Electrical installation
INTORQ | BA 14.0177 | 04/2016
20
5
Electrical installation
5.1
Electrical connection
Switching on
❚
K2 must be closed prior to K1!
Switching off
❚
Normal (AC switching)
-
K2 remains closed
-
Open K1
❚
Emergency stop (DC switching)
-
K1 and K2 are opened at the same time
Fig. 5
Connection diagram for the BFK466 (circuit proposal for DC switching)
DANGER
There is a risk of injury by electrical shock!
❚
Perform electrical connection only when no voltage is applied.
❚
If an emergency stop is carried out without the required suppressor circuit, the control unit
may be destroyed. Observe the correct polarity of the suppressor circuit!
230V AC
L1
N
K1
K2
Bremse
1
2 3 4 5 6
BY255
2x1.5KE250A
bl
sw
Brake
Check the
polarity