Commissioning
Saving energy
- Instruct the customer about energy-saving options.
- Refer your customer to section „Information regarding
energy-efficient operation“ in the operating instruc
-
tions.
- The illuminated ring shows a green colour, if the boiler starts
correctly.
- Instruct the customer in the operation of the boiler. Complete
the commissioning report and hand over the instructions to
the customer.
Setting the BUS address (only for MM with SCOM interface or cascade)
When operating several boilers (number of boilers >1) in conjunction with a cascade module, set the eBUS address of each boiler
in accordance with the table below.
BUS address setting:
Hold down the reset button; after 5 seconds, the corresponding flashing code will be displayed (see table). Select the corresponding
address with the DHW temperature rotary selector. Release the reset button again.
BUS address
DHW rotary selector position
Illuminated ring display
1
1
flashing red
2
2
flashing yellow
3
3
flashing yellow/red
4
4
flashing yellow/green
5
5
flashing green/red
0
6
flashing green (factory setting)
Illuminated ring
Fig.: Control unit overview