cyber
®
simco
®
drive 2 operating manual
Revision: 02
5022-D057946
en-29
de
utsch
english
fra
nçais
ita
lia
no
es
pa
ñol
日本語
6.5.6 X5: Digital inputs and outputs
An external reference potential must be connected to supply the digital inputs.
The digital inputs are galvanically isolated from the logic and power of the
drive amplifier.
An external power supply must be connected to supply the digital outputs.
The digital outputs are galvanically isolated from the logic and power of the
drive amplifier.
The digital outputs are short-circuit proof.
Figure
Pin
no.
Signal
name
Function
Input /
output
6
DIN1
Digital input 1
Input
1
DIN2
Digital input 2
Input
8
DIN3
Digital input 3
Input
2
DIN4
Digital input 4
Input
7
GND
Ground reference
3
DOUT1
Digital output 1
Output
4
DOUT2
Digital output 2
Output
5
VCC24
Digital output
supply
Input
Plug type on drive amplifier: M12 8-pin, male, A-coded
Connection Feature
Unit
Minimum
value
Nominal
value
Maximum
value
DINx
Input voltage
V DC
20
24
28
Input current
mA DC
3
4
5
Input resistance
kOhm
5.6
Sample time
msec
1
DOUTx
Output voltage
V DC
18
24
26
Output current
mA DC
40
Output resistance
kOhm
1
1.5
2
Refresh rate
Hz
1
VCC24
Voltage
V DC
20
24
28
Current
mA DC
80
GND
Ground reference