Specifications
13
4 Specifications
4.1 Measurement values
Differential pressure
Range
-100 .. 100 Pa
Resolution
0.1 Pa
Accuracy
Max of 0.25 Pa or 1%
of measurement
Air flow rate at 50 Pa (extrapolited)
Range
15 .. 6000 m³/h
Resolution
0.1 m³/h
Accuracy
+/- 5% or 1.5 m³/h
(the respective higher
value applies)
Air temperature
Range
-20 .. 50 °C
Resolution
0.1 °C
Accuracy
+/- 0.5 °C
Absolute pressure
Range
300 .. 1200 hPa
Resolution
0.1 hPa
Accuracy
+/- 3 hPa
Relative humidity
Range
20 .. 80% RH
Resolution
0.1% RH
Accuracy
+/- 5% RH