...

Page 12: ...rculator N O relay contact switched line 12 22 AWG copper wire only HP 120 VAC Full Load 7 4 A Locked Rotor 43 2 A Resistive 10 A 3 Boiler Control Signal N O relay contract dry contacts limited to 18...

Reviews: