32 

www

.wittur

.com

Changes can be made without notice

 PM.2.004923.EN - 811-000-000 SDS

©

 DC-PWM Compatible · Edition 22 July 2020

Drive - Instruction Manual

11 

UPGRADE FROM CONTROLLERS PREVIOUS TO F28/F29 CONTROLLER (CONTROLLER TYPE: ASC 10/20, ADC10/11, SEM10/11, LMDC 10/11) F28/29 B

• 

Eliminate the transformer 220/24 V with all its cables because the new SDS is fitted with an in-built switching transformer

• 

Cut the old terminal connection because the new connector is provided with cables with screws

• 

The wires (numbered) must be stripped and wired into the four connectors of the compatible SDS Controller following the 

correspondence given in the underneath table:

• 

Connect  the 220 Vac input to the SDS controller by means of the feeding cable  supplied code no. E066AAWX-A

• 

Select option EMULATION F28 or EMULATION F29 from the Menu General Option (see chapter 8.10) or programm parameter 22 

using the keys on the frontal panel (01 o 02, see also 

“5.3 Programming Mode “PROG”” a pag. 17

).

• 

Check the correct functioning

CONNECTOR

FUNCTION

SEMATIC SDS Rel. 3

 DC COMPATIBILE

1

IM reversing system N/C signal 

1

2

IM reversing system N/O signal 

2

3

Kc closing control

3

4

IM reversing system COM

4

5

Ka opening control

5

6

Ra and Rc opening and closing slow down COM

15

7

24 Vac power

NOT CONNECTED

8

24 Vac power

NOT CONNECTED

9

motor power

43

10

motor power

44

11

Ra opening slow down Input signal

41

12

NOT CONNECTED

13

Rc closing slow down Input signal

42

14

NOT CONNECTED

15

24 Vdc COM

15

OPERATOR TERMINALS

FUNCTION

SEMATIC SDS Rel. 3

 DC COMPATIBILE

16 OUT

La Opening limit switch output contact (to the main lift controller)

16

17 OUT

La Opening limit switch output contact (to the main lift controller)

17

18 OUT

Lc Closing limit switch output contact (to the main lift controller)

18

19 OUT

Lc Closing limit switch output contact (to the main lift controller)

19

MAGNETIC BISTABLE 

SWITCHES FOR OPENING AND

CLOSING LIMITS

FUNCTION

SEMATIC SDS Rel. 3

 DC COMPATIBILE

16 IN

La Opening limit switch input contact (from the magnetic switch)

40

17 IN

La Opening limit switch COM (from the magnetic switch)

15

18 IN

Lc Closing limit switch input contact (from the magnetic switch)

39

19  IN

Lc Closing  limit switch output contact (to the main lift controller)

15

Warning!

If in the old drive the magnetic switches 

La

-Opening Limit and 

Lc

-Closing Limit are directly connected to the main lift controller, 

disconnect and re-connect them at the new SDS Rel.3 DC COMPATIBILE controller 39 - 15 - 40 - 15 input terminals (as shown in 

the table). Connect SDS Rel. 3 DC COMPATIBILE La and Lc outputs to the main lift controller, at terminals 16 - 17 - 18 - 19.

Summary of Contents for sematic DC-PWM Compatible

Page 1: ...com Copyright WITTUR 2020 SDS Drive DC PWM Compatible No part of this publication may be reproduced or translated even in part without prior written permission from WITTUR Subject to change without no...

Page 2: ......

Page 3: ...ches 16 5 Instruction without handset 17 5 1 Automatic Mode AUTO 17 5 2 Manual Mode MAN 17 5 3 Programming Mode PROG 17 6 Functions available 19 6 1 Reversing system force setting 19 6 2 Reversing Sys...

Page 4: ...ntroller Alarm MLC Input Alarm 27 8 5 Limited door reversal Activation by means of the handset 27 8 6 Activation of the Car Door Locking Device setting by means of the Handset 28 8 7 Activation of the...

Page 5: ...System shall not be disclosed to anyone without Sematic s written consent apart from authorized representatives employed by the user which commits itself to the confidentiality clause The Company tha...

