Page 30 / 68
©
Wodtke GmbH - Tübingen. All Rights and Changes Reserved.Printed 04/2015
Part No. 950 976
10
Fire Safety Regulations
Attention:
All flammable components, furniture or furnishing
fabrics, for example, in the immediate vicinity of
the furnace must be protected against the effects
of heat. In particular, the applicable local fire safety
regulations and provisions must be observed.
The following fire safety clearances must be
maintained at minimum:
Di-
men-
sion
Value Explanation
A
80
cm
Minimum distance in radiation
area / to hot air outlets
B
40
cm
Minimum distance in radiation
area / to hot air outlets with
ventilated radiation protection
Di-
men-
sion
Value
Explanation
C
20
cm
or
15
cm
Minimum clearance
outside the
radiation area
and
outside the
area of hot air outlets:
to the rear: 20 cm
to the sides: 15 cm
D
Minimum clearance of flue pipe
to flammable components ac-
cording to specifications of the
flue pipe manufacturer
E
5 cm
Minimum clearance of flue pipe
to rear furnace wall.
F
20
cm
Minimum thickness of non-flam-
mable, dimensionally stable
thermal insulation in the perime-
ter of the flue pipe or clearance
of a protective tube to the flue
pipe in case of lead-through in a
wall with flammable components
No
Fig.
100
cm
A minimum clearance to compo-
nents / objects to be protected of
100 cm is required above the
furnace.
Example with connector piece to chimney
within the installation room
Fig. 55: fire safety clearances
Example with connector piece through wall with
flammable components to chimney
Fireproof
surface /
floor plate
Connector piece
Clearance
E
Ventilated radiation protection