29
3061344_201509
Adjusting the maximum output
CGB-11/CGB-20/CGB-K-20/CGB-24/CGB-K-24
Output setting (parameter GB04)
The output setting can be modified with Wolf control accessories with eBUS capability.
The heating output will be determined by the gas fan speed. By reducing the gas fan speed in accordance with the table, the
maximum output will be matched (at 80/60 °C) to natural gas H and LPG.
Limiting the maximum output relative to a flow/return temperature of 80/60 °C
Settings for parameter GB04 with Wolf connection accessories with eBUS capability in [%]
Maximum output in kW
25
5,0
4,0
3,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
16,0
17,0
18,0
19,0
20,0
21,0
22,0
23,0
24,0
25,0
30
35
40
45
50
55
60
65
70
75
80
85
CGB-1
1
CGB-24
CGB-20
Table: Output setting
CGB-24/CGB-K-24
Heating output
(kW) 7,1
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Display value
(%) 30
32
35
38
42
45
47
52
55
57
61
64
67
70
73
77
82
CGB-20/CGB-K-20
Heating output
(kW) 5,6
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Display value
(%)
27
29
33
37
41
45
49
54
57
62
66
70
74
78
82
CGB-11
Heating output
(kW) 3,3
4
5
6
7
8
9
10
Display value
(%)
26
29
35
42
49
56
63
70