A3091000/A3091250
ProMIX™ 101 Radiant
Heating Reset Control
5
Power-up/Setup Display Sequence
This mode is entered on power-up or any time the Display or Reset Button is pressed while run-
ning. On power-up or reset, the settings scroll through automatically. To scroll manually, press the
Display button once. Then press it after each setting has been reviewed. If the display button is not
pressed for 60 seconds, the control will revert to scrolling automatically. All of the settings may be
adjusted while displayed.
Temperature Scale
(jumper-selectable)
Control Signal Output
(jumper-selectable)
Valve Action
(jumper-selectable)
Outdoor Air Low (Outdoor Design
Temperature) (potentiometer adjustable)
Outdoor Air High (Warm Weather Shutdown)
(potentiometer adjustable)
Primary Loop High (Minimum Return
Temperature) (potentiometer adjustable)
Secondary Loop High (Max. Radiant Loop
Temp.) (potentiometer adjustable)
Secondary Loop Low (Min. Radiant Loop
Temp.) (potentiometer adjustable)
Outdoor Air Temperature (Current Outdoor
Temp.) (sensor input)
Primary Loop Temperature (Current Return
Temp.) (sensor input)
Secondary Loop Temperature (Current Radiant
Temp.) (sensor input)
Continue in run mode
(if scrolling manually, press Display button to
continue)
Brief delay between modes
Fahrenheit
Celsius
0-10VDC
4-20mADC
Direct Acting closed at 0V, open at 10V)
Reverse Acting (closed at 10V, open at 0V)
°
F range
°
C range
°
F range (must be
≥
OAL+20)
°
C range (must be
≥
OAL+11)
°
F range
°
C range
°
F range
°
C range
°
F range (must be
≤
SLH-20)
°
C range (must be
≤
SLH-11)
°
F range
°
C range
Open sensor error
Shorted sensor error
°
F range
°
C range
Open sensor error
Shorted sensor error
°
F range
°
C range
Open sensor error
Shorted sensor error
t
°
F
°
C
Out
0.10
4.20
Act
dA
rA
OAL
-60..41
-51..5
OAH
40..70
4..21
PLL
60..150
15..65
SLH
85..200
29..93
SLL
65..110
18..43
OA
-60..122
-51..50
Err..OPn
Err..Sht
PL
32..221
0..105
Err...OPn
Err...Sht
SL
32..221
0..105
Err...OPn
Err...Sht
run
...