48
3061344_201509
Maintenance
Test run
Completing the adjustments
- Reset the MCBs.
- pen the gas tap.
- Switch ON the boiler.
- Set the program selector to emissions test mode.
- Switch the boiler OFF and close the test ports and hose
nipples; check for leaks.
- Fit the casing.
Flue gas test
Re-adjust the CO
2
content, if required
(see next page)
Carrying out a ventilation test
Check LAF for soundness, if the CO
2
value >
0.2%.
Emissions test mode position