Page 6: ...PONENT SYSTEMS Automatic lift doors Frame and frameless glass doors Enhanced car door operator solutions Complete cabins Car Frames Custom integrated packages Special lift doors cabins and car frames...

Page 7: ...since the following conditions have not been ensured 1 Quality control of raw material supply 2 Process control 3 Product control 4 Conformity tests according to Sematic specifications Furthermore Sem...

Page 8: ...fied by means of the door controller push buttons or by means of the Sematic handset an optional 8 digit keypad and display accessory which can be connected to the card by an RJ45 plug The handset 6 i...

Page 9: ...e Instruction Manual 2 1 SPEED PROFILE Opening cycle O1 Opening acceleration O2 Opening hight speed O3 Opening deceleration Closing cycle C1 Closing acceleration C2 Closing hight speed C3 Closing dece...

Page 10: ...x20 4 A battery fuse 5x20 8 A PERFORMANCE SPEED separately adjustable for opening and closing REVERSAL SENSITIVITY Variable only operational on door closing cycle 3 2 SEMATIC DRIVE SYSTEM DOOR CONTROL...

Page 11: ...uly 2020 Drive Instruction Manual 4 SIGNALS TO FROM THE DOOR CONTROLLER 4 1 SEMATIC DRIVE SYSTEM DC PWM COMPATIBLE CONNECTIONS DOOR POSITION LC SWITCH STATE RC SWITCH STATE RA SWITCH STATE LA SWITCH S...

Page 12: ...04923 EN 811 000 000 SDS DC PWM Compatible Edition 22 July 2020 Drive Instruction Manual 4 2 SEMATIC DRIVE SYSTEM SET UP AND INCOMING OUTGOING SIGNALS FROM THE DOOR CONTROLLER 1 Magnetic switches 2 Sa...

Page 13: ...ilures Re opening control Kn Connector pins 15 23 These connections require dry voltage free contacts both logics available See 4 1 4 2 for the connection to the door controller Closing limit switch c...

Page 14: ...istance has been achieved or as a Gong or Buzzer while the door is opening or as a Thermic alarm signal Contact rating 3A 250Vac 30Vdc Connector pins 35 36 contact normally closed Motor Connector pins...

Page 15: ...s through dummy connector pin for connections between the detector system components 1 Example of photocells barriers with transmitter and receiver connected between themselves through the dummy free...

Page 16: ...are the operations of the magnetic switches Closed door the door close limit pre adjusted by the manufacturer must operate when the carriage has already stopped but the retractable skate is not close...

Page 17: ...3 sec the Door Controller switches to the automatic mode AUTO If no keys are pressed for at least 10 minutes the Door Controller will switch to the automatic mode AUTO Both in automatic and manual mo...

Page 18: ...t Relay 00 01 02 03 00 Off 01 Gong While opening 02 According to of space 03 Termic Alarm signal 08 00 Space Percentage Percentage of the available space o operate the AUX relay 00 99 00 99 00 closing...

Page 19: ...or this setting the main lift controller must be equipped with 2 relays 1 for the opening command and 1 for the closing command The Door Controller checks for continuous presence of the Ka and Kc sign...

Page 20: ...d to 23 and 15 terminals 31 and 32 terminal must be shorted 6 10 EMULATION TYPE SDS DC COMPATIBLE controller may replace different kind of old controllers Usig this parameter is possible to select req...

Page 21: ...r cables Note 4 Auto reset after 5 seconds after 5 occurrences within 5 minutes the system stops 08 Over voltage Over voltage in the power supply Door controller switches to low speed signals the erro...

Page 22: ...cod B147AABX see picture 3 a 16 mm diameter hole is required in any chosen position within the Car walls Note when the handset is connected to the controller the display shows the warrantly expiration...

Page 23: ...wittur com Changes can be made without notice PM 2 004923 EN 811 000 000 SDS DC PWM Compatible Edition 22 July 2020 Drive Instruction Manual 7 2 USER HANDSET MENUS AND SUBMENUS only for Digidoor Emul...

