28
3061344_201509
Displaying/
modifying control parameters
The control parameter can be modified or displayed via controller with eBUS capability. For procedures, check the operating in-
structions of the relevant accessories.
To prevent damage to the heating system, cancel
night setback when outside temperatures fall
below -12 ° C. If this rule is not observed, ice
may form on the flue outlet which may result in
injury to individuals or material losses.
NB
Modifications must only the carried out by a
recognised heating contractor or by Wolf cu
-
stomer service.
Incorrect operation can lead to system faults.
Please note when using parameter GB 05 or
A09 (frost protection/outside temperature), that
frost protection is not safeguarded if you set
temperatures lower than 0 °C. This can lead to
heating system damage.
NB
NB
Settings of column 1 are suitable for control accessories ART and AWT.
Settings of column 2 are suitable for Wolf control systems with BM (programming unit)
1
2
Parameter
Unit
Factory
setting
min
max
GB01
HG01
Flow temperature hysteresis
K
8
5
30
HG02
Lower fan speed
Min. fan speed in %
%
CGB-11: 27
CGB-20: 27
CGB-24: 30
27
100
HG03
Upper fan speed DHW
Max. fan speed in % for DHW
%
CGB-11: 100
CGB-20: 100
CGB-24: 98
27
100
GB04
HG04
Upper fan speed central heating
Maximum fan speed in % for central heating
%
CGB-11: 70
CGB-20: 82
CGB-24: 82
27
100
GB05
A09
Frost protection outside temperature
With connected outside temperature sensor and
insufficient temperature pump ON
°C
2
-10
10
GB06
HG06
Heating circuit pump mode
0 → Pump ON in winter mode
1 → Pump ON when the burner is ON
0
0
1
GB07
HG07
Heating circuit pump run-on time
Heating circuit pump run-on time in heating mode in min.
Heating circuit pump run-on time in heating mode in min.
min
1
0
30
GB08
HG08 or
HG22
Maximum set flow temperature
Applies to heating mode
°C
80
40
90
GB09
HG09
Cycle block
applies to heating mode
min
7
1
30
HG10
e Bus address
Bus address of boiler (display only)
0
0
5
HG11
DHW quick start-up
Temperature of plate heat exchanger in summer mode
(suitable for combi-boilers only)
°C
10
10
60
HG12
Gas type
not assisted
0
0
1
GB13
HG13
Input E1
Input E1 (24 V)
Various functions can be allocated to input E1.
See chapter „Connection input E1“
1
Roomther-
mostat
0
5
GB14
HG14
Output A1 (230VAC)
Various functions can be allocated to output A1.
See chapter „Connection output A1“
6
Cylinder pri-
mary pump
0
9
GB15
HG15
DHW cylinder hysteresis
Switching differential for cylinder reheating
5
1
30
GB16
HG16
Minimum pump speed, heating mode
%
CGB-11: 27
CGB-20: 48
CGB-24: 48
20
100
GB17
HG17
Minimum pump speed, heating mode
%
CGB-11: 56
CGB-20: 77
CGB-24: 82
20
100
HG21
Minimum boiler water temperature TK-min
°C
20
20
90