background image

A3091000/A3091250

ProMIX™ 101 Radiant

Heating Reset Control

6

Run Mode Display Sequence

This mode is entered automatically after the power-up/setup sequence. It continuously loops until a
button is pressed or power is lost.

Important: 

Any changes or adjustments made to the temperature or jumper settings are ignored

until the test/reset or display button is pressed.

Outdoor Air Temperature (Current Outdoor Temp.)
(sensor input)

Primary Loop Temperature (Current Return Temp.)
(sensor input)
(A flashing L appears after PL indicating Low return
temperature and boiler protection active)

Secondary Loop Setpoint (Calculated Radiant
Setpoint)

Secondary Loop Temperature (Current Radiant
Temperature) (sensor input)

LOW AC condition (24AC supply < 20.0 VAC)

°

F range

°

C range

Open sensor error
Shorted sensor erro

°

F range

°

C range

Open sensor error
Shorted sensor errore

°

F range (SLL

SLS

SLH)

°

C range (SLL

SLS

SLH)

°

F range

°

C range

Open sensor error
Shorted sensor error

Circulator & boiler off, valve closed.
(blank if below 15.0 VAC

OA

-60..122
-51..50
Err..OPn
Err..Sht

PL

32..221
0..105
Err...OPn
Err...Sht

SLS

65..110
18..93

SL

32..221
0..105
Err...OPn
Err...Sht

LO...AC...

15.0..19.9

Test Mode Display Sequence

This mode is accessed by holding the display button and pressing the Test/Reset button. The
sequence must be advanced manually by pressing the Display button after each step until the
setup mode is reached.

Display Test

24VAC Supply Voltage Test

Heat Demand (thermostat) Input Test

The thermostat or end switch may be cycled 
to verify proper operation

Circulator Output Test

Boiler Output Test

Warm Weather Shutdown (Outdoor Air Cutoff)
LED Test

DC Output (Valve Control) Test

Continue in setup mode

Open contact, Heat Demand LED off
Closed contact, Heat DemandLED on

Relay, circulator, and Circ. LED on

Relay, boiler, and Boiler LED on

Relay, boiler, and WWSD LED on

DC output ramps from 0-10V repeatedly

See Power-up/Setup Display Sequence

8.8.8

AC

15.0..30.0

ES

off
on

crc

on

blr

on

OAC

on

dc

0..10.0

t

Summary of Contents for A3091000

Page 1: ...is compatible with other types of hydronic heat distribution systems where the use of a weather responsive control is desired Installation and Operating Instructions Features Provides outdoor reset co...

Page 2: ...warmer the desired water tem perature The SL sensor provides feedback for the control loop To provide the proper temperature in the radiant loop the control positions the valve using a proportional in...

Page 3: ...ete Design Assistance Manual SLH setting should never exceed the recommended water temperatures for the method in which the tubing is installed SLL The minimum radiant loop temperature should be set t...

Page 4: ...with 18 22 AWG wire 4 Wire the control as indicated by the termi nal block labels or by the wiring schematic provided in Section 6 Be sure to provide an earth ground to the case 5 The ProMIX 101 Contr...

Page 5: ...op High Max Radiant Loop Temp potentiometer adjustable Secondary Loop Low Min Radiant Loop Temp potentiometer adjustable Outdoor Air Temperature Current Outdoor Temp sensor input Primary Loop Temperat...

Page 6: ...SLL SLS SLH F range C range Open sensor error Shorted sensor error Circulator boiler off valve closed blank if below 15 0 VAC OA 60 122 51 50 Err OPn Err Sht PL 32 221 0 105 Err OPn Err Sht SLS 65 110...

Page 7: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 7 Typical Piping Arrangement using the Wirsbo ProMIX 101 Controller A B...

Page 8: ...Heating Reset Control 8 Typical wiring using the ProMIX 101 Controller and a Wirsbo DT10 Thermostat Typical wiring using the ProMIX 101 Controller Wirsbo Zone Control Module and a Single Pump Relay to...

Page 9: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 9 Typical wiring using the ProMIX 101 Controller with Wirsbo Zone Control Module...

Page 10: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 10 Typical wiring using the ProMIX Controller Wirsbo Zone Control Module and Multiple Pump Relay...

Page 11: ...mperature is below OAL the SL temperature should be at its maximum SLH should not be increased above the maximum tempera ture limitation for the installation method 4 If the heat output is excessive a...

Page 12: ...rculator N O relay contact switched line 12 22 AWG copper wire only HP 120 VAC Full Load 7 4 A Locked Rotor 43 2 A Resistive 10 A 3 Boiler Control Signal N O relay contract dry contacts limited to 18...

Reviews: