Handling
•
Hold the bared con-
ductor against the
terminal.
•
Force down the spring
and push the con-
ductor into the termi-
nal.
•
Relieve the spring -
the conductor is secu-
rely clamped
Cable cross-section required:
The currents specified under the machine
data for the series WSG-08 refer to duty
type S3-40%. This must be taken into
account when selecting the cable cross-sec-
tion required. The continuous Ir.m.s. value
required for the selected cable is approxi-
mated from:
I
r.m.s. (cable)
»
I
N (motor, S3-40%)
/ 1.58
The following table gives the recommended values for
the current-carrying capacity of PVC cables at a maxi-
mum ambient temperature of 40 °C:
Handling the terminal strip
Cable cross-
section
Permissible max.
current
(r.m.s. value)
Permissible max.
motor current I
N
(S3 - 40%)
1.0 mm
2
13.1 A
20.7 A
1.5 mm
2
15.7 A
24.8 A
2.5 mm
2
22.6 A
35.7 A
4.0 mm
2
29.6 A
46.7 A
6.0 mm
2
38.3 A
60.5 A
Note
Motor connection diagram
W1 V1
U1
2 1
M
M 20
für Kabeldurchmesser
7-12 mm
M 20
for cable diameter
7-12 mm
Drillingskaltleiter
triplet PTC
Typ STM-150.DS....
PTC-thermistor
The thermocouples installed in the winding
such as PTC thermistor detectors and ther-
mostatic switches must be evaluated in the
control system or frequency converter to
protect the motor from overtemperature.
The operating voltage of the PTC thermis-
tors is not allowed to exceed 25 V DC.
Caution
3 x 4000
3 x 1330
3 x 550
3 x 250
-20°C
130°C
145°C
150°C
W
id
e
r
s
t
a
n
d
/
R
e
s
is
t
a
n
c
e
[
Ω
]
Temperatur
155°C
165°C
I
N Motor
für Kabel-
Æ
for cable dia.
< 26 A
M 32
13-20 mm
26...45 A
M 32
18-25 mm
> 45 A
M 40
22-32 mm