Page 24: ...tings This option allows to easily and quickly modify the speed profiles Choose this option as indicated in the first part of 8 5 Limited door reversal Activation by means of the handset a pag 27 The...

Page 25: ...ailable BACK press key F1 to restore the MAIN MENU F2 KEY to open and close the door to test the modified profile DRAW press key F3 to update the speed profile drawing 7 5 2 Option Closing Parameters...

Page 26: ...t Only for digidoor emulation This option allows the user to change the closing rest current delay from the closing limit Lc signal The setted time starts from the Lc switch signal Select the desired...

Page 27: ...for the meaning of this parameter Using keys and run through the GENERAL OPTIONS and choose the option MAIN LIFT CONTROLLER TEST Press the OK key to confirm the choice The following options are viewe...

Page 28: ...ay shows the confirmed option and restores the menu GENERAL OPTIONS The following options are available BACK Press key F1 to restore the menu GENERAL OPTIONS MENU Press key F3 to restore the MAIN MENU...

Page 29: ...l The following options are viewed on the display Emulation F28 Emulation F29 Emulation DIGIDOOR 1Nm Emulation DIGIDOOR 2Nm Emulation LM DC 2010 Emulation LM DC 2011 Using keys and choose the required...

Page 30: ...on and time of occurrence day hour minute from the door controller start up Using keys and run through the stored alarm list The following options are available BACK Press key F1 to restore the menu M...

Page 31: ...Press OK to confirm the choice Display shows the last available update and the software version in use at the moment Press OK to confirm the software update Controller operates a reset and the display...

Page 32: ...a and Rc opening and closing slow down COM 15 7 24 Vac power NOT CONNECTED 8 24 Vac power NOT CONNECTED 9 motor power 43 10 motor power 44 11 Ra opening slow down Input signal 41 12 NOT CONNECTED 13 R...

Page 33: ...common line for LA and LC switches is different depending on the MLC Es MLC type 1BN H PA Common line 48V MLC type 1BN L PA Common line 0V 7 MAIN LIFT CONTROLLER HMPU 8 Magnetic switches installed on...

Page 34: ...20 Drive Instruction Manual 12 UPGRADE FROM F28 F29 AND LMDC 2010 2011 DIGIDOOR Short instruction replacement F28 F29 and LMDC 2010 2011 DIGIDOOR 01 F28 03 Digidoor 1 Nm 05 LMDC 2010 02 F29 04 Digidoo...

Page 35: ...28 29C TERMINALS FUNCTION SEMATIC SDS Rel 3 DC COMPATIBILE 1 IM reversing system N C signal 1 2 IM reversing system N O signal 2 4 IM reversing system COM signal 4 3 Kc closing control 3 5 Ka opening...

Page 36: ...h COM from the magnetic switch 15 18 IN Lc Closing limit switch input contact from the magnetic switch 39 19 IN La Closing limit switch COM from the magnetic switch 15 Warning If in the old drive F28...

Page 37: ...G a pag 17 Check the correct functioning F28 29 Rel 2 0 TERMINALS FUNCTION SEMATIC SDS Rel 3 DC COMPATIBILE 1 IM reversing system N C signal 1 2 IM reversing system N O signal 2 4 IM reversing system...

Page 38: ...X A Select option EMULATION LM DC 2010 or EMULATION LM DC 2011 from the Menu General Option see 8 10 Emulation Type a pag 28 or programm parameter 22 using the keys on the frontal panel 05 o 06 see al...

Page 39: ...derneath table Connect the 220 Vac input to the SDS controller by means of the feeding cable supplied code no E066AAWX A Select option EMULATION DIGIDOOR 1Nm or EMULATION DIGIDOOR 2Nm from the Menu Ge...

Page 40: ...door operator toothed belt is tight enough and in good working condition Check and clean the cable connections of the motor and of the motor Encoder 18 SPARE PARTS It is possible to order all the Sem...

Page 41: ......

Page 42: ...YOUR GLOBAL PARTNER FOR COMPONENTS MODULES AND SYSTEMS IN THE ELEVATOR INDUSTRY More information about Wittur Group available on line a WITTUR brand a WITTUR brand a WITTUR brand...

Reviews: