Wolf Cooktop Ventilation Hoods
HOOD PLACEMENT
Installation of the cooktop wall or island hood should be
24"
(610)
to 30"
(762)
from the bottom of the hood to the
countertop. To determine placement of the cooktop hood,
you must calculate the height of the telescopic chimney
flue. The minimum and maximum flue extension for each
cooktop hood is listed in the charts below.
IMPORTANT NOTE:
Both sections of the telescopic
chimney flue must be installed in order for the chimney to
be lifted for service.
Wolf Cooktop Ventilation
15
wolfappliance.com/specs
B
A
C
D
MINIMUM
FLUE
EXTENSION
Cooktop hood placement.
Cooktop Chimney Hoods
FLUE EXTENSION
MINIMUM
MAXIMUM
CTWH30
30
1
/
2
"
(775)
48
1
/
2
"
(1232)
CTWH36
32
5
/
8
"
(829)
50
7
/
8
"
(1292)
IH4227
33
1
/
2
"
(851)
47"
(1194)
Cooktop Low-Profile Hoods
FLUE EXTENSION
MINIMUM
MAXIMUM
CTEWH30I
29
1
/
8
"
(740)
41
1
/
2
"
(1054)
CTEWH36(I)
29
1
/
8
"
(740)
41
1
/
2
"
(1054)
CTEWH45(I)
29
1
/
8
"
(740)
41
1
/
2
"
(1054)
CTEIH42I
28
1
/
4
"
(718)
41
1
/
2
"
(1054)
CALCULATE CHIMNEY FLUE HEIGHT
A)
Height from finished floor to finished ceiling. 8'
(2.4 m)
or 9'
(2.7 m)
ceilings are typical.
B)
Height from finished floor to countertop. A 36"
(914)
countertop height is standard.
C)
Hood mounting height (bottom of hood to countertop).
Dimension C must be between 24"
(610)
and 30"
(762)
.
8'
(2.4 m)
ceilings may not allow the maximum 30"
(762)
hood mounting height.
D)
Calculate chimney flue height: D = A – (B + C).
Dimension D must be between the minimum and
maximum flue extension listed in the charts. Refer to
the illustration below.