32
www
.wittur
.com
Changes can be made without notice
PM.2.004923.EN - 811-000-000 SDS
©
DC-PWM Compatible · Edition 22 July 2020
Drive - Instruction Manual
11
UPGRADE FROM CONTROLLERS PREVIOUS TO F28/F29 CONTROLLER (CONTROLLER TYPE: ASC 10/20, ADC10/11, SEM10/11, LMDC 10/11) F28/29 B
•
Eliminate the transformer 220/24 V with all its cables because the new SDS is fitted with an in-built switching transformer
•
Cut the old terminal connection because the new connector is provided with cables with screws
•
The wires (numbered) must be stripped and wired into the four connectors of the compatible SDS Controller following the
correspondence given in the underneath table:
•
Connect the 220 Vac input to the SDS controller by means of the feeding cable supplied code no. E066AAWX-A
•
Select option EMULATION F28 or EMULATION F29 from the Menu General Option (see chapter 8.10) or programm parameter 22
using the keys on the frontal panel (01 o 02, see also
“5.3 Programming Mode “PROG”” a pag. 17
).
•
Check the correct functioning
CONNECTOR
FUNCTION
SEMATIC SDS Rel. 3
DC COMPATIBILE
1
IM reversing system N/C signal
1
2
IM reversing system N/O signal
2
3
Kc closing control
3
4
IM reversing system COM
4
5
Ka opening control
5
6
Ra and Rc opening and closing slow down COM
15
7
24 Vac power
NOT CONNECTED
8
24 Vac power
NOT CONNECTED
9
motor power
43
10
motor power
44
11
Ra opening slow down Input signal
41
12
NOT CONNECTED
13
Rc closing slow down Input signal
42
14
NOT CONNECTED
15
24 Vdc COM
15
OPERATOR TERMINALS
FUNCTION
SEMATIC SDS Rel. 3
DC COMPATIBILE
16 OUT
La Opening limit switch output contact (to the main lift controller)
16
17 OUT
La Opening limit switch output contact (to the main lift controller)
17
18 OUT
Lc Closing limit switch output contact (to the main lift controller)
18
19 OUT
Lc Closing limit switch output contact (to the main lift controller)
19
MAGNETIC BISTABLE
SWITCHES FOR OPENING AND
CLOSING LIMITS
FUNCTION
SEMATIC SDS Rel. 3
DC COMPATIBILE
16 IN
La Opening limit switch input contact (from the magnetic switch)
40
17 IN
La Opening limit switch COM (from the magnetic switch)
15
18 IN
Lc Closing limit switch input contact (from the magnetic switch)
39
19 IN
Lc Closing limit switch output contact (to the main lift controller)
15
Warning!
If in the old drive the magnetic switches
La
-Opening Limit and
Lc
-Closing Limit are directly connected to the main lift controller,
disconnect and re-connect them at the new SDS Rel.3 DC COMPATIBILE controller 39 - 15 - 40 - 15 input terminals (as shown in
the table). Connect SDS Rel. 3 DC COMPATIBILE La and Lc outputs to the main lift controller, at terminals 16 - 17 - 18 - 19.