Planning Information

A minimum 2"

 (51)

 is required from the bottom of the module 

to combustible materials.  

ELECTRICAL

Installation must comply with all applicable electrical codes.

Locate the electrical supply as shown in the illustrations on 
the following pages. A separate circuit, servicing only this 
appliance is required.

When multiple cooktops or modules are installed side by 
side, each must have its own separate electrical supply.

ELECTRICAL REQUIREMENTS

ELECTRIC MODULES

Electrical Supply

grounded 3-wire, 240/208 VAC, 60 Hz

Steamer

15 amp dedicated circuit

Fryer, Grill, Teppanyaki

20 amp dedicated circuit

Conduit

flexible 4'

 (1.2 m)

GAS MULTIFUNCTION

Electrical Supply

grounded, 120 VAC, 60 Hz

Service

15 amp dedicated circuit

Receptacle

3-prong grounding-type

Power Cord

6'

 (1.8 m)

INTEGRATED MODULES

DRAIN OUTLET

Steamer and fryer modules require a method for draining 
hot water and oil. For the steamer module, options include 
connecting a drain hose from the 

5

/

8

"

 (16)

 outlet tied into 

an existing drain, a separate drain with freefall or placing a 
heat-resistant receptacle under the drain outlet. For the fryer 
module, the drain outlet must be accessible to drain oil into 
a heat-resistant receptacle. 

Summary of Contents for CG243TF

Page 1: ...Wolf New Generation Design Guide REVISED 2 2016 ...

Page 2: ...12 Wolf Customer Care 800 222 7820 ...

Page 3: ...emporary gas cooktop The cooking surface fits flush to the countertop for a striking low profile look Front mounted controls integrate directly into cabinetry below With a choice of knob colors the new contemporary gas cooktop offers exceptional design flexibility Performance enhancements make delicious results even more of a certainty than ever CG365C S GAS COOKTOP CONTEMPORARY ...

Page 4: ...6 CONTEMPORARY 3515 16 913 2015 16 532 7 8 22 63 4 171 VENTILATION OUTDOOR GRILLS RANGES RANGETOPS COOKTOPS COFFEE BUILT IN OVENS BURNER RATING Btu kW 36 CONTEMPORARY SIM HI 20K Burner 300 1 20 000 5 9 12K Burner 2 300 1 12 000 3 5 9 2K Burner 2 300 1 9 200 2 7 ...

Page 5: ...nly this appliance is required A ground fault circuit interrupter GFCI is not recommended and may cause interruption of operation ELECTRICAL REQUIREMENTS Electrical Supply grounded 120 VAC 60 Hz Service 15 amp dedicated circuit Receptacle 3 prong grounding type Power Cord 6 1 8 m GAS SUPPLY Installation must conform with all applicable gas codes A gas supply line of 3 4 19 rigid pipe must be provi...

Page 6: ... above countertop indicates minimum clearance to combustible surfaces combustible materials cannot be located within this area Maximum facade thickness 1 25 Outside corner radius 3 8 10 30 762 13 330 18 457 9 229 E G 36 914 MIN RECESS 21 533 MIN RECESS 35 889 CUT OUT WIDTH COUNTERTOP CUT OUT 20 508 21 2 64 5 64 2 1 2 13 MAX COUNTERTOP PROFILE 5 127 C L 10 254 11 4 32 DIAMETER 4 102 C L 3 76 MIN 5 ...

Page 7: ...wolfappliance com 17 GAS COOKTOP BUILT IN OVENS COOKTOPS COFFEE RANGES RANGETOPS OUTDOOR GRILLS VENTILATION ...

Page 8: ......

Page 9: ...ed lines of Sub Zero and Wolf Controls grates and trim allow them to integrate perfectly with their larger counterparts and deliver equal performance INTEGRATED MODULES GM15 S Grill FM15 S Fryer SM15 S Steamer TM15 S Teppanyaki MM15 S Multifunction BUILT IN OVENS COOKTOPS COFFEE RANGES RANGETOPS OUTDOOR GRILLS VENTILATION ...

Page 10: ...81 21 533 83 4 222 7 8 22 4 102 DRAIN OUTLET Integrated Modules STEAMER FRYER GRILL INTEGRATED MODULES TEPPANYAKI VENTILATION OUTDOOR GRILLS RANGES RANGETOPS COOKTOPS COFFEE BUILT IN OVENS BURNER RATING Btu kW MULTIFUNCTION MAX Burner 22 000 6 5 15 381 21 533 7 8 22 5 127 MULTIFUNCTION 15 381 21 533 7 8 22 61 2 165 ...

Page 11: ...REMENTS ELECTRIC MODULES Electrical Supply grounded 3 wire 240 208 VAC 60 Hz Steamer 15 amp dedicated circuit Fryer Grill Teppanyaki 20 amp dedicated circuit Conduit flexible 4 1 2 m GAS MULTIFUNCTION Electrical Supply grounded 120 VAC 60 Hz Service 15 amp dedicated circuit Receptacle 3 prong grounding type Power Cord 6 1 8 m INTEGRATED MODULES DRAIN OUTLET Steamer and fryer modules require a meth...

Page 12: ...the gas multifunction cooktop If local codes permit a certified 3 9 m long 1 2 13 or 3 4 19 ID flexible metal appliance connector is recommended to connect the units 1 2 NPT male inlet to the gas supply line When multiple gas cooktops or modules are installed side by side they can receive their gas supply from a common line However each unit must have its own regulator installed between the mainli...

Page 13: ...ed area above countertop indicates minimum clearance to combustible surfaces combustible materials cannot be located within this area FRONT VIEW SIDE VIEW COUNTERTOP CUT OUT 13 330 18 457 7 178 E 30 762 75 8 194 6 152 123 8 314 DRAIN OUTLET 191 2 495 21 2 64 min 21 2 64 min 14 356 WARNING The steamer module must be installed at least 15 381 from a fryer module ...

Page 14: ...ea above countertop indicates minimum clearance to combustible surfaces combustible materials cannot be located within this area 13 330 18 457 7 178 E 30 762 75 8 194 6 152 123 8 314 DRAIN OUTLET 191 2 495 21 2 64 min 21 2 64 min 14 356 Fryer Module STANDARD INSTALLATION WARNING The fryer module must be installed at least 15 381 from any open flame cooking device or a steamer module ...

Page 15: ...ODULES Grill and Teppanyaki Modules STANDARD INSTALLATION 191 2 495 21 2 64 min 21 2 64 min FRONT VIEW SIDE VIEW COUNTERTOP CUT OUT NOTE Shaded area above countertop indicates minimum clearance to combustible surfaces combustible materials cannot be located within this area 13 330 18 457 7 178 30 762 E 14 356 ...

Page 16: ...b Zero Inc All other trademarks or registered trademarks are property of their respective owners in the United States and other countries VENTILATION OUTDOOR GRILLS RANGES RANGETOPS COOKTOPS COFFEE BUILT IN OVENS INTEGRATED MODULES Multifunction Cooktop STANDARD INSTALLATION FRONT VIEW SIDE VIEW COUNTERTOP CUT OUT NOTE Shaded area above countertop indicates minimum clearance to combustible surface...

Page 17: ...ANTY The warranty applies only to products installed for normal residential use The warranty applies only to products installed in any one of the fifty states of the United States the District of Columbia or the ten provinces of Canada This warranty does not cover any parts or labor to correct any defect caused by negligence accident or improper use maintenance installation service or repair THE R...

Page 18: ...WOLF APPLIANCE INC P O BOX 44848 MADISON WI 53744 WOLFAPPLIANCE COM 800 222 7820 ...

Reviews: